57
1.1.5 Installation Clearance Data
2500mm
(98-3/8inch)
Nut with
Washer
Nut Spring
Washer
250mm
(9-7/8inch)
250mm
(9-7/8inch)
Figure 3-1-7
Warning! The height of installation for the indoor unit should be 2.5m (8-1/5ft) above.
1.1.6 Drain Piping Work
Installation of Drainage Pipeline:
Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enough to
prevent condensation. Problems with the piping may lead to water leaks.
(1) (Install the drain hose with downward gradient (1/50 to 1/100) and no risers or traps are used for
the hose (Figure 3-1-8).
(2) Be sure there is no crack or leak on the drain hose to avoid the formation of air pocket (Figure
3-1-8).
(3) When the hose is long, install supporters (Figure 3-1-9).
(4) Always use the drain hose which has been insulated properly.
Drain hose
Arrange the drain hose
lower than this drain port
Trap
Air bleeding
Rise
Figure 3-1-8