GRUNDFOS DATA BOOKLET UP Series Circulator pumps 60 Hz
UP Series Table of contents 1. 2. 3. 4. 5.
UP Series 1 Cross-reference charts 1. Cross-reference charts Cross-reference for competitive 3-speed pumps Competitor cross-reference Model Speed High ALPHA2 15-55 FC/FRC ALPHA1 15-55 FC/FRC Med. Low High UPS 15-58 FC/FRC Med.
UP Series 1 Cross-reference charts UPS 15-35 SUC/TLC UPS 15-55 SFC * 4 High - - Astro 20, 25BU(LC, T), Astro 25U-T Med. - - Astro 25U-T Low - - - High - - Med. 005-(B, SF), 006-BF, 007-(B, SF)(IFC), 008-(B, SF)-(IFC), 00R-SF-IFC LR-15B, NBF(SSF)-22, NBF-25 Low - - Grundfos provides no guarantee as to the accuracy of competitor information listed herein.
UP Series 1 Cross-reference charts Reference for replacing TACO models Open systems: Stainless steel and lead-free bronze pump housings 3/4" sweat UP 15-10 BUC7/TLC 5 3/4" sweat 99452458 - 3 5/16 1/2" sweat UP 15-10 BUC5/TLC 5 1/2" sweat 99452457 - - - - - 4 4 4 5 15/16 5 15/16 3 5/16 3 5/16 3 5/16 3 5/16 4 3 5/16 3 5/16 3 5/16 4 3/8 3/4" FNPT 3/4" FNPT 3/4" FNPT Union Union Union Union Union Union 3/4" NPT 3/4" FNPT 3/4" FNPT 3/4" FNPT 1/2" sweat UP 15-35 SUC UP 15-35 SUC UPS 15-35 SUC/
UP Series 1 Cross-reference charts Flange size/ connection type Grundfos model Port-to-port length [in] Flange size/ connection type 1 x 115 V 1 x 208 V 1 x 230 V 3 x 208 V 3 x 230 V 3 x 460 V 003-VRBC4IFC 003-VVBC4 003-VVBC41IFC 003-VVB4 003-VVBC4IFC Grundfos product number Port-to-port length [in] TACO model Competitor cross-reference for TACO Open systems: Stainless steel and lead-free bronze pump housings 4 3/8 3/4" sweat UP 15-42 BUC7/MR 7 1/4 3/4" sweat 59896806 - - - - - 4
UP Series Cross-reference charts 1 007-BF 007-BF5 007-BF-IFC 007-BF5-IFC 007-SF5 007-SF5-IFC Flange size/ connection type Grundfos model Port-to-port length [in] Flange size/ connection type 1 x 115 V 1 x 208 V 1 x 230 V 3 x 208 V 3 x 230 V 3 x 460 V 006-VRBC7IFC 006-VVBC4 006-VVBC71IFC 006-VVB4 006-VVBC7IFC 4 3/8 3/4" sweat UP 15-42 BUC7/MR 7 1/4 3/4" sweat 59896806 - - - - - 4 3/8 1/2" sweat - - - - - - - - - 4 3/8 1/2" sweat - - - - - - - - - 4 3/8 3/
UP Series 1 Cross-reference charts ALPHA2 15-55 SFC, ALPHA1 15-55 SFC 6 1/2 6 3/8 3/4" sweat UP 15-42 BUC7/MR 7 1/4 6 3/8 3/4" sweat UP 15-42 BUC7/MR 7 1/4 3/4" sweat 59896806 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6 3/8 3/4" sweat - - - - - - - - - 6 3/8 3/4" sweat - - - - - - - - - 6 3/8 Flange - - 009-SF5 6 3/8 2-bolt flange-R 009-SF5-IFC 6 3/8 2-bolt flange-R 0010-BF2 6 3/8 2-bolt flange - - 0010-BF3 6
UP Series Cross-reference charts 1 2-bolt flange 0013-SF3 6 1/2 2-bolt flange-R 0013-SF3-IFC 6 1/2 2-bolt flange-R 0014-BF 6 1/2 2-bolt flange-R 0014-BF-1 6 1/2 2-bolt flange 0014-BF1-1IFC 6 1/2 2-bolt flange 0014-SF1 6 1/2 2-bolt flange-R 0014-SF1-1IFC 6 1/2 2-bolt flange-R 0015-MSSF2IFC 0015-MSSF21IFC 6 1/2 6 1/2 2-bolt flange 2-bolt flange-R 1400-10B 6 3/8 2-bolt flange-R 1400-20B 6 3/8 2-bolt flange-R 1400-30B 8 1/2 2-bolt flange-R 1400-40B 8 1/2 2-bolt flange-R 1
