E44.X.00.6C-02 Connection and operating manual GIR 300 page 12 of 28
Parameter Overflow for the available measuring types:
Measuring type
U
I
T.RES
T.TC
FREQ
RPN
[O.VP
[O.DN
SER,
Input signal / sensor
X
X
X
X
X
X
X
X
-
Signal edge
-
-
-
-
-
-
X
X
-
Devisor
-
-
-
-
-
X
X
X
-
Input signal low
-
-
-
-
X
-
-
-
-
Input signal high
-
-
-
-
X
-
X
X
-
Decimal point
X
X
X
-
X
X
X
X
-
Display low
X
X
-
-
X
-
-
-
-
Display high
X
X
-
-
X
-
X
X
-
Temperature unit
-
-
X
X
-
-
-
-
-
Limit
X
X
-
-
X
-
X
X
-
Filter
X
X
X
X
X
-
-
-
-
Address
-
-
-
-
-
-
-
-
X
Output
X
X
X
X
X
X
X
X
X
5.2 Measuring voltage or current (0-50mV, 0-1V, 0-2V, 0-10V, 0-20mA, 4-20mA)
This chapter describes how you configure the device for measuring voltage- or current-signals from an external
transmitter. This instruction demands that you selected “U“ or “I“ as your desired input type like it is explained in chap-
ter 5.1. The display has to show “InP“.
- Press Button 1. The display shows “SEnS“.
- Select the desired input signal using button 2 or button 3 (middle or right button).
Display
Input signal
(voltage measuring)
Notes
10.00
0 – 10 V
2.00
0 – 2 V
1.00
0 – 1 V
0.050
0 – 50 mV
Display
Input signal
(current measuring)
Notes
4-20
4 – 20 mA
0-20
0 – 20 mA
- Validate the selected input signal by pressing button 1. The display shows “SEnS“ again.
- Press button 1 again, The display will show “dP“ (decimal point).
- Select the desired decimal point place by pressing button 2 or button 3.
- Validate the selected decimal position by pressing button 1. The display shows “dP“ again.
- Press button 1 again, the display will show “di.Lo“ (Display Low = low display value).
- Use button 2 and button 3 to select the desired value the device should display when a 0mA, 4mA or
0V input signal is attached.
- Validate the selected value by pressing button 1. The display shows “di.Lo“ again.
- Press button 1 again, the display will show “di.Hi“ (Display High = high display value).
- Use button 2 and button 3 to select the desired value the device should display when a 20mA, 50mV,
1V, 2V or 10V input signal is attached.
- Validate the selected value by pressing button 1. The display shows “di.Hi“ again.
SENS
DP
D,.K,