CENTRAL AIR CONDITIONERS SUPER+ MULTI ULTRA Series MULTIU48HP230V1BO GWHD(48S)HD3DO SUPER FREE MATCH SERIES SERVICE MANUAL T1/R410A/60Hz ( GC201306 - )
Thank you for choosing Gree air conditioners, please read this installation & owner’s manual carefully before operation and keep it for future reference. GREE reserves the right to change this contents of this manual without notice due to product improvement or modification.
Contents PRODUCT ................................................................................................................... 2 1 1.1 1.2 1.3 2 2.1 2.2 2.3 3 4 4.1 4.2 4.3 5 6 MODELS LIST ...................................................................................................................... 2 Outdoor Unit .......................................................................................................................... 2 BU Module ...............................................
Super Free Match Service Manual 3 OUTDOOR UNIT INSTALLATION .................................................................................. 59 3.1 Precautions for R410A ......................................................................................................... 59 3.2 Precaution for Installation .................................................................................................... 59 3.3 Precaution for Operation Test ............................................................
Super Free Match Service Manual 7.9 8 8.1 8.2 9 Electrical Wiring Work for Indoor Unit ............................................................................. 109 INSTALLATION OF DRAINAGE PIPELINE ................................................................. 110 Material Quality Requirements for Condensate Pipe ........................................................ 110 Key Points for Condensate Pipe Installation......................................................................
Super Free Match Service Manual PRODUCT 1 PRODUCT
Super Free Match Service Manual PRODUCT 1 MODELS LIST 1.1 Outdoor Unit Model Product code GWHD(48S)HD3 DO CN860W0330 Cooling Capacity Heating Capacity kW kW 14.0 15.8 Refriger ant Power supply R410A 1,208/230,60 Appearance Ph, V, Hz 1.
Super Free Match Service Manual 1.3 Indoor Unit 1.3.1 Wall mounted type Hansol Capacity Model Product code Cooling (kW) Heating (kW) GWH09TB-D3DNA1A/I CB148N02200 2.6 2.87 GWH12TB-D3DNA1A/I CB148N02300 3.5 3.8 GWH18TC-D3DNA1A/I CB148N04000 5.3 5.6 GWH24TD-D3DNA1A/I CB148N03800 7.1 7.3 R410A Power supply Ph, V, Hz Appearance 1,208/230,60 U-cool Capacity Model Product code Cooling (kW) Heating (kW) GWH09UB-D3DNA1A/I CB204N00800 2.6 2.87 GWH12UB-D3DNA1A/I CB204N01000 3.
Super Free Match Service Manual 1.3.3 Cassette type Capacity Model Product code Cooling (kW) Heating (kW) GKH(12)BA-D3DNA2A/I CN510N0060 3.5 3.85 GKH(18)BA-D3DNA2A/I CN510N0070 4.5 5.0 Refrige rant R410A GKH(24)BA-D3DNA1A/I CN510N0080 6.7 Power supply Ph, V, Hz Appearance 1,208/230,60 8.0 1.3.4 Floor ceiling type Capacity Model Product code Cooling (kW) Heating (kW) GTH(09)BA-D3DNA1A/I CN610N0060 2.5 2.8 GTH(12)BA-D3DNA1A/I CN610N0070 3.5 3.
Super Free Match Service Manual 2 NOMENCLATURE 2.1 Nomenclature of Outdoor Unit GW □ □ (□) □ □ □ □ O 1 2 3 4 5 6 7 8 9 NO. Description Options 1 GW Free-Match Code 2 Cooling Function C: Cooling Only 3 Compressor Frequency 4 Cooling Capacity 5 Climate Type 6 Power Supply 7 Refrigerant 3-R410A 8 Design No. C :Third generation 9 O H: Heat pump D:DC inverter rotor type 48 represents 48000Btu/h 1kW=3.
Super Free Match Service Manual 3 FUNCTION Wall mounted Duct type Cassette type Floor ceiling type Console type Fan operation Mode ● ● ● ● ● Auto Swing Controller ● / ● ● ● Timer Selector ● ● ● ● ● Auto Mode Operation ● ● ● ● ● Cool Mode Operation ● ● ● ● ● Heat Mode Operation ● ● ● ● ● Dry Mode Operation ● ● ● ● ● Fan Mode Operation ● ● ● ● ● Sleep mode setting ● ● ● ● ● Drain Pump / ● ● / / Wired Controller / ● ● ● / Wireless Remote
Super Free Match Service Manual 4 PRODUCT DATA 4.1 Product Data of Outdoor Unit Model MULTIU48HP230V1BO Heat pump Cooling capacity KW 14.0 Heating capacity KW 15.8 Cooling KW 5.0 Heating KW SEER/HSPF 4.4 18/10 Minimum NO. of connectable indoor units 2 Maximum NO. of connectable indoor units 7 1 Nominal input Minimum No. of BU modules to be connected Maximum No.
Super Free Match Service Manual Notes: a. Refer to the product nameplate for parameters and specification of the unit; b. The data will change with the change of products. Refer to those parameters listed on nameplate. c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient. 4.2 Product Data of Indoor Unit 4.2.1 Wall mounted type Hansol Model GWH09TB-D3 DNA1A/I GWH12TB-D3 DNA1A/I GWH18TC-D3 DNA1A/I GWH24TD-D3 DNA1A/I Cooling kW 2.6 3.
Super Free Match Service Manual U-cool Model GWH09UB-D3DNA 1A/I GWH12UB-D3DNA 1A/I GWH18UC-D3DNA 1A/I Cooling kW 2.6 3.5 5.3 Heating kW 2.87 3.8 5.8 Power supply V-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 Motor power input kW 0.04 0.04 0.06 m3/h 510 520 820 CFM 300 306 483 dB(A) 41/37/35/32/30/28/25 42/39/37/34/31/28/26 44/40/37/35/33/31/28 Output kW 0.02 0.02 0.025 Running current A 0.20 0.20 0.32 Gas inch 3/8″(Φ9.52mm) 1/2″(Φ12.7mm) 1/2″(Φ12.
Super Free Match Service Manual Cozy Model GWH09MB-D3 DNA3D/I GWH12MB-D3 DNA3D/I GWH18MC-D3 DNA3D/I GWH24MD-D3 DNA3D/I Cooling kW 2.6 3.5 5.3 6.3 Heating kW 2.87 3.8 5.8 6.75 Power supply V-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Motor power input kW 0.05 0.05 0.05 0.10 3 m /h 520 570 850 1000 CFM 306 335 500 588 dB(A) 41/37/35/26/- 42/38/36/28/- 46/44/40/35/- 53/45/41/37/- Output kW 0.02 0.02 0.02 0.06 Running current A 0.20 0.20 0.
Super Free Match Service Manual 4.2.2 Duct type Model Heat pump GFH(09)EA-D3D NA1A/I GFH(12)EA-D3D NA1A/I GFH(18)EA-D3D NA1A/I Cooling KW 2.5 3.50 4.5 Heating KW 2.8 3.85 5.5 Power supply V-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 Motor power input kW 0.08 0.08 0.10 m3/h 450 500 700 CFM 265 294 412 dB(A) 37/34/31 39/35/32 41/37/33 Output kW 0.04 0.049 0.075 Running current A 0.35 0.35 0.43 Gas inch 3/8″(Φ9.52mm) 3/8″(Φ9.52mm) 1/2″(Φ12.
Super Free Match Service Manual Model Heat pump GFH(21)EA-D3DNA1A/I GFH(24)EA-D3DNA1A/I Cooling KW 6.0 7.0 Heating KW 6.6 8.0 Power supply V-Ph-Hz 208/230-1-60 208/230-1-60 Motor power input kW 0.124 0.124 m3/h 1000 1000 CFM 588.5 588.5 dB(A) 42/38/34 42/38/34 Output kW 0.061 0.061 Running current A 0.54 0.54 Gas inch 5/8″(Φ15.9mm) 5/8″(Φ15.9mm) Liquid inch 3/8″(Φ9.52mm) 3/8″(Φ9.
Super Free Match Service Manual 4.2.3 Cassette type Model Heat pump GKH(12)BA-D3 DNA2A/I GKH(18)BA-D3 DNA2A/I GKH(24)BA-D3 DNA1A/I Cooling KW 3.5 4.5 6.7 Heating KW 4.0 5.0 8.0 Power supply V-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 Motor power input kW 0.05 0.05 0.10 m3/h 600 600 1180 CFM 353 353 694 dB(A) 46/44/42 46/44/42 39/37/35 Output kW 0.011 0.011 0.05 Running current A 0.23 0.23 0.43 Gas inch 3/8″(Φ9.52mm) 1/2″(Φ12.7mm) 5/8″(Φ15.
