E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 1 of 19 Manual for connection and operation of EASYBus-control, display and supervisory device EB 3000 as of Version 1.7 GREISINGER electronic GmbH D - 93128 Regenstauf, Hans-Sachs-Straße 26 Tel.: 09402 / 9383-0, Fax: 09402 / 9383-33, e-mail: info@greisinger.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 2 of 19 INDEX 1. SAFETY REGULATIONS .......................................................................................................................................... 3 2. INTRODUCTION ........................................................................................................................................................ 4 2.1. EASYBUS-terms and definitions .......................................................
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 3 of 19 1. Safety regulations This device was designed and tested considering the Safety regulations for electronic measuring devices. Faultless operation and reliability in operation of the measuring device can only be assured if the General Safety Measures and the devices specific safety regulation mentioned in this users manual are considered. 1.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 4 of 19 2. Introduction The EB3000 is an universal control, display and supervisory device for EASYBUS-sensor modules. The EB3000 is equipped with 20 internal channels (channel-nr. 1..20), which can be allocated arbitrary to different EASYBUS-measurement channels and 2 virtual channels (channel-nr. 21 and 22), to download arbitrary calculation functions. Furthermore the EB3000 has 4 switching outputs and an alarm output.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 5 of 19 3.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 6 of 19 4. Electric connection Electric connection and commissioning of the device must be carried out by trained and skilled personnel. Wrong connection may lead to the destruction of the device, in which case we cannot assume any warranty. Make it a rule to always mount screw-type/plug-in terminals while they are still loose and connect only later.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 7 of 19 4.3. Connection example sensor module sensor module 2 wire cable PC level converter EBW1,EBW 64.. mains: 230V EB 3000 Top side alarm output switching outputs Example for connection Hint: In order to avoid undefined input states and unwanted or wrong switching processes, we suggest to connect the device’s switching outputs after You have configured the device properly. 4.3.1.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 8 of 19 5. Commissioning and configuration of the EB3000 For configuration and commissioning of the EB3000 the software EASYBus-configurator is necessary. You will find this software for free on one of our different product-CD’s or on homepage www.greisinger.de under area SERVICE beneath FREEWARE. 5.1.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 9 of 19 6.2. How to display or reset the min-/max-values You can call and display the min-/max-values of the EASYBUS-measurement channels by using EB3000. Hint: The EB3000 can only readout the respective min-/max-values. The values stored in the respective sensor modules will not be saved in the EB3000. If a min-/max-value is shown, LED „min“ resp. „max“ illuminates. Key-operating: - Key 1 shortly pushed: - Key 1 pushed >1 sec.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 10 of 19 Hint: A call is only possible, if the display of the device shows the actual value - Push key 1 and 3 for >1 second. In the display “AL.Hi“ appears (alarm high, max-alarm limit). - Push key 2 or 3. In the main display the currently adjusted max-alarm limit appears. - Use key 2 and 3 for setting the desired new value, when max-alarm shall be released.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 11 of 19 7. Error codes When detecting an operating state which is not permissible, or the current EASYBUS-measurement channel has an undefined operating state, the EB3000 will display an appropriate error code. The following error codes are defined. An errror code will displayed, if an EASYBUS-measurement channel with an occurred error is selected. Err.
E35.0.01.6C-03 Er.11: Manual for connection and operation of the EB 3000 page 12 of 19 Value could not be calculated Indicates a measuring value, needed for calculation of the display value, is faulty resp. out of range. For possible causes and remedies please read the operation manual of the EASYBUS-sensor module Er.12: Received datasets invalid Indicates, that the received EASYBUS-sensor module datasets for this EASYBUS-measurement channel is invalid. E.
E35.0.01.6C-03 ----: Manual for connection and operation of the EB 3000 page 13 of 19 no measurement channel allocated Indicates, that the displayed channel is configured with no allocated EASYBUS-measurement channel. t.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 14 of 19 8. Specification Display range: -1999 ... +9999 Digit Resolution: Automatically recognition of the resolution of the connected EASYBUSmeasurement channel. Decimal point is set automatically. Accuracy: Depending on the respective EASYBUS-measurement channel. The EB3000 is receiving this value digital without additional error. Sensors: All EASYBUS-sensor modules (inclusive EASYLOG , GIA20EB, GIR2002, ...
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 15 of 19 10. EB3000 - Configuration 10.1. EASYBUS - Configurator Please start software EASYBus-Configurator. The EASYBus-Configurator opening-window appears. Before starting of EASYBUS-Configuration some pre-adjustments must be arranged. Icon choose interface Icon perform EASYBUS system initialisation Icon read EASYBUS 10.1.1. Interface configuration With Icon „choose interface“ we reached setting-window interface configuration.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 EB3000Symbol 10.2. EB3000 - Configuration By double-click on the EB3000-symbol on the device-overview a configuration window for the EB3000 opens. Now 5 register-tabs are available: monitoring / display control outputs alarm virtual channels others 10.2.1.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 17 of 19 Here are 2 essential settings: 1) Allocation of the respective measurement channels - By measurement channel the EASYBUS-measurement channel with identification number is shown, which is allocated to the respective channel. Until 20 channels can be listed.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 18 of 19 10.2.2. Tab: control outputs Here is once again a listing of the measurement channels with allocation to the control outputs. A modification or reselection of the channels results via „drag and drop“ or through manually input of the respective channel number. - channel-nr. allocated measurement channel for this output. ( The regulation function is assigned to this measuring value ) - switch.
E35.0.01.6C-03 Manual for connection and operation of the EB 3000 page 19 of 19 10.2.4. Tab: virtual channels Here you can select functions for both „virtual channels“ for programming into the EB3000. If the desired function is not available, please visit our homepage. Here additional functions for download are available. After download copy transferred datafiles easily into directory „EB3CV“ inside of the configurator-installation directory.