UP Series 1 Cross-reference charts 2400-50S/2 6 3/8 2400-60S 8 1/2 2400-65S 8 1/2 2400-70S 8 1/2 2400-70S/3 8 1/2 2" 2-bolt flange 2" 4-bolt flange 2" 4-bolt flange 2" 4-bolt flange 3" 4-bolt flange UPS 40-160/2 B Magna 40-120 FN UPS 40-160/2 B 2" 4-bolt 96402787 flange* 8 1/2 3/4" to 1 1/2" 2" 4-bolt 11 1/2 96402787 flange* 11 1/2 3 x 460 V 3 x 230 V 3 x 208 V 1 x 230 V - 96402788 96402789 96402789 96402790 - 96734633 - 96734633 - 96402788 96402789 96402789 96402790 UPS 43-100 SF
UP Series 1 Cross-reference charts Closed systems: Cast iron pump housings - - - - UPS 15-58 FRC 005-F2 6 3/8 2-bolt flange ALPHA2 15-55 FRC, ALPHA1 15-55 FRC UPS 15-58 FRC 005-F2-2IFC 6 3/8 2-bolt flange ALPHA2 15-55 FRC, ALPHA1 15-55 FRC UPS 15-58 FC UPS 15-42 F 005-F2-3IFC 6 3/8 2-bolt flange-R 3/8 3/8 3/8 3/8 2-bolt 2-bolt 2-bolt 2-bolt flange flange flange flange ALPHA2 15-55 FC, ALPHA1 15-55 FC 005-VRF2 005-VRF2-2IFC 005-VVF2 005-VVF2-2IFC 6 6 6 6 UP 15-42 FC/MR UP 15-42 FC/MR
UP Series 1 Cross-reference charts 6 6 6 6 3/8 3/8 3/8 3/8 2-bolt 2-bolt 2-bolt 2-bolt flange flange flange flange - - UP 26-64 F/VS - 6 1/2 - ALPHA2 15-55 FC, ALPHA1 15-55 FC 6 1/2 2-bolt flange ALPHA2 15-55 FRC, 6 1/2 ALPHA1 15-55 FRC 2-bolt flange 008-F6-3 008-F6-1IFC - - - - - - - - - - - - - - - - - 2-bolt flange* - 52722553 99163903, 99163906, 99285998, 99287256 99163932, 99163934, 99287244, 99287259 99163903, 99163906, 99285998, 99287256 99163932, 99163934, 99287244
UP Series Cross-reference charts 1 0010-VVF3 6 3/8 2-bolt flange 0010-VVF31IFC 6 3/8 2-bolt flange 0011-F4 6 1/2 2-bolt flange-R 0011-F4-2IFC 6 1/2 2-bolt flange-R 0010-VSF3 6 3/8 2-bolt flange 0010-VSF31IFC 6 3/8 2-bolt flange 0011-VRF4 6 1/2 2-bolt flange-R 0011-VRF41IFC 6 1/2 2-bolt flange-R 3 x 460 V 2-bolt flange 3 x 230 V 6 3/8 3 x 208 V 0010-VRF31IFC 1 x 230 V 2-bolt flange 1 x 208 V 6 3/8 1 x 115 V 0010-VRF3 Flange size/ connection type 2-bolt flange 4-bolt flange
UP Series 1 Cross-reference charts Magna 32-100 F 6 1/2 2-bolt flange - 98071396 98071396 98071396 98071396 - 6 1/2 2-bolt flange-R Magna 32-100 F 6 1/2 2-bolt flange - 98071396 98071396 98071396 98071396 - 6 1/2 2-bolt flange-R Magna 32-100 F 6 1/2 2-bolt flange - 98071396 98071396 98071396 98071396 - 6 1/2 2-bolt flange-R UPS 26-99 FC Magna 32-100 F UPS 26-99 FC Magna 32-100 F Magna 32-100 F 6 6 6 6 6 2-bolt 2-bolt 2-bolt 2-bolt 2-bolt 52722512 52722513 98071396 98071396 98071396
UP Series Cross-reference charts 1 0015e-F4 6 1/2 2-bolt flange ALPHA2 15-55 FRC, 6 1/2 ALPHA1 15-55 FRC 2-bolt flange 6 3/8 2-bolt flange-R 1400-10 6 3/8 2-bolt flange-R 1400-20 6 3/8 2-bolt flange-R 1400-30 8 1/2 2-bolt flange-R 1400-40 8 1/2 2-bolt flange-R 1400-45 6 3/8 2-bolt flange-R 1400-50 6 3/8 2" bolt flange 1400-50/2 6 3/8 1400-60 1400-65 8 1/2 2-bolt flange-R 8 1/2 2-bolt flange-R 2" bolt flange 1400-70 8 1/2 4-bolt flange 1400-70/3 8 1/2 4-bolt flange UPS 26-99