Super Free Match Service Manual 4.2.4 Floor ceiling type Model Heat pump GTH(09)BA-D3 DNA1A/I GTH(12)BA-D3 DNA1A/I GTH(18)BA-D3 DNA1A/I GTH(24)BA-D3 DNA1A/I Cooling KW 2.5 3.5 5.0 6.7 Heating KW 2.8 3.85 5.5 8.0 Power supply V-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Motor power input kW 0.055 0.055 0.11 0.145 m3/h 650 650 950 1250 CFM 382.5 382.5 559 736 dB(A) 40/38/36 40/38/36 45/42/40 48/46/44 Output kW 0.015 0.02 0.02 0.
Super Free Match Service Manual 4.2.5 Console type Model Heat pump GEH(09)AA-D3DNA1 C/I GEH(12)AA-D3DNA1 C/I GEH(18)AA-D3DNA1 C/I Cooling KW 2.6 3.5 5.3 Heating KW 2.8 3.8 5.8 Power supply V-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 Motor power input kW 0.05 0.05 0.05 m3/h 500 600 650 CFM 294 353 383 dB(A) 40/38/36/33/30/27/25 42/40/38/37/35/32/27 48/46/44/41/37/35/32 Output kW 0.03 0.03 0.03 Running current A 0.14 0.14 0.14 Gas inch 3/8″(Φ9.
Super Free Match Service Manual 4.3 Product Data of BU Module Model FXA2A-D FXA2B-D FXA3A-D FXA3B-D FXB5A-D Maximum numbers of connectable indoor units 2 2 3 3 5 Power Supply Connection port to outdoor unit Connection port to indoor unit V-Ph-Hz 208/230-1-60 Gas pipe (inner diameter) mm Φ15.9 Φ16.3 Φ15.9 Φ16.3 Φ15.9 Liquid pipe (inner diameter) mm Φ9.52 Φ9.7 Φ9.52 Φ9.7 Φ9.52 Flare Braze Flare Braze Flare Connection Method Gas pipe (inner diameter) mm Φ9.52 Φ16.3 Φ9.
Super Free Match Service Manual 6 PIPING DIAGRAM Schematic Diagram of Super Free Match Series Inverter Heat Pump Multi System During the cooling operation, the low temperature, low pressure refrigerant gas from the heat exchanger of each indoor unit gets together and then is taken into the compressor to be compressed into high temperature, high pressure gas, which will soon go to the heat exchanger of the outdoor unit to exchange heat with the outdoor air and then is turned into refrigerant liquid.
Super Free Match Service Manual CONTROL CONTROL 18
Super Free Match Service Manual Control 1 OPERATION FLOWCHART 19 CONTROL
Super Free Match Service Manual 1.
Super Free Match Service Manual 1.
Super Free Match Service Manual 2 MAIN LOGIC 2.1 Control Function of Outdoor Unit 2.1.1 Cooling Mode 1) Cooling conditions and process: If the compressor is in stop status and start the unit for cooling operation, when one of the indoor units reaches the cooling operation condition, the unit starts cooling operation; in this case, the electronic expansion valve, the outdoor fan and the compressor start operation.
Super Free Match Service Manual The status of 4-way valve: energized; 3) Outdoor fan control in heating mode The outdoor fan starts before 5s of the starting of compressor and then it will run in high speed for 40s; The fan shall run at every speed for at least 80s; When the compressor stops, the outdoor fan stops after 1min.
Super Free Match Service Manual 2.2.4 Communication malfunction Detection of the quantity of installed indoor units and BU modules: After 3min of energizing, if the outdoor unit does not receive the communication data of certain indoor unit, the outdoor unit will judge that indoor unit is not installed and will treat it as it is not installed. If the outdoor unit receives the communication data of that indoor unit later, the outdoor unit will treat that unit as it is installed. 2.2.
Super Free Match Service Manual 2.4 Control Function of Indoor Unit 2.4.1 Running Mode 1. COOL 2.DRY 3.HEAT 4.AUTO 5 FAN 2.4.2 Basic Functions of the System 1) COOL Mode Under this mode, the fan and swing function goes as the set conditions, and the set temperature range is 16℃ ~30℃. 2) DRY Mode Under this mode, the fan will run at the low speed and the swing function is performed under the set conditions. The set temperature range is 16~30℃.
Super Free Match Service Manual speed. d) Under the HEAT Mode: (Ambient temperature herein is the temperature without temperature compensation) ◆ When the ambient temperature is or lower than the set temperature, the indoor unit runs at the high speed. ◆ When the ambient temperature is higher than the set temperature but lower than the set temperature plus 2℃, the indoor unit fan runs at the medium speed.
Super Free Match Service Manual c) When the indoor unit works without the wired controller, if the timer is not set for the last remote control instruction, the system will memorize this last instruction and works following it; if the timer is set, it will be canceled as the power failure occurs and will have to be reset. d) When the indoor unit works with the wired controller, it will work as the message sent by the wired controller after it is powered on again.
Super Free Match Service Manual 3 REMOTE CONTROLLER 3.1 Wired Remote Controller 3.1.1 Wired Controller XK19 It is designed for the cassette type, duct type and floor ceiling type indoor units. ◆ Outside View of the Wired Controller ◆ LCD of the Wired Controller No. Symbols Description 1 Swing function. 2 Sleep function 3 Running modes of the indoor unit (Cooling, Dry, Fan, Heating and Auto). 4 Defrosting function for the outdoor unit. 5 Gate-control function.
Super Free Match Service Manual 11 Master wired controller (this function is yet unavailable for this unit). 12 It blinks under on state of the unit without operation of any button. 13 Energy-saving function.(this function is yet unavailable for this unit) 14 Ambient/preset temperature value. 15 Electric auxiliary heating function.(this function is yet unavailable for this unit) 16 Blow function. 17 Timing value. 18 Quiet function (two types: quiet and auto quiet).
Super Free Match Service Manual 3.1.3 Operation Instructions 1) On/Off Press On/Off to turn on the unit and turn it off by another press. 2) Mode Setting Under the “On” state of the unit, press Mode to switch the operation modes as the following sequence: Cooling-Dry-Fan-Heating. 3) Temperature Setting Press ▲ or ▼ to increase/decrease the preset temperature. If press either of them continuously, the temperature will be increased or decreased by 1℃ every 0.5s.
Super Free Match Service Manual b. 26℃ is the default Sleep curve temperature before delivery. The wired controller will automatically memorize the Sleep curve after the setting. 8) Turbo Setting Turbo function: The unit at the high fan speed can realize quick cooling or heating so that the room temperature can quickly approach the setting value. In the Cooling or Heating mode, press Function till the unit enters the Turbo setting interface and then press Enter/Cancel to confirm the setting.
Super Free Match Service Manual failure will resume its original running state upon power recovery. Memory contents: On/Off, Mode, set temperature, set fan speed, Save function and Lock function. Enquiry of the Outdoor Ambient Temperature Under the “On” or “Off” state of the unit, press Enter/Cancel for 5s, and the outdoor ambient temperature will be displayed after a sound of click. This enquiry state will quit by pressing Function or On/Off or during the temperature adjustment.
Super Free Match Service Manual 3.2 Wireless Remote Controller YT1F (MOTO) Notes: a. Be sure that there are no obstructions between the receiver and the remote controller; b. Do not drop or throw the remote controller; c. Do not let any liquid into the remote controller and expose the remote controller to direct sunlight or any place where is very hot. d. This is a general use remote controller.
Super Free Match Service Manual Auto, Cool, Dry Fan, Heat modes can be selected circularly by pressing this button. Auto mode is the default after power on. Under Auto mode, the temperature will not be displayed. Under Heat mode, the initial value is 28℃(82℉); Under other modes, the initial value is 25℃(77℉). 6) I FEEL This function can be activated by pressing this button and canceled by another press.
Super Free Match Service Manual of . If the swing function is deactivated when the air guide louver is swing up and down, it will stop at the current position indicates that the air guide louver swings up and down among all five positions. indicates that the air guide louver swings up and down among all five positions.
Super Free Match Service Manual ◆ X-FAN ON: When press the ON/OFF button to turn off the unit, the indoor fan will continue running for about another 10 minutes at the low speed. In this case, the indoor fan can be stopped directly by pressing the button X-FAN. ◆ X-FAN OFF: When press the ON/OFF button to turn off the unit, the whole unit will be stopped completely.
Super Free Match Service Manual 2) - Press this button to decrease set temperature. Holding it down above 2 seconds rapidly decreases set temperature. In AUTO mode, set temperature is not adjustable. 3) + Press this button to increase set temperature. Holding it down above 2 seconds rapidly increases set temperature. In AUTO mode, set temperature is not adjustable.
Super Free Match Service Manual healthy function; LCD display “ 9) ◆ ”. Press this button again to repeat the operation above. SLEEP: Press this button, can select Sleep 1 ( ), Sleep 2 ( ), Sleep 3 ( ) and cancel the Sleep, circulate between these, after electrified, Sleep Cancel is defaulted.
