OSW-P – 120/277V PIR/Single Level Wall Switch Sensor (Ground Required)
www.coopercontrol.com
Specifications
Technology
Passive Infrared (PIR)
Electrical
Ratings
120 VAC:
Incandescent/Magnetic Low Voltage/Magnetic
Ballast – Max. load: 15A, 1800W, 60 Hz
LED/Compact Fluorescent/Electronic Low Voltage/
Electronic Ballast – Max. load: 10A, 1200W, 60 Hz
Motor Load: 1/2 HP @ 125 VAC
277 VAC:
Magnetic Low Voltage/Magnetic Ballast/LED/
Compact Fluorescent/Electronic Low Voltage/
Electronic Ballast - Max. Load: 8A, 2200W, 60 Hz
No Minimum Load Requirement
Time Delays
Selectable 5 seconds/test, 5 minutes (factory
default), 10 and 30 minutes
Coverage
Major motion - 1000 sq. ft.
Minor motion - 300 sq. ft.
Light Level
Sensing
0 to 200 foot-candles
Operating
Environment
Temperature: 32°F – 104°F (0°C to 40°C)
Relative humidity: 20% to 90% non-condensing
For indoor use only
Housing
Durable, injection molded housing. Resin complies
with UL 94V-0
Size
Mounting Plate/Strap Dimensions:
4.2”H x 1.8”W (106.5mm x 46mm)
Product Housing Dimensions:
2.87”H x 1.6”W x 1.42”D (72.8mm x 40.7mm x
36mm)
LED Indicators
Red LED for Ultrasonic detection
Standards
FCC Compliant
cULus Listed
RoHS Compliant
Description/Operation
OSW-P-1001-MV is designed to detect motion from a heat-emitting
source (such as a person entering a room) within its field-of-view
and automatically switch lights ON. These sensors have multi-
segmented lenses. For units to sense motion, the person must
cross between two segments. The distance between segments
increases the farther you are from the sensor, so motion has to be
larger the farther you are from the unit. PIR sensors are considered
line-of-sight sensors, meaning that the sensor must be able to
have a direct line-of-sight to the person making the motion. In
Automatic On Mode, the lights turn ON when a person enters the
room. In Manual On Mode, the lights are turned ON by pressing the
pushbutton. The sensor provides true multi-way ON/OFF control.
When lights have been activated, the lights will remain ON as long
as one of the sensor(s) continue to detect motion. The occupant may
manually turn OFF the lighting by pressing the ON/OFF button on
any of the connected devices. If the room becomes vacant and the
lights are ON, the lights will turn OFF when the unit that detected
motion last times-out.
Applications
Private ofces
Small conference rooms
Lunch/break rooms
Small classrooms
Small restrooms (no stalls)
Small lounge rooms
Small waiting rooms
Small closets
Small storage areas
Wiring Diagram
Single Level Switching
SENSOR IN ONE LOCATION
Light Fixture
White
Neutral
Ground
Bare
Green
3-Way
Blue
Black
Hot
Black
120/277V
Hot
Black
Relay OUT
Red
120/277V
Orange
Relay IN
Three-way wiring
Black Traveler
SENSORS IN BOTH LOCATIONS
Light
Fixture
Red Traveler
White
Neutral
3-Way
Blue
3-Way
Blue
Relay OUT
Red
Black
Relay OUT
Red
120/277V
Ground
Bare
Green
Relay IN
Orange
Black Traveler
Ground
Bare
Green
Relay IN
Orange
Hot
Black
120/277V
Hot
Black
120/277V
Hot
Black
Black Traveler
*For additional wiring diagrams refer to Installation Instructions