UP Series 1 Cross-reference charts Reference for replacing Bell & Gossett models Open systems: Stainless steel and lead-free bronze pump housings NBF-12F/LW 6 3/8 2-bolt flange ALPHA2 15-55 SFC, ALPHA1 15-55 SFC 6 1/2 2-bolt flange* NBF-18S NBF-22U 5 6 3/8 1/2" sweat Union 2-bolt flange UP 15-42 B5 UPS 15-55 SUC UPS 15-55 SFC 5 5 7/8 6 1/2 1/2" sweat 1 1/4" U 2-bolt flange NBF-22 6 3/8 2-bolt flange ALPHA2 15-55 SFC, ALPHA1 15-55 SFC 6 1/2 2-bolt flange* 2-bolt flange UPS 15-55 SFC 6 1
UP Series Cross-reference charts 1 PL-36B 8 5/8 2-bolt flange PL-45B 9 3/8 2-bolt flange PL-50B 9 3/8 2-bolt flange PL-55B 9 9/16 2-bolt flange PL-75B 9 15/16 2" 3 x 460 V 2-bolt flange 3 x 230 V 8 5/8 3 x 208 V PL-30B 1 x 230 V 2" flange-R 1 x 208 V 8 1/2 1 x 115 V 2" AB UPS 15-55 SFC Magna 32-60 FN UPS 50-60 SF Magna 40-120 FN UPS 26-99 SF Magna 32-60 FN UPS 26-150 SF Magna 32-100 FN UPS 43-100 SF Magna 32-100 FN UPS 43-100 SF Magna 32-100 FN UPS 26-150 SF Magna 40-120 FN UPS
UP Series 1 Cross-reference charts 2" flange-R PL-30 8 5/8 2-bolt flange PL-36 8 5/8 2-bolt flange PL-45 9 1/8 2-bolt flange PL-50 9 1/8 2-bolt flange PL-55 9 9/16 2-bolt flange PL-75 9 15/16 2" 3 x 460 V 8 1/2 3 x 230 V 2" 3 x 208 V 2-bolt flange 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1 x 230 V 8 1/2 8 6 6 6 8 8 6 6 6 6 8 6 8 6 6 8 8 8 1 x 208 V Series PR UPS 43-44 FC Magna 32-60 F UPS 26-99 FC Magna 32-60 F UPS 50-44 FC Magna 40-120 F UPS 2
UP Series 1 Cross-reference charts Reference for replacing Laing models Open systems: Stainless steel and lead-free bronze pump housings 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" sweat sweat sweat sweat FNPT FNPT FNPT FNPT sweat sweat sweat sweat FNPT FNPT FNPT FNPT sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat sweat SM-9
UP Series 1 Cross-reference charts E10-BCFVNN1W-24 E10-BCSVNN1W-19 E10-BCSVNN1W-22 E10-BCUVNN1W-19 6 1/2 6 6 6 thermostatic controls Aquastat kit, 1/2" clip Aquastat kit, 3/4" clip Aquastat kit, 1/2" clip Aquastat kit, 3/4" clip on on on on 85-105 °F 85-105 °F 105-115 °F 105-115 °F ** Purchase timer control 599388 24-hour programmable clock/timer 20 - - - - - - - - - - - - 3 1/8 1/2" sweat 98420206 3 1/8 1/2" sweat 98420222 3 1/8 1/2" FNPT 98420210 3 1/8 1/2" FNPT 98420223 6
UP Series 1 Cross-reference charts Reference for replacing Armstrong models Open systems: Stainless steel and lead-free bronze pump housings - - - - - - - 5 1/2" sweat UP 15-10 B5/TLC 5 1/2" sweat 99452454 - - - - - 5 1/2" sweat - - - - - - - - - 5 3/4" sweat UP 15-10 B7 6 3/8 3/4" sweat 59896226 - - - - - 5 3/4" sweat UP 15-10 B7/LC 6 3/8 3/4" sweat 59896209 - - - - - 5 3/4" sweat UP 15-10 B7/TLC 6 3/8 3/4" sweat 99452455 - - - - - 5 3/4" sw
UP Series 1 Cross-reference charts Astro 50B 6 3/8 2-bolt flange-R Astro 50B-LC Astro 50B-T Astro 50B-TA 6 3/8 2-bolt flange-R 6 3/8 2-bolt flange-R 6 3/8 2-bolt flange-R Astro 50B-3 6 3/8 2-bolt flange-R Astro Astro Astro Astro 6 6 6 6 70B 70B-LC 70B-T 70B-TA 3/8 3/8 3/8 3/8 2-bolt 2-bolt 2-bolt 2-bolt flange flange flange flange S25B 6 1/2 Flange S35B 8 1/2 2" NPT H32B 8 1/2 Flange 3 x 460 V 3 x 230 V 3 x 208 V 1 x 230 V UPS 26-99 SFC Magna 32-100 FN UPS 26-99 SFC Magna 32-100 F