Super Free Match Service Manual (display " " signal) and Quiet OFF (there is no signal of " "displayed),after powered on, the Quiet OFF is defaulted. Note: the Quiet function cannot be set up in Fan and Dry mode; Under the Quiet mode (Display " " Under the Quiet mode (Display " " signal), the fan speed is not available. 12) CLOCK : Press CLOCK button, blinking . Within 5 seconds, pressing + or - button adjusts the present time.
Super Free Match Service Manual 3) Combination of " TEMP " and "CLOCK" buttons : About Energy-saving Function Press “TEMP” and “CLOCK” simultaneously in COOL mode to start energy-saving function. Nixie tube on the remote controller displays “SE”. Repeat the operation to quit the function.
Super Free Match Service Manual 3) FAN Press this button, Auto, Low, Medium-low, Medium, Medium-high, High speed can be circularly selected. After powered on, Auto fan speed is default. Under DRY mode, Low fan speed only can be set up. Low fan Low-Medium fan Medium-High fan Medium fan High fan Note: It’s Low fan speed under Dry mode. 4) TEMP Press this button, the following temperature can be set circularly: the setting temperature, indoor ambient temperature and outdoor ambient temperature.
Super Free Match Service Manual mode or fan speed. 8) X-FAN: Pressing X-FAN button in COOL or DRY mode, the icon is displayed and the indoor fan will continue operation for 10(2) minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is defaulted. X-FAN is not available in AUTO, FAN or HEAT mode. 9) +: Presetting temperature can be increased.
Super Free Match Service Manual 15) TIMER ON Timer On setting : Signal “ON” will blink and display, signal will conceal, the numerical section will become the timer on setting status. During 5 seconds blink, by pressing + or - button to adjust the time value of numerical section, every press of that button, the value will be increased or decreased 1 minute. Hold pressing + or - button, 2 seconds later , it quickly change, the way of change is: During the initial 2.
Super Free Match Service Manual temperature will be decreased 1℃, after that the unit will keep on running under this temperature; ③ When setting the initial temperature 28℃~29℃, after turned on Sleep function, the temperature will be increased 1℃ in every hour, after 1℃ the temperature will be maintained, after 7hours, the temperature will be decreased 1℃, after that the unit will keep on running under this temperature; ④ When setting the initial temperature 30℃, under this temperature setting, after 7hour
Super Free Match Service Manual 1) 2) 3) Press SLEEP button, to set sleep. Press TIMER ON and TIMER OFF button, can set the scheduled timer on timer off. Press LIGHT button, to control the on and off of the displaying part of the unit (This function may be not available for some units). 4) Press TURBO button, can realize the ON and OFF of TURBO function. 3.4.
Super Free Match Service Manual Press “TEMP” and “CLOCK” simultaneously in HEAT mode to start 8℃ Heating Function Nixie tube on the remote controller displays “ ” and a selected temperature of “8℃”. (46℉ if Fahrenheit is adopted). Repeat the operation to quit the function. About Quiet function When quiet function is selected: ① Under cooling mode: indoor fan operates at notch 4 speed.
Super Free Match Service Manual Press this button can turn on or turn off the air conditioner. After turning on the unit, operation indicator " " on indoor unit is ON (green indicator. Color may be different for different models) and indoor unit gives out a sound. 2) MODE Press this button, Auto, Cool, Dry, Fan, Heat mode can be selected circularly. After energization, AUTO mode is defaulted.
Super Free Match Service Manual by 1 minute. Holding down either button rapidly changes the time setting by 1 minute and then 10 minutes. Within 5 seconds after setting, press TIMER ON button to confirm. 8) TIMER OFF Press this button to initiate the auto-off timer. To cancel the auto-timer program, simply press the button again. TIMER OFF setting is the same as TIMER ON. 9) CLOCK Pressing CLOCK button blinks. Within 5 seconds, pressing + or - button adjusts the present time.
Super Free Match Service Manual 4 Smart Zone Controller (CE50-24/E) 4.1 General Introduction 4.1.1 Function Introduction This smart zone controller is a kind of regional controller, which is designed for free match units, capable of controlling up to 16 indoor units.
Super Free Match Service Manual 4.2 Communication Network Note: The smart zone controller can connect with maximum up to 16 indoor units. 4.3 LCD No. Name 1 Fan speed 2 Running mode It displays the running mode of the indoor unit, auto, cool, dry, fan and heat. 3 System clock It displays the current time (hour and minute) in 24-hour time system and also the week day. 4 Shield It displays the shielded status, “ALL”, “TEMP”, “MODE” and “ON/OFF”.
Super Free Match Service Manual It displays the set temperature, indoor unit code (01-16), and symbols of Celsius and Fahrenheit scale. 6 Set temperature/ Indoor unit code 7 Control mode It displays “CENTER” under the centralized control mode and no display under the single control mode. 8 Ambient temperature/ Serial port It displays the ambient temperature, serial port as well as symbols of Celsius and Fahrenheit scale.
Super Free Match Service Manual 7 Tue 2/10 It is used for the switchover between unit 2 and unit 10; Under the timing or clock setting status, it indicates Tuesday. 8 Wed 3/11 It is used for the switchover between unit 3 and unit 11; Under the timing or clock setting status, it indicates Wednesday. 9 Thu 4/12 It is used for the switchover between unit 4 and unit 12; Under the timing or clock setting status, it indicates Thursday.
Super Free Match Service Manual INSTALLATION 53 INSTALLATION
Super Free Match Service Manual INSTALLATION 1 PRECAUTIONS FOR INSTALLATION 1.1 Precautions for Installation Before installation, please ensure the installing site, power ratings, possible operating range (pipe distance, height difference between indoor and outdoor unit, power voltage) and installing space are correct and suitable. To ensure correct installation, please make sure to read the Safety Considerations thoroughly before starting the installation works.
Super Free Match Service Manual Do not use or store flammable, explosive, poisonous or other dangerous substances beside the air conditioner. The compressor will vibrate sharply if the voltage is too low and damage the refrigerating system. Electrical component are easy to damage if the voltage is too high.
Super Free Match Service Manual 1.2 Key Points of Installation Installation Procedures Description and Acceptance Criteria ◆ The materials specified on the engineering drawing shall be purchased as specified (e.g. copper tube, thermal insulation tube, PVC pipe, power cables, air switch, etc). ◆ The materials not specified on the engineering drawing shall be purchased according to the actual quantity of works (e.g. hanger frame, cable duct, etc).
Super Free Match Service Manual acceptable if pressure drop is within 0.02MPa. (With the temperature change by 1℃, the pressure will change by approx. 0.01MPa) Thermal insulation Installation of outdoor unit Connection of indoor unit and outdoor unit ◆ ◆ The thermal insulation tube must meet the specifications. Seal between the thermal insulation pipes to avoid air entry. ◆ ◆ Select the installing position correctly.
Super Free Match Service Manual 2 FLOW CHART OF INSTALLATION Design kicking-off Material selection Inspection of site installation position Installation of indoor unit Installation of remote controller Connection of power cables Installation of outdoor unit Connection of power cables Installation of BU module Connection of transmission line Connection of power cables Installation of piping adapter Installation of refrigerant pipes Leakage test Vacuum the system through the gas and liquid valve
Super Free Match Service Manual 3 OUTDOOR UNIT INSTALLATION 3.1 Precautions for R410A It is very strict that the refrigerant pipes should be clean and dry. The R410A is a mixed refrigerant, when add the refrigerant to the unit, it must keep the refrigerant in its liquid state. If the refrigerant is in gas state, the composition has been changed and the capability of the unit will decrease. When the refrigerant is leak out, please do not touch the leakage. Otherwise, it will result in frostbite.
Super Free Match Service Manual 3.5 Parts and Components of Unit For the super free match series system, one outdoor unit is able to drive up to three BU modules and nine indoor units which include cassette type, duct type, wall-mounted type, floor ceiling type and console type. The outdoor unit will run as long as any one indoor unit receives the running command, and all indoor units stop once the outdoor unit is turned off. 3.
Super Free Match Service Manual mounting surface must be horizontal plane. There is enough space for the installation and maintenance. The place should be well-ventilated, so the machine can absorb and discharge sufficient air. Outdoor unit shall be installed close to the indoor unit, hence to minimize the length and bends of cooling pipe. Avoid place the outdoor unit under the windows or between the constructions, hence to prevent normal operating noise from entering the room.
Super Free Match Service Manual 3.9 Installation of the Outdoor Unit 1) 2) 3) 4) 5) INSTALLATION Check the installation location and ensure it is strength and level, so that the unit will not cause any operating vibration or noise after installation. In accordance with the foundation drawing in the following figure, please drill 4 holes in the installation location. A: The outlet side B: Bottom view (mm) C: Drain hole Fix the unit securely with the foundation bolts.
