Instructions / Assembly

8
INSTALLATION SITE INSTRUCTIONS
Indoor Unit
Select a site that allows for the following:
1. Ensure the installation complies with the installation minimum dimensions (defined below)
and meets the minimum and maximum connecting piping length and maximum change in
elevation as defined in the System Requirements section.
2.
Air inlet and outlet will be clear of obstructions, ensuring proper airflow throughout the room.
3. Condensate can be easily and safely drained.
4. All connections can be easily made to outdoor unit.
5. Indoor unit is out of reach of children.
6.
A mounting wall strong enough to withstand four times the full weight and vibration of the unit.
7. Filter can be easily accessed for cleaning.
8. Leave enough free space to allow access for routine maintenance.
9. Install at least 10 ft. (3 m) away from the antenna of TV set or radio. Operation of the air
conditioner may interfere with radio or TV reception in areas where reception is weak.
An amplifier may be required for the affected device.
10. Do not install in a laundry room or by a swimming pool due to the corrosive environment.
Minimum Indoor clearances
6 in
(1500mm)
6 in
(1500mm)
6 ft (1.8m)
6 in (1500mm)
Ceiling
Floor