UP Series 1 Cross-reference charts Closed systems: Cast iron pump housings UPS 15-58 FRC Astro 230CI-R 6 3/8 Astro 250CI 6 3/8 6 1/2 2-bolt flange 2-bolt flange-R ALPHA2 15-55 FRC, 6 1/2 ALPHA1 15-55 FRC 2-bolt flange 2-bolt flange Astro 250CI-R 6 3/8 Astro 20F 6 3/8 2-bolt flange-R 2-bolt flange-R Astro 30 2-bolt flange-R 6 3/8 UPS 26-99 FC Magna 32-100 F UPS 15-58 FRC ALPHA2 15-55 FRC, 6 1/2 ALPHA1 15-55 FRC UP 15-42 FR UPS 15-58 FC Astro 30-3 6 3/8 2-bolt flange Astro 50 Astro 50-3 A
UP Series 1 Cross-reference charts Reference for replacing Wilo models Open systems: Stainless steel and lead-free bronze pump housings Star Z-15 BN5 3 1/8 Star Z-15 BS5 3 1/8 Star 3 BS 5 Star 3 BS 7 Star 5 B Star 5 BU Star Star Star Star 5 BFX 8 BS 5 8 BS 7 11 BF Star 11 BU Star 16 SF Star 16 BFX 1/2" union NPT 1/2" sweat 5 5 6 3/8 1/2" sweat 3/4" sweat 2-bolt flange 3/4" union 6 1" union 6 3/8 2-bolt flange-R 5 1/2" sweat 5 3/4" sweat 6 3/8 2-bolt flange 3/4" union 6 1" union 6 3/8 2-bolt flan
UP Series Cross-reference charts 1 3 x 208 V 3 x 230 V 3 x 460 V 1 x 115 V Flange size/ connection type 99163937, 6 1/2 2-bolt flange* 99163972, 99287250, 99287262 1 x 230 V ALPHA2 15-55 SFC, ALPHA1 15-55 SFC Port-to-port length [in] Grundfos model Flange size/ connection type 6 1/2 2-bolt flange-R Grundfos product number 1 x 208 V Stratos ECO 16BFX Port-to-port length [in] Wilo model Competitor cross-reference for Wilo Open systems: Stainless steel and lead-free bronze pump housings -
UP Series 1 Cross-reference charts Closed systems: Cast iron pump housings Star 5 FX Star 16 F 6 3/8 2-bolt flange-R 6 3/8 2-bolt flange UP 15-10 FR UP 15-10 F UPS 15-58 FRC Star 16 FX 6 3/8 2-bolt flange-R ALPHA2 15-55 FRC, ALPHA1 15-55 FRC UPS 15-58 FC Star S 16 F 6 3/8 2-bolt flange ALPHA2 15-55 FC, ALPHA1 15-55 FC UPS 15-58 FRC Star S 16 FX 6 3/8 2-bolt flange-R ALPHA2 15-55 FRC, ALPHA1 15-55 FRC Star 17 FX 8 1/2 2-bolt flange-R Star 21 F 6 3/8 Star 21 FX 6 3/8 2-bolt flange-R Star S 2
UP Series 1 Cross-reference charts Discontinued products These tables show the new products or part numbers which replace discontinued products or part numbers.
UP Series 1 Cross-reference charts ALPHA Cast iron, flanged 115 V Old model Product number New model Product number ALPHA 15-55F 59896877 ALPHA2 15-55F ALPHA 15-55F/LC (line cord) 59896832 ALPHA2 15-55F/LC 99163903 99163906 ALPHA 15-55FR 59896878 ALPHA2 15-55FR 99163932 ALPHA 15-55FR/LC (line cord) 59896833 ALPHA2 15-55FR/LC 99163934 Stainless steel, flanged 115 V 28 ALPHA 15-55SF 59896879 ALPHA2 15-55SF 99163937 ALPHA 15-55SF/LC (line cord) 59896834 ALPHA2 15-55SF/LC (line cord
UP Series 2 Performance ranges 2. Performance ranges ALPHA2 Performance and operating mode selection TM04 6025 0611 The hydraulic performance shown is without check valve. Pos. Description Pos. Description • Push-button for selection of pump setting • Every time the push-button is pressed, the circulator pump setting is changed. Constant pressure I • The duty point of the pump will move left and right along the lowest constant-pressure curve depending on the water demand in the system.
