- Do not attempt to open or repair the unit without qualified electrician while
it is malfunctioned.
- The following conditions may cause lower sensitivity:
- In very foggy nights, the sensitivity may be less due to moisture collecting
on the lens.
- In very hot days, the sensitivity may be less since high ambient
temperature is close to body temperature
- In very cold days when heavy clothing is dressed, especially the facial
area is covered, very little heat will be emitted from the body causing the
unit to be less sensitivity.
- Cleaning wipe with dry cloth only. Soap or rough cloth may damage the
detector lens.
NOTE
4.4.5 Walk Test
NOTE
LED will turn on for 60sec at first time to switch the power on of detector or
power is re-supplied again after the power is shut off, then turn off. During
the of warming up period, the load is uncontrolled by Lux setting. Once any
movement is detected after warming up period, it will enter into normal
mode. If no movement is detected within 15sec, load will turn off
automatically and won't be controlled by pre-set timer but enter into standby
mode immediately
4.5.1 LED function
4.5.1.1 The LED of Mc Guard is behind the lens. (See FIG. 16)
4.5.1.2 In the walk test, LED will turn on for 2 sec once the detector is
triggered. It is uncontrolled by Lux setting and can be regarded as
indicator. Under manual on 4hrs mode. LED turns ON 1sec and OFF
5sec as indication.
4.5.1.3 LED remains OFF either in AUTO mode or OFF mode.
FIG. 15
FIG. 17
4.5.2 Test procedure
The purpose of conducting walk test is to select a proper installation place
to get the best detection range. Set the slide switch at the position of AUTO,
TIME knob to “Test”, then conduct a walk test referring to step 4.5.2.1 to
4.5.2.7 and Lux is disabled (See FIG. 17).
FIG. 16
4.5.2.1 Install the detector correctly, refer to FIG.5 - FIG.7 to make sure
correct wiring.
4.5.2.2 Switch the power on.
4.5.2.3 Walk from outside across to the detection pattern, once the detector
is triggered, LED and load will all turn on for 2sec.
4.5.2.4 Refer to point "4.4 Usage of lens shield label", detection range and
angle can be changed by adjusting lens shield.
4.5.2.5 Repeat the step 4.5.2.3 and 4.5.2.4 until it meets user's demands.
4.5.2.6 Pay attention to the walking direction while proceeding the test
(See FIG. 3)
Start
Finish
When Detector works abnormally, check assumptive problems and
suggested solutions in following table that be will hopefully to solve your
problem.
5 TROUBLE SHOOTING
Problem Possible cause Suggested solution
LED
does
not turn
on.
1.Power does not
switch on.
2.Incorrect wiring.
1.Switched on the power.
2.Refer to wiring diagrams
and connect wiring
correspondingly.
Lights
do not
turn on.
1.
2.Defective load.
3.The slide switch is
set at OFF.
Incorrect wiring.
1.
connect wiring correspondingly.
2.Replace the defective load with a
new one.
3. Adjust slide switch to AUTO or ON.
Refer to wiring diagrams and
Lights
do
not turn
off.
1.TIME setting is too
long or detector is
continuously
triggered.
2.Incorrect wiring.
1.Setting TIME at test mode, check
whether the detector is nuisance
triggered.Keep away from detection
zone to avoid activating detector
2.Refer to wiring diagrams and
connect wiring correspondingly.
Nuisance
triggering
There are heat
sources or any objects
which may sway in the
wind within the
detection field.
Avoid aiming the detector toward
any heat sources, such as air
conditioners, electric fans, heaters or
any highly reflective objects. Make
sure there are no swaying objects
within the detection field.
Push
button
does not
work.
1.
2.Defective switch.
Incorrect wiring
1.Please check if the push button is
connected between R and L.
2.Replace the push button with a
new one.
7 GUARANTEE
GROTHE GmbH presence sensor is manufactured according to
the latest techniques and subjected to quality control.
If however, a defect should occur, GROTHE GmbH provides a
warranty to the following extent.
1. The warranty covers 24 months from date of purchase of the
device by the final end user. Compliance with the claim deadline
is to be demonstrated by voucher of purchase date by means of
an included invoice, delivery note, or similar document.
2. The guarantee includes the correction or resupply of a device
(according to our dicretion) if the function of the device is limited
or non existing due to proven material or manufacturing errors.
3. The warranty does not cover damage during the transport. Moreover,
damages on account of not following the instruction concerning
installation and unprofessional installation of the device.