Specification

UL Classified.
See complete marking on back of packaging
Cellulose
Insulation
BLOW-IN
OR
SPRAY-APPLIED
FACT SHEET
25lbs (11.3kg)
SANCTUARY
®
R-Value at 75° F Mean Temp.
Valor de resistencia termica (valor R)
a 75 F de temperature media
Minimum Thickness (inches)
Espesor minimo (en pulgadas)
Net Coverage (no adjustment for framing)
Cobertura neta (sin compesación para la estructura)
Initial Installed Thickness
Espesor inicial instalado
Settled Thickness
Espesor asentado
Maximum Sq. Ft. per Bag
Pies cuadrados máximos por bolsa
Minimum Bags per 1,000 Sq. Ft.
Cantidad minima de bolsas por 1,000 pies cuadrados
Minimum Weight per Sq. Ft.
Peso minimo por pie cuadrado
Net Coverage (adjusted for 2" x 6" framing on 16" centers)
Cobertura neta (con compensación para una estructura de 2" x 6" en centros de 16")
Maximum Sq. Ft. per Bag
Pies cuadrados máximos por bolsa
Minimum Bags per 1,000 Sq. Ft.
Cantidad minima de bolsas por 1,000 pies cuadrados
THE ABOVE COVERAGE CHART IS BASED ON A NOMINAL BAG WEIGHT OF 25 LBS USING A VOLUMATIC III, 3RD
GEAR AND 8" GATE. THE CHART IS BASED ON SETTLED THICKNESS AND IS FOR ESTIMATING PURPOSES ONLY.
DO NOT EXCEED MAXIMUM SQUARE FEET COVERAGE PER BAG. THE APPLICATOR MUST INSTALL BOTH THE
MINIMUM NUMBER OF BAGS PER 1000 SQ. FT. AND THE MINIMUM INSTALLED THICKNESS TO ENSURE THE
STATED R-VALUE HAS BEEN REACHED. FAILURE TO MEET BOTH THESE REQUIREMENTS MAY PREVENT THE
APPLICAITON OF SPECIFIED R-VALUE.
JOB CONDITIONS, APPLICATION TECHNIQUES, EQUIPMENT AND SETTINGS
CAN INFLUENCE ACTUAL COVERAGE. MINIMUM NET WEIGHT IS 23.75 LBS.
THE ABOVE COVERAGE CHART IS BASED ON A NOMINAL BAG WEIGHT OF 25.0 LBS USING A VOLUMATIC III, 3rd
GEAR AND 8" GATE. THE CHART IS BASED ON SETTLED THICKNESS AND IS FOR ESTIMATING PURPOSES ONLY.
DO NOT EXCEED MAXIMUM SQUARE FEET COVERAGE PER BAG. THE APPLICATOR MUST INSTALL BOTH THE
MINIMUM NUMBER OF BAGS PER 1000 SQ. FT. AND THE MINIMUM INSTALLED THICKNESS TO ENSURE THE
STATED R-VALUE HAS BEEN REACHED. FAILURE TO MEET BOTH THESE REQUIREMENTS MAY PREVENT THE
APPLICATION OF SPECIFIED R-VALUE. THE INSTALLED MOISTURE CONTENT MUST BE BETWEEN 16% AND 22%
IN ATTIC APPLICATIONS. JOB CONDITIONS, APPLICATION TECHNIQUES, EQUIPMENT, AND SETTINGS CAN
INFLUENCE ACTUAL COVERAGE. MINIMUM NET WEIGHT IS 23.75 LBS.