UP Series 2 Performance ranges ALPHA1 Performance and operating mode selection The hydraulic performance shown is without check valve. H [m] H [ft] 6 20 18 5 Constant Pressure III 16 14 4 12 10 Constant Pressure II 8 2 6 Constant Pressure I 4 1 2 0 0 0 0.0 Pos. 1 2 0.5 3 4 1.0 5 6 7 1.5 8 9 2.0 10 11 12 2.5 13 14 3.0 15 3.5 16 17 18 4.0 Q [US GPM] Q [m³/h] Description • Push-button for selection of pump setting.
UP Series 2 H [m] 14 12 Performance ranges UPS, 3-speed H [ft] UPS 45 60 Hz 40 UPS 26-150 35 10 30 8 6 25 20 15 4 UPS 15-58 10 2 5 0 0 0 5 10 15 20 25 30 35 40 45 50 55 Q [US GPM] 0 H [m] 2 4 6 8 10 Q [m³/h] TM04 5461 3209 UPS 26-99 H [ft] UPS 10 60 Hz 30 UPS 43-100 8 25 6 20 UPS 50-60 15 4 10 2 0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [US GPM] 0 5 10 15 20 25 Q [m³/h] TM04 5460 3209 UPS 43-44 5 31
UP Series 2 Performance ranges UPS, cross-reference 3-speed, stainless steel H [m] H [ft] UPS 18 5 60 Hz 16 14 UPS 15-55 4 12 3 10 8 2 6 UPS 15-35 4 1 0 0 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Q [US GPM] 0 1 2 3 4 5 Q [m³/h] TM04 5462 3209 2 UP 10-16 A/PM B5/BN5/BU H [m] H [ft] 1.2 4.0 UP10-16B5/BN5/BU 60 Hz 3.5 1.0 3.0 0.8 0.6 0.4 2.5 2.0 1.5 1.0 0.0 0.5 0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 Q [US GPM] 0.0 32 0.1 0.2 0.3 0.
UP Series 2 H [m] H [ft] 36 10 1. 2. 3. 4. 5. 6. 7. 8. 9.
UP Series 2 Performance ranges UP, open systems, 1/2" H [m] H [ft] 4 4.5 1. UP 15-42 B5 2. UP 15-18 B5 3. UP 15-10 B5 4. UP 15-42 BUC5 5. UP 15-18 BUC5 6. UP 15-10 BUC5 14 4.0 13 12 3.5 3.0 11 10 9 2.5 2.0 8 1 7 6 1.0 0.5 5 5 4 2 3 6 2 3 1 0.0 0 0 1 2 3 4 5 6 7 8 9 10 11 12 Q [US GPM] 0.0 0.5 1.0 1.5 2.0 Q [m³/h] TM03 9131 3507 1.5 UP, open systems, 3/4" H [m] H [ft] 7. UP 15-42 B7 8. UP 15-18 B7 9. UP 15-10 B7 10. UP 15-42 BUC7 11. UP 15-18 BUC7 12.
UP Series 3 Product range 3.
UP Series 3 Product range Bronze Product number Flow rate Open systems UP 10-16 PM B5/LC UP 10-16 A PM B5/LC UP 10-16 PM BN5/LC UP 10-16 A PM BN5/LC UP 10-16 A PM BU/LC UP 15-10 B5 UP 15-10 B5/LC UP 15-10 B5/TLC UP 15-10 B7 UP 15-10 B7/LC UP 15-10 B7/TLC UP 15-10 BUC5 UP 15-10 BUC5/LC UP 15-10 BUC5/TLC UP 15-10 BUC7 UP 15-10 BUC7/LC UP 15-10 BUC7/TLC UP 15-18 B5 UP 15-18 B5/LC UP 15-18 B5/TLC UP 15-18 B7 UP 15-18 B7/LC UP 15-18 B7/TLC UP 15-18 BUC5 UP 15-18 BUC7 UP 15-42 B5 UP 15-42 B5/LC UP 15-42 B5/TL
UP Series 3 Product number Flow rate Open systems 115 V UP 15-10 SU7P/DTLC*, UP 15-10 SU7P/TLC* ALPHA2 15-55 SF** ALPHA2 15-55 SF/LC** ALPHA1 15-55 SF*** ALPHA1 15-55 SF/LC*** UP 15-29 SF UP 15-29 SU UP 15-29 SU/LC UP 15-29 SUC/TLC UP 15-35 SUC UPS 15-35 SFC UPS 15-35 SUC UPS 15-35 SUC/TC UP 15-55 SUC UPS 15-55 SFC UPS 15-55 SUC UPS 15-55 SUC/TLC UP 26-96 SF UP 26-99 SF UPS 26-99 SFC UP 26-116 SF UPS 26-150 SF UPS 43-100 SF UPS 50-60 SF 595916, 99452459 99163937 99163972 99287262 99287250 59896771 59896
UP Series 4 Identification 4.