Super Free Match Service Manual 4 INDOOR UNIT INSTALLATION 4.1 Installation of Wall Mounted Type 4.1.1 Important Notices The installation of air conditioner unit must be in accordance with national and local safety codes. Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited from installation by himself. Please contact the dealer after buying this machine.
Super Free Match Service Manual 4.1.5 Installation of Mounting Plate 1) Mounting plate should be installed horizontally. As the water drainage pipe for the indoor unit is two-way type, during installation, the indoor unit should slightly slant to water tray's outlet for smooth drainage of condenser water. 2) Fix the mounting plate on the selected location with screws.
Super Free Match Service Manual 2) Put the drain hose into insulating tube. Wrap the insulating tube with wide rubber belt to prevent the shift of insulating tube. Slant the drain hose downward slightly for smooth drainage of condensate. Note: The insulating tube should be connected reliably with the sleeve outside the outlet pipe. The drain hose should be slanted downward slightly, without distortion, bulge or fluctuation. Do not put the outlet in the water. 4.2 Installation of Duct Type 4.2.
Super Free Match Service Manual 4.2.3 Caution for Installation ◆ ◆ ◆ ◆ ◆ Ensure the hanger is strong enough to withstand the weight of the unit. The drainage of the drain pipe is easy. No obstacle is in the inlet/outlet and the air circulation is in good condition. Ensure the installation space is left for the access to maintenance. It should be far away from where there is heat source, leakage of inflammable, explosive substances, or smog. ◆ It is the ceiling type unit (concealed in the ceiling).
Super Free Match Service Manual 4.2.6 1) Installation of the Indoor Unit Requirements on the Installation Location Ensure the hanger is strong enough to withstand the weight of the unit. The drainage of the drain pipe is easy. No obstacle is in the inlet/outlet and the air circulation is in good condition. Ensure the installation space shown in the following figures is left for the access to maintenance.
Super Free Match Service Manual Caution! Prior to the installation, please make a good preparation for all piping (refrigerant pipe, drain pipe) and wiring (wires of the wired controller, wires between the indoor and outdoor unit) of the indoor unit to make the further installation much easier. If there is an opening in the ceiling, it is better to reinforce it to keep it flat and prevent it vibrating. Consult the user and builder for more details.
Super Free Match Service Manual No. Name No. Name No. Name 1 Hanger 4 Return Air Inlet 7 Air Supply Outlet 2 Return Air Duct 5 Filter Screen 8 Plenum Box 3 Canvas Duct 6 Main Air Supply Duct 2) Installation of the Round Air Supply Duct No. Name No. Name No.
Super Free Match Service Manual 4.2.9 Installation of the Return Air Duct 1) The default installation location of the rectangular flange is in the back and the return air cover plate is in the bottom. 2) If the downward return air is desired, just change the place of the rectangular flange and the return air cover plate. Connect one end of the return air duct to the return air outlet of the unit by rivets and the other to the return air louver.
2) 3) Super Free Match Service Manual There is a condensate outlet on both left and right sides of the unit. Once one is confirmed to be used, the other should be clogged by a rubber plug, bundled by the binding wire and insulated by the insulation material to avoid water leakage. The right outlet is defaulted to be clogged with a plug. Caution!:No water leakage is allowed on the joint of the condensate pipe. 4.2.11 1) 2) 3) 4) 4.2.
Super Free Match Service Manual 5) Insert the drain hose into the drain hole and tighten it with clamps. 6) Wrap the clamps with large amount of sponge for thermal insulation. 7) The drain hose inside the room also should be insulated. 4.2.13 Precautions for the Lift Pipe The installation height of the lift pipe should be less than 850mm. It is recommended to set an inclination angle 1°~2°for the lift pipe toward the drainage direction.
Super Free Match Service Manual 4.3 Installation of Cassette Type 4.3.1 Installation Location and Matters Needing Attention The installation of air conditioner unit must be in accordance with national and local safety codes. Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited from installation by himself. Please contact your dealer after buying this machine.
Super Free Match Service Manual 4.3.
Super Free Match Service Manual 4.3.4 Installation and Servicing Space The drilling of holes in the ceiling must be done by the professional personnel. 4.3.5 1) 2) 3) 4) 5) Installation of the Indoor Unit The primary step for install the indoor unit. When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and lower of the hoisting stand to fix it. The use of gasket anchor board can prevent gasket break off.
Super Free Match Service Manual 6) Backout the install cardboard. Note: Please do tighten the nuts and bolts to prevent air conditioner break off. 4.3.6 Drainage hose 1) Install the drain hose The diameter of the drain hose should be equal or bigger than the connection pipe’s. (The diameter of polythene pipe: Outer diameter 25mm Surface thickness ≥ 1.5mm) Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of air bubble.
Super Free Match Service Manual 2) Drain stepup pipe note The install height of the drain raising pipe should less than 280mm. The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm. 3) Instruction The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t have to endure the unnecessary outside force. Please install the drain hose according to the following process if several drain hoses join together.
Super Free Match Service Manual Check the drain in the state of refrigerating after installation of the electric circuit. 4.4 Installation of Floor Ceiling Type 4.4.1 Important Notices The installation of air conditioner unit must be in accordance with national and local safety codes. Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited from installation by himself. Please contact your dealer after buying this machine.
Super Free Match Service Manual Model A B H C D 1220 225 700 1158 280 GTH(09)BA-D3DNA1A/I GTH(12)BA-D3DNA1A/I GTH(18)BA-D3DNA1A/I GTH(24)BA-D3DNA1A/I 4.4.5 1) Installation and Servicing Space The space around the unit is adequate for ventilation. 2) Important notice The unit must be installed by the professional personnel according to this install instruction to ensure the well use. Please contact the local Gree special nominated repair department before installation.
Super Free Match Service Manual It should be done by professional personnel when the air conditioner unit is moved to other place. 4.4.6 There are 2 styles of installation Ceiling type and Floor type Each type is similar to the other as follows: 1) Determine the mounting position on ceiling or wall by using paper pattern to indicate indoor frame. Mark the pattern and pull out the paper pattern.
Super Free Match Service Manual It is possible to install using inward facing hanger brackets by not removing the brackets from the indoor unit. (Refer to ⑧) Be sure to use only the specified accessories and parts for installation work. 4.5 Installation of Console Type 4.5.1 4.5.2 Installation Location and Matters Needing Attention The installation of air conditioner unit must be in accordance with national and local safety codes.
Super Free Match Service Manual 4.5.3 There are 2 styles of installation Ceiling type and Floor type Each type is similar to the other as follows: The indoor unit should be sited in a place where: 1) the restrictions on installation specified in the indoor unit installation drawings are met. 2) Both air intake and exhaust have clear paths met. 3) The unit is not in the path of direct sunlight. 4) The unit is away from the source of heat or steam.
Super Free Match Service Manual 4.5.6 Installation and Servicing Space 4.5.7 Installation of the Indoor Unit 1) Preparation Open the front panel, remove the 4 screws and dismount the front grille while pulling it forward. Follow the arrows to disengage the clasps on the front case to remove it. Follow the procedure below when removing the slit portions. 2) For Moldings Remove the pillars. (Remove the slit portions on the bottom frame using nippers.) 3) For Side Piping Remove the pillars.
Super Free Match Service Manual 4) Installation Secure using 6 screws for floor installations.(Do not forget to secure to the rear wall.) For wall installations, secure the mounting plate using 5 screws and the indoor unit using 4 screws. The mounting plate should be installed on a wall which can support the weight of the indoor unit. Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points on the wall.
6) Super Free Match Service Manual Remove the air filters and pour some water into the drain pan to check the water flows smoothly. 7) 8) Insert the supplied C drain hose into the socket of the drain pan. Fully insert the drain hose until it adheres to a seat of the socket.
Super Free Match Service Manual 5 BU MODULE INSTALLATION 5.1 Precaution for Installation The installation of the air conditioner must be in accordance with the national and local laws and regulations. The quality of the installation will affect the capability of air conditioner directly. The installation should be left to the appointed service center. Please contact your dealer after purchasing this machine.
Super Free Match Service Manual ④ NO. ① ② ③ Name Gas piping of indoor unit side Liquid piping of indoor unit side Hanger metal Electrical equipment plate NO. ⑤ ⑥ ⑦ ⑧ Name Liquid piping of outdoor unit side Gas piping of outdoor unit side Drain hole Printed circuit board 5.3 Selection of Installation Location The BU module is for indoor use. If installing in the outdoors, the location must be away from wind and rain. Otherwise, it maybe causes water leakage, electric shocks or fire etc.