11
13
19
22
26
30
32
38
40
44
48
49
50
60
3.3
3.9
5.7
6.6
7.7
8.9
9.5
11.2
11.8
12.9
14.0
14.3
14.6
17.3
3.0
3.6
5.3
6.1
7.2
8.3
8.8
10.4
10.9
12.0
13.0
13.3
13.5
16.1
78.6
65.8
44.2
38.0
31.2
25.9
23.8
19.0
17.7
15.7
14.1
13.8
13.5
10.8
0.32
0.38
0.57
0.66
0.80
0.97
1.05
1.32
1.41
1.59
1.77
1.81
1.86
2.31
86.7
72.6
48.8
41.2
33.4
27.4
25.2
19.9
18.6
16.5
14.6
14.2
14.0
11.1
12.7
15.2
22.6
26.3
32.1
38.6
42.0
52.6
56.5
63.5
70.8
72.6
74.3
92.5
11.5
13.8
20.5
24.2
30.0
36.5
39.7
50.1
53.8
60.8
68.5
70.2
71.4
89.8
AT TIC COVERAGE CHART – LOOSE-FILL AND STABILIZED APPLICATIONS
LOOSE-FILL APPLICATIONS STABILIZED APPLICATIONS
Tabla de Cobertura de Ático - Aplicaciónes de Relleno Suelto y Aplicaciónes Estabilizadas
This coverage chart is based on the Volumatic III, 2nd gear, 6" gate. The installed moisture content must be between 25% and 35% as measured by a
hand held moisture meter. Do not cover the insulation until the insulation moisture content, measured and documented after a minimum period of 24
hrs from the time of installation, reaches 25% or less in accordance with Greenfiber's Wallspray Manual. Install dry dense pack Sanctuary insulation
in all exterior wall sections where added vapor impediments, such as cabinets, mirrors, tubs, and shower enclosures are located. If unsure where
impediments are located, dry dense pack the entire exterior wall section(s). Non-standard or unusual wall configurations (i.e., other than 2x4 and 2x6
walls) can affect thermal and sound properties and require special installation considerations. These types of designs should be analyzed and, if
necessary, tested prior to plan review. Contact Greenfiber technical representative for applications or framing that is not included on these charts.
Spray-Applied Sidwall Applications (2.75 pcf minimum installed density)
Thermal Resistance
(R value)
Resistencia térmica
(R)
Framing
Estructura
Installed Thickness
(Inches)
Espesor instalado (pulgadas)
Minimum Wt Per Square foot
lb/ft
2
Pesonimo por pie cuadrado
lb/ft
2
Maximum Coverage per Bag
(Adjusted for Framing)
Cobertura máxima por bolsa (con compensación para la estructura)
16
16 pulgadas o.c. pie2/bolsa
inch o.c.
ft
2
/Bag
24 pulgadas o.c. pie2/bolsa
24 inch o.c.
ft
2
/Bag
2 x 4
2 x 6
13
21
3.5
5.5
0.79
1.24
35.0
22.3
33.8
21.6
SIDEWALL COVERAGE CHART SPRAY-APPLIED APPLICATIONS
SANCTUARY
®
Dry Dense-Pack Sidewall & Floor Applications (3.5 pcf minimum installed density)
Thermal Resistance
(R value)
Resistencia térmica
(R)
Framing
Estructura
Installed Thickness
(Inches)
Espesor instalado (pulgadas)
Minimum Wt Per Square foot
lb/ft
2
Pesonimo por pie cuadrado
lb/ft
2
Maximum Coverage per Bag
(Adjusted for Framing)
Cobertura máxima por bolsa (con compensación para la estructura)
16
16 pulgadas o.c. pie2/bolsa
inch o.c.
ft
2
/Bag
24 pulgadas o.c. pie2/bolsa
24 inch o.c.
ft
2
/Bag
This coverage chart is for dry applications only and is based on the Krendl KS200, with material applied dry.
2 x 4
2 x 6
2 x 8
13
21
28
3.5
5.5
7.5
1.02
1.60
2.19
27.0
17.2
12.6
26.1
16.6
12.1
SIDEWALL & FLOOR COVERAGE CHART – DENSE-PACK APPLICATION
SANCTUARY
®
Tabla de Cobertura Lateral y del Piso - Aplicaciónes de Paquete Denso
Tabla de Cobertura Lateral - Aplicaciónes Aplicadas por Spray
PM-6.3328 Rev C 05/20
Wilkes-Barre, PA 18702
Debert, Nova Scotia
Norfolk, NE 68701
Mesa, AZ 85212
Salt Lake City, UT 84119
Tampa, FL 33605
Waco, TX 76704
Manufactured by
US Greenfiber, LLC
Toll-Free 800-228-0024
www.greenfiber.com
Greenfiber is a registered
trademark of US Greenfiber, LLC.
© 2020 US Greenfiber, LLC.
All rights reserved.
US Greenfiber, LLC
5500 77 Center Drive, Suite 100
Charlotte, NC 28217
Made in USA
WHAT YOU SHOULD KNOW ABOUT R-VALUES
READ THIS BEFORE YOU BUY
This chart shows the R-Value of this insulation. R means
resistance to heat flow. The highter the R-Value, the greater
the insulating power. Compare insulation R-Values before you
buy. There are other factors to consider. The amount of the
insulation you need depends on the climate you live in. Also,
your fuel savings from isulation will depend upon the climate,
the type and size of your house, the amount of insulation
already in your house, and your fuel use patterns and family
size. If you buy too much insulation, it will cost you more than
what you’ll save on fuel. To get the marked R-Value, it is
essential that this insulation be installled properly.

Summary of content (1 pages)