UP Series 4 UP 15-42F nameplate ALPHA2 control panel Class F IMPEDANCE PROTECTED I1/1 (A) P1 (W) .74 85 - FOR INDOOR USE ONLY MAX FLUID TEMP. 230F 10 11 12 13 14 15 99K4 UL C US LISTED Fig. 1 Pos. Nameplate, UP 15-42F Fig. 2 Description Non-submersible pump 2 Pump type 3 Voltage 115 V 4 Frequency 60 Hz 5 Capacitor 10 μF 6 Single-phase UP 15-42 F 7 Power 85 W 8 Current 0.
UP Series 5 Applications 5. Applications The Grundfos circulator pumps, series UP(S), are specifically designed for heating systems. The pumps are also suitable for recirculation of hot domestic water and for circulation of liquid in cooling and airconditioning systems. Heating systems Common uses: • Boiler/hydronic • ground-source • radiant floor • hydronic and fan-coil • solar • heat recovery.
UP Series 5 Description (ALPHA2, ALPHA1) Controller complete Rotor can Radial bearing Shaft Rotor cladding Thrust bearing Thrust bearing retainer Bearing plate Impeller Pump housing Gaskets Description (UP, closed systems) Inlet cone, bearing plate, bearing retainers, rotor can, rotor cladding, shaft retainer Stator housing Shaft, upper and lower radial bearings Material Description (UP, open systems) Composite, PC Stainless steel Ceramics Ceramics Stainless steel Carbon EPDM (ethylene propylene rubbe
UP Series 5 Pumped liquids The pump must always be installed with the motor shaft in horizontal position. See fig. 3. Proper installation of the pump will have the terminal box located to one side of the pump or the other with the conduit entry down. UP(S) pumps can be installed in both vertical and horizontal lines. UP(S) pumps are intended for indoor use only.
UP Series 5 UP(S) The maximum allowable water temperature is determined by the ambient air temperature as shown in the table below.
UP Series 5 Applications Maximum system pressure Performance 145 psi (10 bar). UP(S) models Minimum inlet pressure Flow range: 0-120 gpm (0 - 27.3 m3/h) Head range: 0-46 ft (0-14 m) The required minimum inlet pressure must be available at the pump inlet. The pressure required at the inlet of the pump is a function of the temperature of the water as shown in the tables below. ALPHA2 models UP(S) models ALPHA1 models Flow range: 0-17 gpm (0 - 3.9 m3/h). Head range: 0-19 ft (0 - 5.8 m).
UP Series 6 UP 10-16 Comfort PM, PM Auto UP 10-16 A/T/PM B5/BN5/BU H [m] H [ft] 1.2 4.0 60 Hz 1.0 3.0 0.4 2.5 1.5 1.0 0.2 0.0 Head range: 0 - 3.9 ft (0 - 1.2 m) Motor: Single-phase Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) 2.0 0.5 0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 Q [US GPM] 0.0 0.1 0.2 0.3 0.4 Q [m³/h] Model TM06 0178 4913 0.6 0 - 2.2 gpm (0 - 0.5 m3/h) Max.
UP Series 6 Technical data UP 10-16 Comfort PM, PM Auto, PM Temperature Temperature mode The UP 10-16 pump is designed for recirculation of domestic hot water in single-family homes with dedicated hot-water return piping. Utilizing a low-noise permanent magnet motor, energy consumption is reduced to as little as 6 W. Selecting the Auto mode ensures that the pump runs only when required. The result is maximum comfort - no waiting for hot water plus decreased water and power consumption.
UP Series 6 H [m] Head range: 0 - 6.2 ft (0 - 1.9 m) Motor: 2-pole, single-phase Max. liquid temperature: 220 °F (104 °C) Min. liquid temperature: 36 °F (2 °C) b Max. system pressure: 145 psi (10 bar) a Note: If the UP pump is equipped with a timer, the maximum liquid temperature is 150 °F (66 °C). H [ft] a. UP15-10B5 b. UP15-10B7 60 Hz 7 2.0 6 1.6 0 - 8.2 gpm (0 - 1.9 m3/h) Flow range: 5 Technical data UP 15-10 B5/B7 4 1.2 Model UP 15-10 B5 and B7 3 0.
UP Series 6 Technical data UP 15-10 BUC5/BUC7 H [m] 2.0 6.5 1.8 6.0 H [ft] a 5.5 a. UP15-10BUC5 b. UP15-10BUC7 60 Hz b 1.6 5.0 1.4 4.5 1.2 4.0 0 - 6.6 gpm (0 - 1.5 m3/h) Flow range: Head range: 0 - 6.6 ft (0-2 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Note: If the UP pump is equipped with a timer, the maximum liquid temperature is 150 °F (66 °C). 3.5 1.0 0.8 0.6 0.4 3.
