Multi Technical Product Guide

33
EXTENDED PERFORMANCE RATINGS
25°F 49,212 36,540 53,192 38,511 56,860 40,939
35°F 48,092 36,497 51,216 37,388 53,704 38,828
45°F 45,716 35,110 48,888 36,275 52,380 37,976
55°F 44,012 34,065 46,932 35,199 50,312 36,728
65°F 42,512 33,032 46,776 35,503 49,600 36,258
75°F 40,840 31,937 44,000 33,836 47,324 34,925
85°F 39,200 31,125 42,000 32,424 45,600 34,063
95°F 37,200 29,723 40,000 31,960 43,760 32,864
105°F 35,200 28,582 37,912 30,254 41,200 31,642
115°F 33,200 27,357 35,200 28,512 37,600 29,441
5°F 34,729 34,729 32,776 32,776 31,973 31,973
15°F 37,122 37,122 33,867 33,867 33,664 33,664
25°F 39,388 39,388 37,384 37,384 35,257 35,257
35°F 41,586 41,586 38,491 38,491 36,876 36,876
45°F 43,759 43,759 42,275 42,275 39,713 39,713
55°F 43,818 43,818 42,275 42,275 40,690 40,690
65°F 43,611 43,611 42,973 42,973 41,649 41,649
Model No: MULTI42HP230V1A 42,000 BtuH
Cooling Performance
Heating Performance
TC- Total Capacity (BtuH) SHC- Sensible Capacity (BtuH)
Capacity data is based on the following conditions:
Cooling Nominal Test Conditions Heating Normal Test Conditions
Indoor: 80°F DB/67°F WB Indoor: 70°F DB/60°F WB
Outdoor: 95°F DB/75°F WB Outdoor: 47°F DB/43°F W
OUTDOOR AMBIENT
TEMPERATURE (DB)
INDOOR ENTERING AIR TEMPERATURES (DB) 50% RH
62°F
TC SHC
67°F
TC SHC
72°F
TC SHC
OUTDOOR AMBIENT
TEMPERATURE (DB)
(80% RH)
INDOOR ENTERING AIR TEMPERATURES (DB)
65°F
TC SHC
70°F
TC SHC
75°F
TC SHC