6.2 Working Temperature Range
Table 6.2
Test Condition
Indoor Side Outdoor Side
DB
°C(°F)
WB
°C(°F)
DB
°C(°F)
WB
°C(°F)
Nominal Cooling 26.7(80.0) 19.4(67.0) 35.0(95.0) 23.9(75.0)
Nominal Heating 21.1(70.0) 15.6(60.0) 8.33(47.0) 6.11(43.0)
Rated Cooling 26.7(80.0) 19.4(67.0) 46.1(115.0) 23.9(75.0)
Low Temp. Cooling 19.4(67.0) 13.9(57.0) -18.0(0) −
Rated Heating 26.7(80.0) − 23.9(75.0) 18.3(65.0)
Low Temp. Heating 20.0(68.0) − -18.0(0) -
Note:
① .
The design of this unit conforms to the requirements of ARI 210/240-2008 standard.
② .
If the static pressure is different, the air volume will be different, and then performance will be affected.
③ .
Cooling (heating) capacity stated above is measured under nominal working conditions
corresponding to standard external static pressure. The parameters are subject to change with
the improvement of products, in which case the values on nameplate take precedence.
④ .
In this table, there are two outside DB values under the low temp cooling conditions, and the
one in the brackets is for the unit which can operate at extreme low temperature.
7 Troubleshooting and Maintenance
7.1 Troubleshooting
If your air conditioner suffers from abnormal operation or failure, first check the
following points:
Table 7.1
Failure Possible Reasons
The unit cannot be started.
① .
The power wire is not connected.
② .
Electrical leakage of air conditioner causes tripping of the leakage
switch or GFi Breaker.
③ .
The operating buttons are locked.
④ .
The control loop has failure.
The unit operates for a
while and then stops.
① .
There is obstacle in front of the condenser.
② .
The control loop is abnormal.
③ .
Cooling operation is selected when the outdoor ambient temperature is
above 46°C(115°F).
U-match Series Cassette Type Unit