UP Series 6 H [m] 2.0 0 - 8.0 gpm (0 - 1.8 m3/h) Flow range: H [ft] UP15-10F/FR 60 Hz 6 1.6 5 Head range: 0 - 5.5 ft (0 - 1.7 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Technical data UP 15-10 F/FR Closed system 1.2 4 Model 3 UP 15-10 F/FR 0.8 Volts Amps Watts Hp Capacitor 115 0.23 25 0.034 2 μF / 400 V Approvals 2 0.4 0.0 0 0 0.0 1 2 0.5 3 4 5 1.
UP Series 6 Technical data UP Comfort System UP 15-10 SU7P/TLC H [m] 1.2 UP15-10SU7P/TLC 60 Hz 4.5 0.6 0 - 5.1 ft (0 - 1.6 m) Motor: 2-pole, single-phase Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Open system 4.0 3.5 Model 3.0 UP 15-10 SU7P/TLC 1.0 0.8 Head range: Max. liquid temperature: 150 °F (66 °C) H [ft] 5.0 1.4 0 - 6.3 gpm (0 - 1.4 m3/h) Flow range: Volts Amps Watts 115 0.23 25 Hp Capacitor 0.034 2 μF / 400 V Approvals 2.5 2.0 1.
UP Series 6 H [m] H [ft] a. UP15-18B5 b. UP15-18B7 60 Hz 14 4.0 13 12 3.5 11 3.0 10 8 7 2.0 Head range: 0 - 13.9 ft (0 - 4.2 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Note: If the UP pump is equipped with a timer, the maximum liquid temperature is 150 °F (66 °C). 9 2.5 0 - 14.7 gpm (0 - 3.3 m3/h) Flow range: Model 6 UP 15-18 B5 5 1.5 4 a 1.
UP Series 6 Technical data UP 15-18 BUC5/BUC7 H [m] 5 H [ft] a. UP15-18BUC5 b. UP15-18BUC7 60 Hz 16 b 0 - 14.7 gpm (0 - 3.3 m3/h) Head range: 0 - 14.5 ft (4.4 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) 14 a 4 Flow range: Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) 12 3 10 Model UP 15-18 BUC5 UP 15-18 BUC7 8 Volts Amps Watts Hp Capacitor 115 115 0.74 0.74 86 86 0.115 0.
UP Series UP 15-29 SU/SF H [m] H [ft] 3.0 10 UP15-29 60 Hz Motor: 2-pole, single-phase 145 psi (10 bar) Open system 6 Note: If the UP pump is equipped with a timer, the maximum liquid temperature is 150 °F (66 °C). 5 4 3 Model 0 0 2 4 0 6 8 1 10 12 2 14 16 18Q [US GPM] 3 4 Q [m³/h] TM03 8847 4412 0.5 1 Volts UP 15-29 SF UP 15-29 SUC UP 15-29 SU 2 0.0 0 - 9.7 ft (0 - 2.2 m) Max. system pressure: 7 2.0 1.0 Head range: Min. liquid temperature: 36 °F (2 °C) 8 1.
UP Series 6 Technical data UP 15-35 SUC H [m] 4 H [ft] UP15-35SUC 60 Hz 12 Flow range: 0 - 17.5 gpm (0 - 4.0 m3/h) Head range: 0 - 11.5 ft (3.5 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) 3 10 Max. system pressure: 145 psi (10 bar) Open system 8 2 6 Model UP 15-35 SUC Volts Amps Watts Hp Capacitor 230 0.50 114 0.
UP Series UPS 15-35 SUC/SFC H [m] H [ft] 12 3.0 UPS15-35 60 Hz 3 3.5 Flow range: 0 - 21.5 gpm (0 - 4.9 m3/h) Head range: 0-12 ft (0 - 3.7 m) Motor: 2-pole, single-phase 11 Max. liquid temperature: 165 °F (74 °C) 10 Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) 9 2.5 8 2 7 Note: If the UP pump is equipped with a timer, the maximum liquid temperature is 150 °F (66 °C). 2.0 6 5 Model 1.0 0.5 UPS 15-35 SUC/ SFC 3 2 1 0.
UP Series 6 Technical data UP 15-42 B5/B7 H [m] 5 H [ft] a. UP15-42B5 b. UP15-42B7 60 Hz 16 b 14 0-17 gpm (0 - 3.9 m3/h) Head range: 0-15 ft (0 - 4.6 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) 12 Max. system pressure: 145 psi (10 bar) 10 Note: If the UP pump is equipped with a timer, the maximum liquid temperature is 150 °F (66 °C). a 4 3 Flow range: 8 2 Model 6 UP 15-42 B5 4 1 0 0 0 1 0.0 2 0.5 3 4 5 1.
