Vent Fan (AUX Mode)
This mode is intended to operate a vent fan for a battery enclosure which helps ventilate hydrogen
gas from the enclosure. If the voltage remains above the threshold voltage set point, the vent fan will
remain active.
When the voltage falls back below the set point, the vent fan will continue for another 15 seconds,
then turn off.
Figure 20 Setting the Vent Fan Aux Mode
To set the mode for Vent Fan:
1. From the main menu, press <> or <> to move the
to the left of Aux.
2. Press <GO> to open the AUX MODE screen.
3. The Vent Fan screen should be the first default screen to
display. If any other mode screen is displayed, press
<NEXT> to cycle through the available modes until
Vent Fan is displayed again.
4. Press <MODE> to switch between ON, OFF, or AUTO.
ON activates the AUX output.
OFF deactivates the AUX output.
AUTO controls the output according to the criteria of
the selected AUX mode.
AUX MODE
Vent Fan
Output: Off Off
EXIT NEXT SET MODE
Charger Aux Light
EQ Misc Advanced
Logging Stats
EXIT GO
Main Menu
Charger Aux Light
EQ Misc Advanced
Logging Stats
EXIT GO
AUX MODE
Vent Fan
EXIT VOLT
VENT FAN VOLTS
> 14.4
BACK - +
AUX MODE
Vent Fan
Output: Off Off
EXIT NEXT SET MODE
<NEXT> advances to the
next AUX MODE screen.
To change the set points for Vent Fan:
1. Press <SET> to advance to the set point screen.
2. Press <VOLT> to advance to the VENT FAN VOLTS screen.
3. Press <-> or <+> to increase or decrease the value.
4. Press <BACK> to return to the Vent Fan set point screen.
5. Press <EXIT> to return to the AUX Mode screen.
To Exit:
Press <EXIT> once to return to the main menu.
Press <EXIT> twice to return to the status screen.