Multi Technical Product Guide

PERFORMANCE SPECIFICATIONS
9
Heating
MULTI18HP230V1A 8.2 19,000 (8,530-22,600) 5 °F 80 °F
MULTI24HP230V1A 8.2 29,000 (7,500-35,000) 5 °F 80 °F
MULTI30HP230V1A 8.2
30
,400
(7,500-36,000) 5 °F 80 °F
MULTI36HP230V1A 8.2 35,800 (10,663-40,944) 5 °F 80 °F
MULTI42HP230V1A 8.2 44,500 (10,663-47,768) 5 °F 80 °F
MODEL NUMBER HSPF
HEATING CAPACITY
RATED
(BtuH) MIN
RANGE
(BtuH)
MAX
OUTDOOR TEMP
OPERATING RANGE
Cooling
MULTI18HP230V1A 16 10.2 18,000 (7,000-21,000) 23 °F 118 °F
MULTI24HP230V1A 16 8.2 26,000 (7,500-33,000) 23 °F 118 °F
MULTI30HP230V1A 16 7.3 29,000 (7,500-34,000) 23 °F 118 °F
MULTI36HP230V1A 16 8.0 34,000 (8,530-34,120) 23 °F 118 °F
MULTI42HP230V1A 16 9.3
40
,000
(8,530-46,403) 23 °F 118 °F
MODEL NUMBER SEER EER
COOLING CAPACITY
RATED
(BtuH) MIN
RANGE
(BtuH)
MAX
OUTDOOR TEMP
OPERATING RANGE
Notes:
1.
Ratings are based on: Cooling Standard: 80°F (26.7°C) db, 67°F (19.4°C) wb air entering indoor unit and 95°F (35°C) db air entering
outdoor unit. Heating Standard: 70°F (21.1°C) db air entering indoor unit and 47°F (8.3°C) db, 43°F (6.1°C) wb air entering outdoor unit.
2. Ratings are based on 25 ft. (7.62 m) of interconnecting refrigerant lines.
3. All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data tables for air flows at selected fan speeds.
Legend:
EER - Energy Eciency Ratio
HSPF - Heating Seasonal Performance Ratio
SEER - Seasonal Energy Eciency Ratio
MODEL NUMBER BRAND
MULTI18HP230V1AO EXV 2
MULTI24HP230V1AO EXV 3
MULTI30HP230V1AO EXV 4
MULTI36HP230V1AO EXV 4
MULTI42HP230V1AO EXV 5
NUMBER OF PORTS
FOR INDOOR UNITS