Super Free Match Service Manual 5.4 Outline Dimension and Servicing Space of FXA2A-D 1) Outline dimension Indoor unit side (mm) Sorts 2) Outdoor unit side (mm) Port A Port B Liquid pipe Φ6.35 Φ6.35 Φ9.52 Gas pipe Φ9.52 Φ9.52 Φ15.9 Installation and service space INSTALLATION 88 NO.
Super Free Match Service Manual 5.5 Outline Dimension and Servicing Space of FXA2B-D 1) Outline dimension Indoor unit side (mm) Sorts Outdoor unit side (mm) Port A Port B Liquid pipe Φ6.5 Φ6.5 Φ9.7 Gas pipe Φ16.3 Φ16.3 Φ16.3 2) Installation and service space NO.
Super Free Match Service Manual 5.6 Outline Dimension and Servicing Space of FXA3A-D 1) Outline dimension Indoor unit side (mm) Port A Port B Port C Outdoor unit side (mm) Liquid pipe Φ6.35 Φ6.35 Φ6.35 Φ9.52 Gas liquid Φ9.52 Φ9.52 Φ9.52 Φ15.9 Sorts 2) Installation and service space INSTALLATION 90 NO.
Super Free Match Service Manual 5.7 Outline Dimension and Servicing Space of FXA3B-D 1) Outline dimension Indoor unit side (mm) Port A Port B Port C Outdoor unit side (mm) Liquid pipe Φ6.5 Φ6.5 Φ6.5 Φ9.7 Gas liquid Φ16.3 Φ16.3 Φ16.3 Φ16.3 Sorts 2) Installation and service space NO.
Super Free Match Service Manual 5.8 Outline Dimension and Servicing Space of FXB5A-D 1) 2) Outline dimension Sorts Indoor unit side (mm) Outdoor unit side (mm) Liquid pipe Φ6.35 Φ9.52 Gas pipe Φ9.52 Φ15.9 Installation and service space INSTALLATION 92 NO.
Super Free Match Service Manual 5.9 Installation Instruction 1) 2) 3) Check the installation location and ensure it is strength and level. Otherwise, there should be enough space to install drainage pipe, so that the condensed water can be discharged. Reference to the size of hanger metal and drill 4 holes in the installation location. Hang the hanger bolts. 4) Fix the modules securely with the hanger bolts. You can get the M10 or M8 hanger bolts, nuts and washers from the market.
Super Free Match Service Manual 6 REFRIGERATION PIPING WORK 6.
Super Free Match Service Manual 6.3 Connection of Branch Pipe 1) If two or three BU modules used, Y-type branch pipe of FQ01A/A will be chosen. FQ01A/A (Liquid pipe) FQ01A/A (Gas pipe) 2) Y-type branch pipe is equipped with auxiliary tubes to adjust the diameter of different pipes. If the dimension of the pipe selected is different from the dimension of branch pipe joint, Cut the copper tube in the middle with tube cutter and clear up burrs. Please do that as following figure.
Super Free Match Service Manual ⑤ See the schematics below: Outdoor unit lower than indoor unit Outdoor unit higher than indoor unit INSTALLATION 96
Super Free Match Service Manual 6.5 Connection of Outdoor Unit Refrigerant Pipe NO. ① ② ③ ④ Name Coping plate Rear side plate Front side plate Gas side stop valve NO. ⑤ ⑥ ⑦ Name Liquid side stop valve Right connection board Front connection board NO. A B Name Front connection 1) 2) 3) 4) 5) 6) Side connection Unscrew the coping plate, front side plate, right connection board and front connection board.
Super Free Match Service Manual 1) Piping adapter(Optional accessories) NO. Name Port A (mm) Port B (mm) 1 Φ15.9→Φ19.05 Φ15.9 Φ19.05 2 Φ9.52→Φ12.7 Φ9.52 Φ12.7 3 Φ9.52→Φ15.9 Φ9.52 Φ15.9 4 Φ6.35→Φ9.52 Φ6.35 Φ9.52 2) Install the piping adapter ① Refer to the piping connection size of the outdoor unit and indoor units, the appropriate piping adapter should be adopted. ② Align the flared end of copper tube with the center of pipe joint. Tighten the nuts with hands.
Super Free Match Service Manual 2) Brazing the piping adapter ① If the connection size of the pipe adapter selected is different from the piping connection size of BU module, cut the tube of the piping adapter from middle with tube cutter and remove the burrs. ② To avoid heat damage the internal structure of the BU module, wrap the pipes to be brazed with sufficient wet cloths. ③ After brazing, use wet cloths to cool off the pipes to be brazed sufficient.
Super Free Match Service Manual ① Outdoor unit shall be installed close to the indoor unit, hence to minimize the length and bends of connection pipes. ② The height gap of outdoor unit and indoor units should be as small as possible 2) The brazing operation must be strictly in accordance with the process requirements. During the installation, do not damage the pipeline. 6.7.2 The process of flaring ① Using the tube cutter to cut the connecting pipe in the appropriate place and remove the burrs.
Super Free Match Service Manual Caution! During the connection of the indoor unit and BU module to the refrigerant pipe, never pull any joints of the indoor unit and the BU module by force; otherwise the capillary pipe or other pipe may crack, which then would result in leakage. The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of it.
Super Free Match Service Manual 1: Outdoor unit 2: Gas side stop valve 3: Liquid side stop valve 4: Pressure-vacuum gauge 5: Hi-knob 6: Lo-knob 7: Vacuum pump 5) 6.10 Turn off the knobs firstly and then the pump, and if the pressure of the pressure-vacuum gauge does not rise within 2 hours, the system is under a vacuum. Otherwise, the system has leaked, please look for where the gas leaks in.
Indoor unit 3 Wall mounted type Super Free Match Service Manual GWH09UB-D3DNA1A/I Indoor unit 4 Wall mounted type GWH09MB-D3DNA3D/I Indoor unit 5 Duct type GFH(09)EA-D3DNA1A/I Indoor unit 6 Wall mounted type GWH09TB-D3DNA1A/I Serial No. Diameter(mm) Length(m) L1 Φ9.52 20 L2 Φ9.52 10 L4 Φ9.52 10 1A Φ6.35 5 1B Φ6.35 5 1C Φ6.35 5 2A Φ6.35 5 2B Φ6.35 5 2C Φ6.35 5 The total length of the liquid pipes: 20+10+10+5+5+5+5+5+5=70(m).
Super Free Match Service Manual stop valve. The Lo-knob should be closed completely. ③ Turn off the R410A tank and the Hi-knob immediately, when the adding refrigerant is enough. ④ Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and completely. 2) If the pressure of the system is too high to charge refrigerant, you can do as follow. ① Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and completely.
Super Free Match Service Manual 7 Electrical Wiring Work 7.1 Wiring Connection The “L1”, “3” terminals are connected to the live wire, the “L2”,”N(1)” terminals are connected to the neutral wire and the ”2” terminal is connected to the transmission line. 7.
Super Free Match Service Manual The length of the recommended power cable should be less than 15 meters; otherwise, the diameter of the power cable is not enough. Mentioned power cable and transmission line length is just a reference value. It may be different depending on the condition of installation, humidity or materials, etc. An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring. 7.
Super Free Match Service Manual 7.6 Electrical Wiring Work for Outdoor Unit 1) 2) 3) 4) 5) 6) 7) 8) Knock the holes in the plate of the chosen direction with the hammer. Place the rubber ring on the knockout hole. Let the power cable and transmission line go through the knockout hole. Connect the power cable of the outdoor unit to the L1, L2 terminals with the sign of the XT1 and as well as the ground screw.
Super Free Match Service Manual b) FXA3A-D and FXA3B-D c) FXB5A-D NO. 1 2 3 Name Terminal black for BU module power supply Terminal black for transmission line Ground screw NO. 4 5 6 Name Terminal black for indoor unit power supply DIP switch Printed circuit board 3) 4) 5) 6) 7) INSTALLATION Let the power cable and transmission line go through the rubber ring.
Super Free Match Service Manual 8) 9) Fix the power cable and transmission line firmly by cable fixing clip. Screw the electrical equipment plate. Caution! The transmission line and the power cable must be separated and separated with an interval of at least 2cm; otherwise it may be result in communication problem. Confirm the each cable connected to the terminal screw is exactly and securely after finishing the electric work. Fix each ground wire separately with the ground screw.
Super Free Match Service Manual 6) Recover the surface panel. 7) The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube. 8 INSTALLATION OF DRAINAGE PIPELINE 8.1 Material Quality Requirements for Condensate Pipe Generally, the condensate pipe shall be water supply U-PVC pipe, adhered by using special glue. The other materials available include: PP-R pipe, PP-C pipe and hot-dipped galvanized steel pipe.
