HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL Models: LIVV09HP230V1A LIVV18HP230V1A LIVV30HP230V1A LIVV12HP230V1A LIVV24HP230V1A LIVV36HP230V1A
Thank you for choosing a Livv Heat Pump for your customer. Please read this installation manual carefully before installing and starting up the Livv System. Take a moment to fill out the product and installation form on the back cover. Retain both the manual and installation record for future reference. Table of Contents Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY PRECAUTIONS Please read the following before operation. Recognize safety information. This is the safety-alert symbol. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death.
SAFETY PRECAUTIONS CAUTION • The unit should be installed and serviced only by trained, qualified installers and service technicians. Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel. • Owner should be cautioned that children should not play with the appliance. WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.
NOMENCLATURE / / / / / / 4
65.6(20) 82(25) 24(0.68) 28.2(0.8) 42.3(1.2) 52.9(1.5) 77.6(2.2) 88.2(2.5) 16/3 16/3 10 20 19 24 0.2(20) 0.5(50) 0.5(50) 0.
SUGGESTED TOOLS • Standard Wrench • Adjustable/Crescent Wrench • Torque Wrench • Hex Keys or Allen Wrenches • Drill & Drill Bits • Hole Saw • Pipe Cutter • Screw drivers (Phillips & Flat blade) • Manifold and Gauges • Level • R410A Flaring Tool • Clamp on Amp Meter • Vacuum Pump • Safety Glasses • Work Gloves • Refrigerant Scale • Micron Gauge 6
PART NAMES Indoor unit Air inlet 1 2 3 4 Air outlet Part Name 1. Front Panel 2. Aux. Button 3. Air Filter 4. Horizontal Louver 5. Remote Controller 6. XE71-44/G Wired Tether Controller (sold separately) 5 7. Inter-Connection Wire 8. Drain Hose 9.
INSTALLATION SITE INSTRUCTIONS Indoor Unit Select a site that allows for the following: 1. Ensure the installation complies with the installation minimum dimensions (defined below) and meets the minimum and maximum connecting piping length and maximum change in elevation as defined in the System Requirements section. 2. Air inlet and outlet will be clear of obstructions, ensuring proper airflow throughout the room. 3. Condensate can be easily and safely drained. 4.
INSTALLATION SITE INSTRUCTIONS Outdoor Unit Select a site that allows for the following: 1. Outdoor location meets all minimum installation clearances defined below. 2. Sound from outdoor unit will not annoy neighbors. 3. All connections can be easily made to indoor unit. 4. Air inlet and outlet will be clear of obstructions to ensure proper airflow. 5. Wall or roof is strong enough to withstand the full weight and vibration of the outdoor unit (for wall or roof installation only). 6.
INDOOR UNIT INSTALLATION A C B INDOOR UNIT DIMENSIONS in (mm) Model B C 31.1 (790) 33.3 (845) 38.2 (970) 42.4 (1078) 10.8 (275) 11.4 (289) 11.8 (300) 12.8 (325) 7.9 (200) 8.3 (209) 8.8 (224) 9.7 (246) 12 5/6 LIVV09HP230V1A LIVV12HP230V1A LIVV18HP230V1A LIVV24HP230V1A A B 10 A C INDOOR UNIT DIMENSIONS in (mm) Model LIVV30HP230V1A LIVV36HP230V1A A 53.2 (1350) 53.2 (1350) B 12.8 (326) 12.8 (326) C 10.0 (253) 10.0 (253) Installation of Mounting Bracket 1.
INDOOR UNIT INSTALLATION Mounting Bracket Diagrams and Dimensions 6 5/8 18 3/16 6 5/16 4 5/8 Φ2 1/4 Φ2 1/4 Φ 2 1/4 2 1/8 2 1/8 6 21 5/16 12K 230V 27 7 3/16 8 1/8 Φ 2 3/4 1 1/2 Φ2 3/4 1 5/8 6 18K 230V 3 1/8 24K 230V 13 7/8 29 5/8 10 Φ2 3/4 11 5/8 7 5/16 1 5/8 5 1/2 1 9/16 27 Φ2 3/4 1 1/2 7 1/2 1 3/8 3 5/16 5 9K 230V Φ 2 3/4 Φ 2 1/4 1 3/8 3 1/2 4 7 1/4 Φ2 3/4 8 3 1/2 30K and 36K 230V 11
OUTDOOR UNIT INSTALLATION Outdoor Unit Dimensions 28 12 5/8 30 5/8 11 1/4 21 1/4 10 1/8 20 9K and 12K 230V 12
OUTDOOR UNIT INSTALLATION Outdoor Unit Dimensions 13 3/16 27 9/16 35 38 15 5/16 14 5/16 22 18K and 24K 230V 36 1/4 31 1/8 14 9/16 3 39 3/8 16 13/16 1 24 15 9/16 1 30K and 36K 230V 13
PIPING INSTALLATION Refrigerant Piping CAUTION Use refrigeration grade piping ONLY. Uses of other piping will void the Manufacturer’s Warranty. Piping Preparation 1. Do not open service valves or remove protective caps on pipes until all connections are made. 2. Keep tubing free of dirt, sand, moisture and contaminants. 3. Insulate each refrigerant pipe and condensate hose with minimum 3/8” (10 mm) wall thermal pipe insulation. 4.
