SQFlex Service Instructions

10 / 60
Trouble-shooting by means of CU 200
Indication/Fault Possible cause Remedy
1. No light in front
cover.
Pump does not
deliver water.
No voltage supply.
Reestablish the voltage supply.
Position of ribbon cable
connector is wrong or
cable is defective.
Correct the position of the cable or replace it.
2. No light in front
cover, and pump
does not deliver
water. But the LEDs
inside CU 200 indi-
cating 5 V, 10 V and
24 V internal supply
voltage are on, and
the ‘CONTROL
INDICATOR’ LED is
not flashing.
CU 200 is defective. Replace the CU 200.
3. Pump does not start.
Green indicator light
in ON/OFF button is
on.
No fault indicated.
CU 200 or pump is defec-
tive.
Check that the ‘CONTROL INDICATOR’ LED is
flashing. If not, replace the CU 200.
Check that there is sufficient voltage on the
PUMP terminals. If no voltage can be measured,
replace the CU 200.
If a supply voltage to the pump can be detected,
continue as follows:
Switch off the energy supply and wait for one
minute.
Switch on the energy supply and observe what
happens:
If the green indicator light in the ON/OFF button
is on and the pump still does not start, the pump
or pump cable is defective.
Repair or replace pump or cable.
4. Off light in the ON/
OFF button is on.
Pump has been stopped.
Press the ON/OFF button on the CU 200 to start
the pump.
5. CU 200 indicates
‘F3 = no contact to
pump’.
CU 200 defective.
Check
- the connection in the CU 200
- the pump cable
- the end cover with socket on the pump.
Pump cable or connec-
tions defective.
Pump is defective.
Repair or replace the pump.
6. CU 200 indicates
‘F1 = overvoltage’
Supply voltage is above
permissible range.
Disconnect the solar modules to allow the volt-
age to drop.
Reconfigure the modules and reconnect them.
If a different supply source is used, check that
the voltage is within the recommended voltage
range.
Note: As the voltage is detected at the motor, allow
for the voltage drop in the pump cable.
7. CU 200 indicates
‘F2 = overtempera-
ture’.
Too high water tempera-
ture.
Ensure that the water temperature is below the
maximum permissible level.
Incrustations on motor.
Remove incrustations on the motor.
Pump is defective.
Repair or replace the pump.