Super Free Match Service Manual 6) 7) 8) Do not tie the condensate pipe and refrigerant pipe together. To ensure smooth drainage of condensate, a vent hole shall be set at the highest point of drainage pipe. Carry out water flow test and full water test after the pipe connection is completed. On one hand, check if the drainage is smooth; on another hand, check the piping system for any leakage. 9) Steel sheath shall be provided to the pipe crossing the wall or slab.
Super Free Match Service Manual 14) The long drainage pipe may be fixed by using hanger bolts, thus to ensure a gradient of 1/100 (PVC cannot be bent). The spacing between the supports of horizontal pipe is 0.8-1.0m. Twisting will be caused and thus air bag will be formed if the spacing is too high. Once the air bag is formed, the pump can only compress the air bag no matter how forcible it pushes, but there is no flowing water, thus resulting in abnormal water level.
Super Free Match Service Manual 16) Connection of drainage branch pipe to the standpipe or horizontal pipe of drainage main pipe. The horizontal pipe cannot be connected to the vertical pipe at a same height. It can be connected in a manner as shown below: No.1: 3-way connection of drainage pipe joint No.2: Connection of drain elbow No.3: Connection of horizontal pipe Drainage pipe is requisite for air conditioner unit.
Super Free Match Service Manual 9 Installation of Protective Layer on Connection Pipe 1) 2) 3) 4) 5) 6) 7) The refrigerant pipes should be insulated by the heat insulation material and plastic tape in order to prevent water condensation and leakage. Do not use the foam on the branch pipe as the material for heat insulation. The heat insulation material: Heat resistance to 100℃ or more; Thickness of 9mm or more.
Super Free Match Service Manual MAINTENANCE 115 N MAINTENANCE
Super Free Match Service Manual MAINTENANCE 1 Testing Board Introduction 1.1 Compose of Testing Board The testing board is in front of electrical box and can be observed well. It has several following advantages: detect indoor unit numbers and indoor unit address, displays real running function and error code automatically. It is composed of the function section, data section and button section. 1.
Super Free Match Service Manual 1.3 Process Control Setting 1.3.1 Button section Key Fuc + - Enter Back Signification Function Increase Decrease Enter Back Caution! ① When entering the menu to set parameters, the function section will flash running codes and the data section will flash the current parameters. ② When the menu is set, the data section will flash “=”. After the “=” stops blinking, the unit will run the new parameters. 1.3.
Super Free Match Service Manual Back: Press “Back” key to the previous menu, and long press the “Back” key to exit the operation. ③ Display unit 1(d1) operation: When entering into the display unit 1: The function section display running code uninterrupted and the data section display the current value uninterrupted. “+” “-”Keys are invalid in the operation. ④ If no operation is performed within 1min, it will automatically return to the normal display. 1.3.
Super Free Match Service Manual 3) 4) current parameters. Switch with the “+” “-” to the target value, and then press “Enter” key: the function section display “Fo” code uninterrupted and the data section flashes the new parameters uninterrupted. After the unit is running in the “Fo” mode, please turn off the liquid stop valve. Check the low pressure by operating the testing board. If the low pressure is 0.03Mpa for more than 30 second, please turn off the gas stop valve.
Super Free Match Service Manual 2.2 Problem Handling The conditions listed below are not classified into errors.
Compressor power protection Super Free Match Service Manual L9 L9 Flash 21 times Fb Intermediate vapor injection temperature sensor error Compressor discharge temperature protection Flash 23 times E4 E4 Lack of refrigerant or jam protection Flash 31 times F0 F0 Normal operation Flash 1 time Frequency limitation for AC current Flash 2 times F8 Oil returning Flash 3 times F7 Defrosting Flash 4 times Frequency limitation for IPM temperature Flash 5 times EU Frequency limitation for PF
Super Free Match Service Manual Running mode conflicts E7 Communication error E6 E7 E6 indoor unit address Communication error between the main board and driving board P6 Communication error between the main board and testing board CE Gas sensor error of indoor unit Fn Humidity sensor error of indoor unit L1 Water full error of indoor unit E9 E9 Jumper terminal error of indoor unit C5 C5 Phase lack of power supply dJ Fan motor error of outdoor unit L3 Refrigerant recovery mode Fo
Super Free Match Service Manual Indoor unit E gas tube temperature sensor error Flash 9 time b7 b7 indoor unit address Indoor unit E liquid tube temperature sensor error Flash 10 times b5 b5 indoor unit address 3 FLOW CHART OF TROUBLESHOOTING Service personnel shall collect the malfunction information as much as possible and research them thoroughly, list these electrical parts which may cause malfunction, and shall be able to determine the specific reason and solve the faulted parts.
Super Free Match Service Manual 3.
Super Free Match Service Manual 3.
Super Free Match Service Manual 3.
Super Free Match Service Manual 3.
Super Free Match Service Manual 3.
Super Free Match Service Manual 4 POWER DISTRIBUTION 4.1 Diagram of Power Distribution (The thick line represents power line while thin line represents the control line.
Super Free Match Service Manual 4.2 Wiring diagram Note: This drawing is just for reference; please always refer to the electric wiring stuck to the unit for actual wiring. 4.2.
Super Free Match Service Manual 4.2.
Super Free Match Service Manual ◆ Cozy GWH09MB-D3DNA3D/I; GWH12MB-D3DNA3D/I; GWH18MC-D3DNA3D/I; GWH24MD-D3DNA3D/I 2) Duct type GFH(09)EA-D3DNA1A/I; GFH(12)EA-D3DNA1A/I; GFH(18)EA-D3DNA1A/I; GFH(21)EA-D3DNA1A/I; GFH(24)EA-D3DNA1A/I MAINTENANCE 132
Super Free Match Service Manual 3) Cassette GKH(12)BA-D3DNA2A/I; GKH(18)BA-D3DNA2A/I; GKH(24)BA-D3DNA1A/I 4) Floor ceiling GTH(09)BA-D3DNA1A/I; GTH(12)BA-D3DNA1A/I; GTH(18)BA-D3DNA1A/I; GTH(24)BA-D3DNA1A/I 133 N MAINTENANCE
Super Free Match Service Manual 5) Console GEH(09)AA-D3DNA1C/I; GEH(12)AA-D3DNA1C/I; GEH(18)AA-D3DNA1C/I 4.2.
Super Free Match Service Manual FXA3A-D; FXA3B-D 135 N MAINTENANCE
Super Free Match Service Manual FXB5A-D MAINTENANCE 136
Super Free Match Service Manual 5 THE RESISTANCES OF COMMON TEMPERATURE SENSORS 5.1 15 KΩ Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) -20 144.000 0.472 0.311 20 18.750 2.222 1.467 -19 138.100 0.490 0.323 21 17.930 2.278 1.503 -18 128.600 0.522 0.345 22 17.140 2.334 1.540 -17 121.600 0.549 0.362 23 16.390 2.389 1.577 -16 115.000 0.577 0.381 24 15.680 2.445 1.613 -15 108.700 0.
Super Free Match Service Manual Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) 61 3.579 4.037 2.664 66 2.998 4.167 2.750 62 3.454 4.064 2.682 67 2.898 4.190 2.766 63 3.333 4.091 2.700 68 2.797 4.214 2.781 64 3.217 4.117 2.717 69 2.702 4.237 2.796 65 3.105 4.143 2.734 70 2.611 4.259 2.811 Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) Temp.
Super Free Match Service Manual Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) 34 13.59 2.977 1.965 55 5.942 3.855 2.544 35 13.04 3.027 1.998 56 5.726 3.887 2.565 36 12.51 3.076 2.030 57 5.519 3.919 2.586 37 12 3.125 2.063 58 5.32 3.949 2.607 38 11.52 3.173 2.094 59 5.13 3.979 2.626 39 11.06 3.220 2.125 60 4.948 4.008 2.646 40 10.62 3.266 2.155 61 4.773 4.037 2.
Super Free Match Service Manual Temp. Resistance (℃) (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) 2 145.42 0.322 0.212 45 21.425 1.591 1.050 3 138.26 0.337 0.223 46 20.601 1.634 1.078 4 131.5 0.353 0.233 47 19.814 1.677 1.107 5 126.17 0.367 0.242 48 19.061 1.721 1.136 6 119.08 0.387 0.256 49 18.34 1.764 1.164 7 113.37 0.405 0.267 50 17.651 1.808 1.193 8 107.96 0.424 0.280 51 16.99 1.853 1.
Super Free Match Service Manual Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) Temp. (℃) Resistance (kΩ) Voltage (15K/5V) Voltage (15K/3.3V) 88 4.7541 3.389 2.237 110 2.4983 4.001 2.640 89 4.6091 3.423 2.259 111 2.4308 4.022 2.655 90 4.4693 3.456 2.281 112 2.3654 4.044 2.669 91 4.3345 3.488 2.302 113 2.3021 4.064 2.682 92 4.2044 3.520 2.323 114 2.2409 4.085 2.696 93 4.0789 3.551 2.344 115 2.1816 4.105 2.709 94 3.9579 3.582 2.