PIPING INSTALLATION Piping Taper Nut Indoor Unit Piping Wrench Torque Wrench Torque Table Pipe Diameter inch (mm) 1/4 (6) 3/8 (9.5) 1/2 (12.7) 5/8 (16) Nut Size inch (mm) 1/4 (17) 3/8 (22) 1/2 (25) 5/8 (29) Tightening Torque ft-lbs N-m 10 to 13 25 to 30 36 to 45 50 to 60 14 to 18 34 to 42 49 to 61 68 to 82 4. Properly align piping and tighten flare nut using a standard wrench and a torque wrench as shown in figure below.
N(1) 2 3 green white red (yellow- (blue) black (brown) green) L1 G black white green (brown) (blue) (yellowgreen) L1 Indoor unit connection L2 L2 POWER
POWER AND WIRING INSTALLATION Indoor Unit Wire Connections WARNING Disconnect all electrical power to indoor and outdoor units including disconnects, fuses and circuit breakers. Lockout and tag all disconnect switches. 1. Open front cover of indoor unit and remove field wiring terminal block cover. 2. Pull interconnecting wires up from back of indoor unit and position in close to the terminal block on indoor unit.
POWER AND WIRING INSTALLATION Outdoor Unit Wire Connections WARNING Disconnect all electrical power to unit including disconnects, fuses and circuit breakers. Lockout and tag all disconnect switches. 1. Remove the service panel on right side of the outdoor unit. 2. Insert interconnecting wires and main power wires through the wire holes on conduit mounting bracket. Cable Cross Board 3. Secure main power conduit (and interconnecting wire conduit, if required) with locking nuts to conduit mounting bracket.
TESTING AND INSPECTION Leaking Test 1. Connect the charging hose of the manifold valve to charge the end of the low-pressure valve. 2. Add dry nitrogen to a pressure of 200 lbs. Tightly close both high- and low-pressure valves. 3. Leak-test flare fittings with soap bubbles. If no leak is detected, release nitrogen. CAUTION Use vacuum pump, rather than refrigerant, to discharge air when installing the unit.
TESTING AND INSPECTION Vacuum Procedure (con’t) 7. Confirm that manifold valves are closed and disconnect the vacuum pump. 8. Open the service valves to the fully ‘back-seat’ position to let the refrigerant flow to the indoor unit and balance the pressure in system. Important: Do not allow air to enter the connection pipe when removing the hose. 9. Replace service valve caps and tighten.
TESTING AND INSPECTION Condensate Drain Pipe Testing Carefully and slowly add 8-10 ounces of water to the indoor unit drain pan. • Verify the water drains easily out the condensate drain hose. • If water does not drain easily from the drain hose, then remove kinks, increase drain pitch, or add an auxiliary condensate drain pump. Start-up Checklist □ Turn on main power to indoor and outdoor units. • Verify the system is not displaying an error code on the indoor unit display.
TROUBLESHOOTING PROBLEM CAUSE/SOLUTION System does not restart. Cause: The system has a built-in three-minute delay to prevent short and/or rapid cycling of the compressor. Solution: Wait three minutes for the protection delay to expire. Indoor unit emits unpleasant odor when started Cause: Typically unpleasant odors are the result of mold or mildew forming on the coil surfaces or the air filter. Solution: Wash indoor air filter in warm water with mild cleaner.
TROUBLESHOOTING PROBLEM CAUSE/SOLUTION Water leakage from the outdoor unit. Cause: It is normal for the outdoor unit to generate condensate water in the reverse cycle heating and defrost mode. Solution: This is normal. No action is required. The unit is not heating or cooling adequately. Wireless remote controller does not work. Cause: There are a number of reasons for inadequate cooling or heating. Solution: Check the following: • Remove obstructions blocking airflow into the room.
DIAGNOSTIC CODES Troubleshooting The Livv System has onboard diagnostics. The outdoor unit will provide status indicators. The indoor wall unit and remote controller will display error codes. The following is a summary of the codes with explanation: Malfunction Name Indoor Unit & Remote Display Outdoor Unit Indicators Yellow Red Possible Causes 1) Over charged with refrigerant. 2) Blocked or dirty outdoor coil .
DIAGNOSTIC CODES Malfunction Name Indoor Unit & Remote Display IPM Module Protection H5 Indoor DC Fan Motor Malfunction H6 1) Loose connections between fan motor and control board 2) Fan motor or blower wheel bearings malfunction. 3) Control board malfunction. Compressor De-Synchronized Malfunction H7 1) Compressor voltage is not balance.
CARE AND CLEANING WARNING Take notice of the following items before cleaning the Livv Indoor wall unit. • To avoid electric shock or injury, do not attempt to clean the unit unless it has been turned off and disconnected from the main power supply. • Do not wash the unit with water; this may cause an electric shock. • During cleaning, be sure to use a stable standing platform. Air Filter Cleaning Changing your air filter on a regular basis prevents many problems.
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI www.greecomfort.com PRODUCT & INSTALLATION RECORD For your convenience, please record the model and serial numbers of your new equipment in the spaces provided. This information, along with the installation data and dealer contact information, will be helpful should your system require maintenance or service. UNIT INFORMATION Outdoor Unit: Model No. Serial No. Indoor Unit: Model No. Serial No.