User's Manual

Setup
3A2960D 15
Cycle Mode: Pump ON
The display alternates between the number of cycles
remaining and indicates the amount of time remaining in
the pump cycle, counting down the Backup Pump ON
time value (see Cycle Mode (on:CY) ON Setup, page
11).
The Cycle ON LED illuminates and the pump output
is enabled as long as the system is in the Pump ON
state.
If the Input Cycle Switch is activated the amount of
times equal to the Cycle Definition variable before
the Backup Pump On Time expires, the system
switches to a Pump OFF state.
If the cycle switch is NOT activated the number of
times equal to the cycle definition variable before
the Backup Pump On Time expires the system
faults, goes to the Pump OFF state and pauses until
the Alarm is cleared.
Pump ON time is shown in MM:SS (minutes:sec-
onds)
Cycle Mode: Pump OFF
The display indicates the amount of time remaining in
the pump OFF cycle, counting down the Pump OFF time
value (see Programming OFF Time Duration, page 12).
The pump output is disabled during the Pump OFF
time.
The Time OFF LED illuminates as long as the sys-
tem is in the Pump OFF state.
Pump OFF time is shown in HH:MM (hours:minutes)
or MM:SS if the time remaining is less than an hour.
Timer Mode: Pump ON
The display indicates the amount of time remaining in
the pump cycle, counting down the Pump ON time value
(see Time Control (on:ti) ON Setup, page 12).
The Pump output is enabled.
Pump ON time is shown in MM:SS (minutes:sec-
onds).
Timer Mode: Pump OFF
The display indicates the amount of time remaining in
the pump OFF cycle, counting down the Pump OFF time
value (see Programming OFF Time Duration, page 12).
The Time OFF LED illuminates and the pump output
is disabled during the Pump OFF time.
Pump OFF time is shown in HH:MM (hours:minutes)
or MM:SS if the time remaining is less than an hour.
Alarm Operation
When an alarm situation occurs:
pump operation is immediately
disabled,
the front panel Alarm LED illuminates,
an error code displays
an audible alarm sounds
the alarm output contact activates
Press the Reset button once to clear
buzzer; press and hold for 3 seconds
to clear alarm and switch controller to
OFF MODE.
See Alarm Types and Messages Table, page 16 for
additional information related to alarms and alarm mes-
sages.