Service Manual

Table Of Contents
U-Match Series DC Inverter Service Manual
11
3.2 Operation Range
Mode
Range of Outdoor Temperature
Cooling
-18.0(0)~48.0(118.4)
Heating
-18.0(0)~24.0(75.2)
3.3 Electrical Data
3.3.1 Outdoor unit
Table 1-3-1 Electrical Data of Outdoor Unit
Model
Compressor
Fan Motor
Fuse/Breaker
Capacity
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protection
Power Supply
Qty.
RLA
FLA
V/Ph/Hz
A
A
A
A
A
GUHD18ND3FO
208/230V ~ 60Hz
1
12.0
1.5
5/25
17
25
GUHD24ND3FO
208/230V ~ 60Hz
1
18.0
1.5
5/40
24
40
GUHD30ND3FO
208/230V ~ 60Hz
1
18.0
1.5
5/40
24
40
GUHD36ND3FO
208/230V ~ 60Hz
1
21.2
2.0
5/45
29
45
GUHD42ND3FO
208/230V ~ 60Hz
1
21.2
2*2.0
5/50
31
50
GUHD48ND3FO
208/230V ~ 60Hz
1
32.5
2*2.0
5/70
45
70
3.3.2 Indoor unit
Table 1-3-2 Electrical Data of Indoor Unit
Model
Power Supply
Fan Motor FLA
Fuse/Breaker
Capacity
Minimum Circuit
Ampacity
Maximum
Overcurrent
Protection
V/Ph/Hz
A
A
A
A
GFH18D3FI
208V/230V ~ 60Hz
0.6
5/15
1
15
GFH24D3FI
208V/230V ~ 60Hz
1.3
5/15
2
15
GFH30D3FI
208V/230V ~ 60Hz
1.3
5/15
2
15
GFH36D3FI
208V/230V ~ 60Hz
2.1
5/15
3
15
GFH42D3FI
208V/230V ~ 60Hz
2.1
5/15
3
15
GFH48D3FI
208V/230V ~ 60Hz
4.0
5/15
5
15
GKH18D3FI
208V/230V ~ 60Hz
0.5
5/15
1
15
GKH24D3FI
208V/230V ~ 60Hz
0.5
5/15
1
15
GKH30D3FI
208V/230V ~ 60Hz
0.9
5/15
1.5
15
GKH36D3FI
208V/230V ~ 60Hz
0.9
5/15
1.5
15
GKH42D3FI
208V/230V ~ 60Hz
0.9
5/15
1.5
15
GKH48D3FI
208V/230V ~ 60Hz
1.5
5/15
2
15
GTH18D3FI
208V/230V ~ 60Hz
0.6
5/15
1
15
GTH24D3FI
208V/230V ~ 60Hz
0.6
5/15
1
15
GTH30D3FI
208V/230V ~ 60Hz
1.4
5/15
2
15
GTH36D3FI
208V/230V ~ 60Hz
1.4
5/15
2
15
GTH42D3FI
208V/230V ~ 60Hz
1.4
5/15
2
15
GTH48D3FI
208V/230V ~ 60Hz
2.1
5/15
3
15