Installation Guide

INSTALLATION OF INDOOR UNIT
Piping Height Requirements
The system piping layout must take in the constraints of vertical height on system performance. The
outdoor unit has a vertical height limit in which it can properly circulate refrigerant in the system.
INSTALLATION OF INDOOR UNIT
Step 2
Piping Design and Layout
The piping design and layout are critical factors for the overall performance and reliability of the
system. Find the desired locations for each indoor unit and the outdoor unit.
Measure and record the piping length (L1,L2, L3….Ln) from the outdoor unit to each indoor unit.
NOTE: Min. refrigerant line length between the indoor and outdoor units is 10 ft. (3 m).
L1=
L2=
L3=
L4=
L5=
Find the indoor units with the greatest vertical distance from the outdoor unit. Measure the maximum
vertical height (H1) from the bottom of the outdoor unit to the bottom of the highest mounted indoor units.
H1=
Find the two indoor units with the greatest vertical distance from each other. Measure the maximum
vertical height (H2) between those two indoor units from bottom of one unit to bottom of the other unit.
H2=
Capacity Size Distance
(BtuH) ft (m)
18,000 33 (10)
24,000 66 (20)
30,000 66 (20)
36,000 82 (25)
42,000 82 (25)
Capacity Size Distance
(BtuH) ft (m)
18,000 16 (5)
24,000 33 (10)
30,000 33 (10)
36,000 50 (15)
42,000 50 (15)
Maximum Elevation between
Outdoor to Indoor Unit (H1)
The maximum elevation (H1) from the bottom
of the outdoor unit to the bottom of the highest
mounted indoor units must be less than:
The maxi
mum elevation (H2) between those
two indoor units from bottom of one unit to
bottom of the other unit must be less than:
Maximum Elevation between
Indoor Units (H2)
NOTE: If an indoor unit is below the outdoor unit, install oil traps in the suction/gas pipe every 20 vert. ft (6 m)
Capacity Size Distance
(BtuH) ft (m)
18,000 33 (10)
24,000 66 (20)
30,000 66 (20)
36,000 82 (25)
42,000 82 (25)
Capacity Size Distance
(BtuH) ft (m)
18,000 66 (20)
24,000 230 (70)
30,000 230 (70)
36,000 230 (70)
42,000 262 (80)
Maximum Equivalent Pipe Length
Outdoor to Farthest Indoor Unit (Ls)
The maximum equivalent pipe length from the outdoor
to the farthest indoor units (LS) must be less than:
The maximum total pipe length making up
the system (LT) must be less than:
Maximum Total
Pipe Length (LT)
NOTE: The outdoor unit is shipped with a full charge of R-410A refrigerant. The factory charge is based on
25 ft (7.6 m) pipe runs. For pipe runs over this limit, add 0.2 oz/ft (20 g/m) of additional re
frigerant.
9 10
L=L1 L2
L2
L3
...Ln
++ +
L
S
...Ln
H1
H2
L2
Ln
L1
H1
H2
TWD-0813-017 Multi install rev:Layout 1 9/27/13 12:53 PM Page 11