User's Manual

PNEUMATIC LUBE SENTRY VALVE
OPERATION: Initiate lubricant flow from the lube pump serving the
divider valve or pump to point system (until flow has been established,
the electric or pneumatic circuit to the Lube Sentry must be bypassed).
Lubricant passing through the hydraulic section of the valve (See Figure
1 or 2) from port (1) to port (2) moves to piston (3) in the direction of the
arrow. The actuator rod (4) is attached to piston (3) and simultaneously
moves in the same direction allowing the directional spool (5) in the air
valve of the Pneumatic Lube Sentry (See Figure 1) to permit air to flow
between port “A and port “C” or tripping the microswitch(es). (See Figure
2 Note 2 on the Electric Lube Sentry.) The Lube Sentry is now in a flow
position.
When lubricant flow stops, spring (6) returns piston (3) in the opposite
direction, closing the porting to the lube outlet (7). The lubricant ahead
of piston (3) is forced back through the adjustable needle valve (8) at a
controlled rate. As piston (3) returns to the right, the attached actuator rod
(4) moves the Pneumatic Lube Sentry directional spool (5) permitting air
to now flow between port “A and port “B” (See Figure 1), or changing the
position of the microswitch(es) (See Figure 2 Note 2) on the Electric Lube
Sentry. The Lube Sentry is now in a no-flow condition. Figure 1 shows a
typical no-flow position.
Adjusting needle valve (8) clockwise increases shutdown time. A
counterclockwise adjustment decreases the shutdown time.
Note 1: Pneumatic Valve Operation (During Lubricant Flow)
Figure 1. Pneumatic Lube Sentry Valve Figure 2. Electric Lube Sentry Valve
ELECTRIC LUBE SENTRY VALVE
Flow - Green Light - ON; Red Light - OFF
No-Flow - Red Light - ON; Green Light - OFF
Note 2:
FLOW CONDITION :
For Closed Contact: Use Red and Blue Wires (Red Common)
For Open Contact: Use Red and White Wires (Red Common)
NO-FLOW CONDITION:
For Open Contact: Use Red and Blue Wires (Red Common)
For Closed Contact: Use Red and White Wires (Red Common)
CAUTION: If only two of the three wires are used, tape un-used wire.
Pneumatic/Electric
Lube Sentry Valve
Operation Port “A Port “B” Port “C”
Norm. Open Air In Plugged Air Out
Norm. Closed Air Out Air In Plugged

Summary of content (4 pages)