Super Free Match Service Manual 6 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS 6.1 Outdoor Unit 6.1.1 Disassembly and Assembly of the plates Remarks: Prior to the assembly of the plates, make sure the power supply is cut off. Steps Illustrations 1.Disconnect the coping plate 2.Disconnect the front side plate 3.Disconnect the outer case MAINTENANCE 142 Operation Instructions a) b) a) Unscrew the fixed screws of the coping plate; Remove the coping plate.
Super Free Match Service Manual a) 4.Disconnect the left side plate and rear side plate Unscrew the fixed screws of left side plate and rear side plate; b) Remove left side plate and rear side plate. 6.1.2 Assembly and Disassembly of the Compressor Remarks: Prior to the assembly of the compressor, make sure there is no refrigerant in the pipeline and the power supply is cut off. Steps Illustrations Operation Instructions a) 1.
Super Free Match Service Manual 3.Loose the fixed screws of the compressor base Twist off four nuts for compressor with wrench Unscrew the fixed screw of the compressor base 4.Remove the compressor away from the seating Remove and replace the compressor. Note: never let the flame contact any other component during the replacement. 5.Fix the new compressor on the seating Tighten the screws on the seating of the new compressor.
Super Free Match Service Manual 6.Solder the pipeline with the suction and discharge ports of the compressor Solder the connecting pipe to make them connected Note: never let the flame contact any other component. a) 7.Reconnect the power cords Tighten the fixing screw of the power cord. b) Connect the power cord. Note: mark the color of the power cord and corresponding terminal. 8.Put back the electric heating belt and the discharge temperature sensor etc. a) 9.
Super Free Match Service Manual 6.1.3 Disassembly and Assembly of 4-way valve Remarks: Prior to the assembly of the compressor, make sure there is no refrigerant in the pipeline and the power supply is cut off. Steps Illustrations Operation Instructions 1.Remove the magnet coil of the 4-way valve a) Unscrew the fixed screws of the magnet coil; b) Remove the magnet coil. 2.Disconnect the 4-way valve and the connecting pipe Solder off the connecting pipes.
Super Free Match Service Manual 6.2 Indoor unit 6.2.1 Wall mounted type ◆ Removal and Assembly of Fan Motor Remark: Prior to the assembly of the motor, make sure the power supply is cut off. Steps Illustrations Operation Instructions a) b) 1.Remove the front panel, front case and electric box Loosen the screws; Unplug the motor terminals in the electric box. Loosen the earth screws and lift up Unscrew the fixed screws of the evaporator, and then remove it 2.Remove the evaporator a) 3.
Super Free Match Service Manual a) Remove the filter screen Unscrew the fixed screws of the return air 2.Remove the cover plate for return air b) 3.Remove the rear volute Undo the buckle of the rear and front volutes and then remove the rear volute away. 4. Remove the front volute Unscrew the fixed screws of the front volute and then remove it away 5.
Super Free Match Service Manual a) Separate the motor away from the motor support. b) Remove the fan blade c) Take the motor out from the return air frame Note: the motor support shall be removed in advance and then changed to the unit. 6. Remove the motor away. Assemble the fan as the reverse disassembly order and then take a power-on test. 7.Replace with a new motor 6.2.
Super Free Match Service Manual 3.Unscrew the fixed bolts of the fan Unscrew the fixed bolts of the fan with the spanner 4.Remove the fan Remove the fan 5.
Super Free Match Service Manual 6.Remove the motor and replace it Remove the motor and replace it 7.Screw the fixed bolts of the motor Screw the fixed bolts of the motor 8.
Super Free Match Service Manual 9.Mount the water tray and screw the screws Mount the water tray and screw the screws ◆ Removal and Assembly of drainage pump Remark: Prior to the assembly of the drainage pump, make sure the power supply is cut off. Steps Illustrations Operation Instructions 1.Unscrew the fixed screws of the water tray Unscrew the fixed screws of the water tray 2.
Super Free Match Service Manual 3. Pull out the drainage pipe and unscrew the fixed screws the water pump. Pull out the drainage pipe and unscrew the fixed screws the water pump. 4.Take out the pump and replace it Take out the pump and replace it 5. Connect the drainage pipe and screw the fixed screws the water pump. Connect the drainage pipe and screw the fixed screws the water pump. 6.
Super Free Match Service Manual 6.2.4 Floor ceiling type Remark: Prior to the assembly of the indoor unit, make sure the power supply is cut off. ◆ Removal panel grating module Steps Illustrations Move down the clip of the sub-assy of fromt grill until the front grill is open. (As is shown in the graph, arrow represents the position of bottons. There are two clips for each grating.
Super Free Match Service Manual ◆ Remove air deflecting plate modules Steps Illustrations Remove the air deflecting plates from the air deflecting plate support assembly, and then remove both ends from the air sweeping motor. joint (As is shown in the graph, arrow represents the support assembly and circle the air sweeping motor joint.
Super Free Match Service Manual ◆ Remove fixing plate sub-assy for air sweeping fans Steps Illustrations Remove fixing plate sub-assy for air sweeping fans ◆ Remove fan and motor components Steps Operation Instructions Remove the screws shown in the graph Illustrations Operation Instructions 1. Remove front and back scroll cases Press the buckle at the joints of front and back scroll cases with hands and pull upward to remove the front scroll case. Then remove the screws on the back scroll case.
Super Free Match Service Manual 7 EXPLODED VIEWS AND PART LIST 7.1 Outdoor unit Parts list: MULTIU48HP230V1BO NO.
Super Free Match Service Manual 19 20 21 Liquid side stop Valve Underlay groupware Electrical Heater(compressure) 22 Magnet Coil 07330000002 1 01894100090 1 7651521215 1 4304000425 1 23 Electromagnetic Valve 43000054 1 24 Electromagnetic Valve groupware 43044100234 1 25 Electromagnetic Valve groupware 43044100232 1 43003091 1 Magnet Coil 4304000439 1 28 Chassis Sub-assy 01194100051P 1 29 Drainage Connecter 06123401 1 30 Nage hole Cap 06813401 3 26 Electromagnetic Va
Super Free Match Service Manual 7.2 Indoor unit 7.2.1 Wall mounted type ◆ Hansol GWH09TB-D3DNA1A/I; GWH12TB-D3DNA1A/I; GWH18TC-D3DNA1A/I Part list: GWH09TB-D3DNA1A/I for CB148N02200; GWH12TB-D3DNA1A/I for CB148N02300; GWH18TC-D3DNA1A/I for CB148N04000; NO.
Super Free Match Service Manual 6 Guide Louver (small) 10512127 1 10512127 1 1051222601 1 7 Crank 10582070 2 10582070 2 10582070 2 8 Helicoid Tongue sub-assy 2611224404 1 2611224404 1 2611236701 1 9 Left Axile Bush 10512037 2 10512037 2 1051203701 2 10 Propeller Axile Bush 1054202101 1 1054202101 1 1054204701 1 11 Evaporator Support 24212114 1 24212114 1 24212139 1 12 Evaporator Assy 01002364 1 01002364 1 0100238601 1 13 Cross Flow Fan 10352033 1 10
Super Free Match Service Manual GWH24TD-D3DNA1A/I Part list: GWH24TD-D3DNA1A/I for CB148N03800 NO.
Super Free Match Service Manual 13 O-Gasket of Cross Fan Bearing 76512203 1 14 Left Evaporator Support 24212041 1 15 Evaporator Assy 01002340 1 16 Wall Mounting Frame 01252398 1 17 Right Evaporator Support 2421204201 1 18 Fan Motor 1501213401 1 19 Motor Fixed Clip1 26112324 1 20 Motor Fixed Clip2 26112325 1 21 Pipe Clamp 26112071 1 22 Fixed Clip(Evaporator) 02112009 1 23 Drainage Hose 0523001403 1 24 Rubber Plug (Water Tray) 76712012 1 25 Step Motor 152124020
Super Free Match Service Manual ◆ U-Cool GWH09UB-D3DNA1A/I; GWH12UB-D3DNA1A/I Part list: GWH09UB-D3DNA1A/I for CB204N00800; No.
Super Free Match Service Manual 10 Rear Case Assy 22202234 1 22202220 1 11 Rubber Plug (Water Tray) 76712012 1 76712012 1 12 Drainage Hose 05230014 1 05230014 1 13 Axile Bush Sub-assy 10542024 1 10542024 1 14 Damping Washer Sub-assy 76512011 1 76512011 1 15 Fan Bearing 76512210 1 76512210 1 16 Evaporator Support 24212128 1 24212128 1 17 Evaporator Assy 0100229401 1 01002294 1 18 Shield Board (Elbow) 01382010 1 01382010 1 19 Motor Press Plate 26112261
Super Free Match Service Manual GWH18UC-D3DNA1A/I Part list: GWH18UC-D3DNA1A/I for CB204N01200 NO.
