Overview of Primary Product

7
Functions
VersaFlo UP, UPS
Relay module
The relay module is an optional extra for single-head
and dual-head pumps.
The module enables direct connection of the pump to
line voltage and an external operating or fault indication
device. The signal output for an external signal device
can be set to activate during operation or fault by means
of the selector switch.
The signal outputs of relay modules in dual-head pumps
can be interconnected so that the pumps are operating
alternately as duty pump and standby pump.
The pump is connected directly to line voltage as the
pump incorporates overload protection at all three
speeds. If the pump has been cut out by the thermal
overload switch, it will restart automatically when it has
cooled to normal temperature
.
Indicator lights on relay module
The indicator lights on pumps with relay module have
more detailed operating and fault indications.
All pumps with relay module are equipped with a green
and a red indicator light. Their functions are as shown in
the table below.
Signal output of relay module
The relay module is equipped with a signal output for
external operating or fault indication.
By means of the selector switch, the output can be used
as:
Operation signal output between terminals 2 and 3
or
Fault signal output between terminals 1 and 3.
Functions of indicator lights and signal output
Note: Pumps with relay module must not be connected
to a frequency converter.
TM00 9236 4596
Relay
module
Speed
switch
Selector
switch for
signal output
Indicator lights Signal output
Description
Green Red Operation Fault
Off Off
The pump has been
stopped. The electricity
supply has been switched
off or a phase is missing.
Perma-
nently on
Off The pump is running.
Perma-
nently on
Perma-
nently on
Only three-phase pumps:
The pump is running, but
with wrong direction of
rotation.
Off
Perma-
nently on
The pump has been cut
out by the thermal over-
load switch.
Flashes Off
The pump has been
stopped by an external
on/off switch.
Flashes
Perma-
nently on
The pump is or has been
cut out by the thermal
overload switch and it
has been stopped by an
external on/off switch.