DC Inverter Series for R410A Unitary Split Air Conditioner
19
3.3.2 Electrical Parameters
Model Power supply
Fuse
capacity
(A)
Maximum
overcurrent
protection
(A)
Minimum
circuit
ampacity
(A)
208/230V-
1Ph-60Hz
35 35 24
208/230V-
1Ph-60Hz
45 45 35
3.3.3 Connection of Power Cords and Thermostat Wires
(1) For solid wires (as shown below):
1) Use wire cutters to cut off the wire end and then peel away about 25mm
of the insulation layer.
2) Use a screwdriver to unscrew the terminal screw on the terminal board.
3) Use nippers to bend the solid wire into a ring that fits the terminal screw.
4) Form a proper ring and then put it on the terminal board. Use a
screwdriver to tighten up the terminal screw.
(2) For stranded wires (as shown below):
1) Use wire cutters to cut off the wire end and then peel away about 10mm
of the insulation layer.
2) Use a screwdriver to unscrew the terminal screw on the terminal board.
3) Use a round terminal fastener or clamp to fix the round terminal firmly
on the peeled wire end.
4) Locate the round terminal conduit. Use a screwdriver to replace it and
tighten up the terminal screw (as shown below).
FLEXX36HP230V1AO
FLEXX60HP230V1AO