Super Free Match Service Manual 16 Evaporator Support 24212135 1 17 Evaporator Assy 01002956 1 18 Shield board (elbow) 01382010 1 19 Wall Mounting Frame 01252032 1 20 Motor Press Plate 26112295 1 21 Fan Motor 1501209803 1 22 Pipe clamp 26112164 1 22 Step Motor 15212125 1 24 Step Motor 15212126 1 25 Crank 73012005 2 26 Electric Box Assy 20302297 1 27 Electric Box 2011213401 1 28 Electric Box Cover 2012215801 1 29 Electric Box Cover2 2012215903 1 30 Dis
Super Free Match Service Manual ◆ Cozy GWH09MB-D3DNA3D/I; GWH12MB-D3DNA3D/I Part list: GWH09MB-D3DNA3D/I for CB171N04500; NO.
Super Free Match Service Manual 12 Left Axile Bush 10542037 1 10542037 1 13 Air Louver 1 10512164 1 10512164 1 14 Guide Louver 10512157 1 10512157 1 15 Front Case Panel Assy 2001213931 1 2001213931 1 16 Filter Sub-Assy 1112220403 2 1112220403 2 17 Front Panel Assy 20012548 1 20012548 1 18 Screw Cover 24252016 3 24252016 1 19 Capacitor 33010002 1 33010002 1 20 Jumper 4202300107 1 4202300108 1 21 Electric Box Cover 2 2012207504 1 2012207504 1 22 Main
Super Free Match Service Manual GWH18MC-D3DNA3D/I、GWH24MD-D3DNA3D/I Part list: GWH18MC-D3DNA3D/I for CB171N04700; GWH24MD-D3DNA3D/I for CB171N07000 NO.
Super Free Match Service Manual 13 O-Gasket sub-assy of Bearing 7651205102 1 7651205102 1 14 Cross Flow Fan 10352019 1 10352030 1 15 Evaporator Support 24212133 1 24212103 1 16 Evaporator Assy 01002575 1 0100257204 1 17 Wall Mounting Frame 01252218 1 01252032 1 18 Motor Press Plate 26112494 1 26112316 1 19 Fan Motor 1501214601 1 15012136 1 20 Pipe Clamp 26112164 1 26112164 1 21 Drainage hose 05230014 1 0523001401 1 22 Step Motor 15012086 1 1501300101
Super Free Match Service Manual 7.2.2 Duct type GFH(09)EA-D3DNA1A/I; GFH(12)EA-D3DNA1A/I Part list: GFH(09)EA-D3DNA1A/I for CN210N0070; GFH(12)EA-D3DNA1A/I for CN210N0060 No.
Super Free Match Service Manual 13 Terminal Board 420111041 1 420111041 1 14 Main Board 30226338 1 30226338 1 15 Capacitor 33010020 1 33010027 1 16 Electric Box Sub-Assy 01395200071 1 01395200071 1 17 Electric Box assy 01395200034 1 01395000001 1 18 Electric Box Cover 01424253 1 01424253 1 19 Cover Plate of the Fan 01265300 1 01265300 1 20 Bottom Cover Plate 01265299 1 01265299 1 21 Supporter 01895225 2 01895225 2 22 Bar Clasp 70819522 4 70819522 4
Super Free Match Service Manual GFH(18)EA-D3DNA1A/I Part list: GFH(18)EA-D3DNA1A/I for CN210N0080; NO.
Super Free Match Service Manual 10 Rear volute casing 26905206 3 11 Bottom Cover Plate 01265332 1 12 Transformer 4311023303 1 13 Terminal Board 420111041 1 14 Main Board 30226338 1 15 Capacitor 33010027 1 16 Electric Box Sub-Assy 01395200071 1 17 Electric Box assy 01395000001 1 18 Electric Box Cover 01424253 1 19 Temperature Sensor 390001982G 1 20 Ambient Temperature Sensor 39000206 1 21 Cover Plate of the Fan 01265333 1 22 Fan Motor 15705218 1 23 Bar Cla
Super Free Match Service Manual GFH(21)EA-D3DNA1A/I; GFH(24)EA-D3DNA1A/I Part list: GFH(21)EA-D3DNA1A/I for CN210N0080; GFH(24)EA-D3DNA1A/I for CN210N0090 NO.
Super Free Match Service Manual 9 Front volute casing 26905205 4 10 Rear volute casing 26905206 4 11 Bottom Cover Plate 01265337 1 12 Transformer 4311023303 1 13 Terminal Board 420111041 1 14 Main Board 30226338 1 15 Capacitor 33010027 1 16 Electric Box Sub-Assy 01395200071 1 17 Electric Box assy 01395000001 1 18 Electric Box Cover 01424253 1 19 Cover Plate of the Fan 01265338 1 20 Temperature Sensor 390001982G 1 21 Ambient Temperature Sensor 39000206 1 22
Super Free Match Service Manual 7.2.
Super Free Match Service Manual Part list: GKH(12)BA-D3DNA2A/I for CN510N0060; GKH(18)BA-D3DNA2A/I for CN510N0070 NO.
Super Free Match Service Manual GKH(24)BA-D3DNA1A/I 179 N MAINTENANCE
Super Free Match Service Manual Part list: GKH(24)BA-D3DNA1A/I for CN510N0080 NO.
Super Free Match Service Manual 7.2.4 Floor ceiling type GTH(09)BA-D3DNA1A/I; GTH(12)BA-D3DNA1A/I; GTH(18)BA-D3DNA1A/I; GTH(24)BA-D3DNA1A/I Part list: GTH(09)BA-D3DNA1A/I for CN610N0060; GTH(12)BA-D3DNA1A/I for CN610N0070; GTH(18)BA-D3DNA1A/I for CN610N0050; GTH(24)BA-D3DNA1A/I for CN610N0080 NO.
Super Free Match Service Manual 5 Front Connecting Plate 01349414P 1 01349414P 1 01349414P 1 6 Base Frame 26909448 1 26909448 1 26909448 1 7 Air Lead Plate sub-assy 02229418 1 02229418 1 02229418 1 8 Supporter(Motor) 01805288 1 01805288 1 01805288 1 9 Mid-clapboard sub-assy 01249427 1 01249427 1 01249427 1 10 Front volute casing 26905205 4 26905205 4 26905205 4 11 Rear side plate assy 01319440 1 01319440 1 01319440 1 12 Centrifugal fan 10425200 4 10
43 Display Board 30294220 1 30294220 1 Super Free Match Service Manual 30294220 1 44 Terminal Board 420111041 1 420111041 1 420111041 1 45 Capacitor CBB61 33010089 1 33010026 1 33010027 1 46 Electric Box Cover 01429420 1 01429420 1 01429420 1 47 Transformer 43110257 1 43110257 1 43110257 1 48 Main Board 30226350 1 30226350 1 30226350 1 49 Electric Box 01429419 1 01429419 1 01429419 1 50 Room Sensor 3900019822 1 3900019822 1 3900019822 1 7.2.
Super Free Match Service Manual 5 Temp.
Super Free Match Service Manual 7.3 BU Module FXA2A-D; FXA2B-D; FXA3A-D; FXA3B-D Part list: FXA2A-D for EN01300120; FXA2B-D for EN01300080; FXA3A-D for EN01300130; FXA3B-D for EN01300090. NO.
Super Free Match Service Manual Heat Insulation 10 Pipe 1220552703 1 1220552703 1 1220552703 1 1220552703 1 11 Rubber Ring 76510031 1 76510031 1 76510031 1 76510031 1 12 Rubber Ring 76510021 1 76510021 1 76510021 1 76510021 1 13 Fixed Plate 3 01844100008P 1 01844100008P 1 01844100008P 1 01844100008P 1 14 Sponge(Coping plate) 12204437 1 12204437 1 12204437 1 12204437 1 4304413215 1 4304413215 1 4304413215 1 4304413215 1 15 Electric Expansive Loop 430
Super Free Match Service Manual FXB5A-D Part list: FXB5A-D for EN01300140; NO.
Super Free Match Service Manual 23 Heat Insulation Pipe 2(Gas) 75094100006 5 24 Liquid Branch Pipe 04224100290H 1 25 Heat Insulation Pipe 5(Liquid) 75094100004 5 26 Heat Insulation Pipe 1(Liquid) 75094100003 1 4304413208 1 4304413215 1 4304413222 1 4304413216 1 4304413217 1 27 Electric Expansive Loop 28 Temperature Sensor Assy 39008000044G 1 29 Terminal Board 42011154 2 30 Terminal Board 4201115402 1 31 Terminal Board 420111041 5 32 Electric Plate 01244100012 1
CAT NO: GREE_MULTIU_SERVICE_48MBH_070119 JF00303439