Installation Guide

Installation Instructions
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Model # ONW-D-1001-DMV-N-W
Model # ONW-D-1001-DMV-N-V
Model # ONW-D-1001-DMV-N-LA
Model # ONW-D-1001-DMV-N-G
Model # ONW-D-1001-DMV-N-B
NeoSwitch Dual Technology Dual Relay
Occupancy Sensing Wall Switch
(Neutral Required)
General Information
Technology: Passive Infrared (PIR) and Ultrasonic (US)
Electrical Ratings:
120 VAC:
• Incandescent/Tungsten – Max. load: 6.7 amps,
800W, 50/60 Hz
• Fluorescent/Ballast – Max. load: 10 amps,
1200W, 50/60 Hz
Motor Load: ¼ HP @ 125 VAC
230/277 VAC:
• Fluorescent/Ballast – Max. load: 9.8 amps,
2700W, 50/60 Hz
Ballast Compatibility: Compatible with magnetic and
electronic ballasts
No Minimum Load Requirement
Time Delays: Self-Adjusting, 15 seconds/test (10 min
Auto), Selectable 5, 15, 30 minutes
Coverage: Major motion – 1000 sq. ft.
Minor motion – 300 sq. ft.
Light Level Sensing: 0 to 200 foot-candles
Operating Environment:
• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: 20% to 90% Non-condensing
Housing: Durable, injection molded housing.
Polycarbonate resin complies with UL 94VO.
Size:
• Mounting Plate/Strap Dimensions:
4.195" H x 1.732" W (106.553 mm x 44 mm)
• Product Housing Dimensions: 2.618" H x 1.752"
W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)
LED Indicators: Red LED indicates PIR detection;
Green LED indicates Ultrasonic detection; Green LED
acts as EcoMeter or night light locator.
Specifications
Description
Coverage
The ONW-D-1001-DMV-N Occupancy Sensing Wall Switch is a Passive Infrared (PIR) and Ultrasonic (US) motion
sensing lighting control and conventional wall switch all-in-one, used for energy savings and convenience.
The sensor combines PIR and US technologies to monitor a room for occupancy.
PIR Technology
The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature
that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.
US Technology
The sensor produces a low intensity, inaudible sound. It detects occupancy from changes in the acoustic waves
caused by motion, such as reaching for a telephone, turning a page in a book, walking into a room, turning in a
swivel chair, etc. The sensor does not respond to audible sound.
Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications thus saving
additional energy. PIR is used to turn the lights ON and then either technology will keep the lights ON.
The ONW-D-1001-DMV-N allows the control of two separate loads with one occupancy sensor switch.
Energy Saver Mode – Either or both loads may be configured to turn ON manually. The default setting for the
second load is Manual ON. This ensures the wall switch only activates one load. If both loads are ON when the
sensor times-out, only the primary load will be activated. If the lights were shut OFF manually, the unit will activate
the primary load only.
In Automatic ON Mode, the lights turn ON automatically when a person enters the room. In Manual ON Mode, the
lights are turned ON by pressing the universally recognized light icon pushbutton. In either mode, the lights stay ON
as long as the sensor detects motion in the room. When the room is vacated, the lights turn OFF automatically after
a preset time delay interval.
The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and
time delay in real-time. By adjusting sensitivity and time delay automatically, the sensor is maximizing the potential
energy savings that are available in the particular application.
The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding
individuals to take control of their lighting to maximize energy savings.
The ONW-D-1001-DMV-N is designed for offices up to 300 square feet.
Location
When installing the ONW-D-1001-DMV-N in a new junction box, choose the switch location carefully to provide
optimum coverage of the occupied area. When replacing an existing wall switch, bear in mind that there must be a
clear line-of-sight between the sensor and the area to be covered. Avoid pointing the ONW-D-1001-DMV-N directly
into the hallway where it may detect passers-by.
Installation
The ONW-D-1001-DMV-N can be installed in any standard single gang box. It may be
installed in the same manner as an ordinary wall switch.
• Wire the ONW-D-1001-DMV-N as described in the wiring section
• Mount the ONW-D-1001-DMV-N in the junction box
EcoMeter Operation
Load 1 Load 2 EcoMeter LED
OFF OFF 100%
ON OFF 50%
OFF ON 50%
ON ON OFF
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used
as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All
installations should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements.
3. Mount unit to wall box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install wall switch plate.
The Daylighting feature prevents
lights from turning ON, when the room is
adequately illuminated by natural light.
The Walk-Through feature maximizes
energy savings by not leaving the lights
ON after a momentary occupancy. The
sensor will switch the lights ON when
it detects a person entering the area. If
the sensor does not continue to detect
motion 20 seconds following the initial
activation, it will automatically go to a
shorter 2 minute time delay.
Bathroom Mode – When selected,
bathroom mode keeps the second relay ON for an additional 8 minutes, after the first relay has been turned OFF.
Combine this with changing the pushbutton to the light/fan graphic and you now have the universally recognized and
easy to use bathroom solution.
Relay Swap Option – A common problem in electric wiring is wiring the wrong switch to the wrong load. This can
make control of loads confusing to an end user. The Relay Swap option solves the problem by allowing the switch
buttons on the face of the unit to be swapped, after the unit is wired and installed.
Action
EcoMeter Benefit
A person enters the space and one of
the loads is activated
50% Increased awareness of energy savings
Both loads are on OFF
The area is vacated and the lights
turn OFF automatically
100%
Increased awareness of energy savings;
Acts as a night light locator
A person turns the lights OFF
manually upon exiting an area
100%
Increased awareness of energy savings
and reminds individuals to take control of
their lighting for additional savings;
Acts as a night light locator
If the Daylighting function is
activated for one of the two loads
and there is sufficient daylight in the
space, the unit will hold the load OFF
50%
Increased awareness of energy savings;
Lets persons know that the daylight
sensor is holding the lights OFF
If the Daylighting function is
activated for both loads and there
is sufficient daylight in the space,
the unit will hold the loads OFF
100%
Increased awareness of energy savings;
Lets persons know that the daylight
sensor is holding the lights OFF
,
36
8
,
Minor Motion, IR
Major Motion, IR
20
,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
,
10
8
,
,
15
20
,
P/N 9850-000320-01
• Read all instructions on both sides of this
sheet first
• Install in accordance with ALL local codes
• For indoor use only
LOAD 2
LOAD 1
120 to 277 VAC
BLACK
RED
BLUE
RED
NEUTRAL
GROUND
GREEN
WHITE
Wiring Diagram 1: 120 to 277 VAC dual level single circuit wiring diagram

Summary of content (2 pages)