UP Series UP 15-42 BUC5/BUC7 H [m] 5 Flow range: 0-17 gpm (0 - 3.9 m3/h) Head range: 0-15 ft (0 - 4.6 m) Motor: 2-pole, single-phase Max. liquid temperature: 205 °F (96 °C) 14 Min. liquid temperature: 36 °F (2 °C) 12 Max. system pressure: 145 psi (10 bar) Model H [ft] a. UP15-42BUC5 b. UP15-42BUC7 60 Hz 16 4 3 Technical data 6 10 UP 15-42 BUC5 UP 15-42 BUC7 8 2 Volts Amps Watts Hp Capacitor 115 115 0.74 0.74 85 85 0.114 0.
UP Series 6 Technical data UP 15 MixiMizer™ UP 15-42 BUC5/BUC7/MR H [m] 5 H [ft] c 14 0 - 13.5 gpm (0 - 3.1 m3/h) Head range: 0-15 ft (0 - 4.6 m) Motor: 2-pole, single-phase Max. liquid temperature: 205 °F (96 °C) a. MIN - both models b. UP15-42BUC5 c. UP15-42BUC7 60 Hz 16 Flow range: Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) 4 b 12 3 Model UP 15-42 BUC5/MR UP 15-42 BUC7/MR 10 Volts Amps Watts 115 115 0.74 0.74 85 85 Hp Capacitor 0.
UP Series UP 15-42 F/FR H [m] 5 H [ft] UP15-42F/FR 60 Hz 16 0-17 gpm (0 - 3.9 m3/h) Head range: 0-15 ft (0 - 4.6 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) 14 Min. liquid temperature: 36 °F (2 °C) 12 Max. system pressure: 145 psi (10 bar) 10 Closed system 4 3 Flow range: Technical data 6 8 Model 2 6 Volts Amps Watts Hp Capacitor 115 230 0.74 0.43 85 95 0.114 0.128 10 μF / 180 V 2 μF / 400 V UP 15-42 F/FR 4 1 0 0 0 0.0 2 4 0.5 1.
UP Series 6 Technical data UPS 15-42 F H [m] 5 H [ft] UPS15-42F 60 Hz 16 3 0 - 17.5 gpm (0 - 4.0 m3/h) Head range: 0 - 15.5 ft (0 - 4.7 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) 14 Min. liquid temperature: 36 °F (2 °C) 4 2 12 3 Flow range: Max. system pressure: 145 psi (10 bar) 10 Model Speed Volts Amps Watts 8 2 UPS 15-42 F 1 6 4 230 0.41 0.19 0.14 92 40 30 Hp Capacitor 0.124 0.054 0.041 2 μF / 400 V Approvals 2 0 0 0.0 2 4 0.5 1.
UP Series UP 15 MixiMizer™ UP 15-42 FC/MR H [m] 5 H [ft] a. MIN - UP15-42FC/MR b. MAX - UP15-42FC/MR 60 Hz 16 b 14 Flow range: 0-16 gpm (0 - 3.6 m3/h) Head range: 0-15 ft (0 - 4.6 m) Motor: 2-pole, single-phase Max. liquid temperature: 205 °F (96 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Technical data 6 4 12 Model 3 10 UP 15-42 FC/MR Volts Amps Watts Hp Capacitor 115 0.74 85 0.
UP Series 6 Technical data UP variable speed Flow range: 0-16 gpm (0 - 3.6 m3/h) UP 15-42 F/VS Head range: 0 - 15.5 ft (0 - 4.7 m) Motor: 2-pole, single-phase Max. liquid temperature: 205 °F (96 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) H [m] 5 H [ft] a. MIN - UP15-42F/FV b. MAX - UP15-42F/FV 60 Hz 16 b 14 4 12 Model 3 UP 15-42 F/FV 10 Volts Amps Watts Hp Capacitor 115 0.74 85 0.114 10 μF / 180 V Approvals 8 2 6 4 2 a 0 0 0 0.
UP Series UP 15-55 SUC H [m] H [ft] UP15-55SUC 60 Hz 18 5 0 - 21.5 gpm (0 - 4.9 m3/h) Head range: 0-17 ft (0 - 5.2 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) 16 14 4 12 3 Flow range: Technical data 6 Closed system 10 Model 8 2 UP 15-55 SUC 6 Volts Amps Watts Hp Capacitor 230 0.42 97 0.130 2 μF / 400 V Approvals 4 2 0 0 0 2 4 6 0.0 0.5 1.0 8 1.5 10 2.
UP Series 6 Technical data UPS 15-55 SFC/SUC/TLC H [m] H [ft] UPS15-55SFC/SUC 60 Hz 18 3 5 16 2 14 0-25 gpm (0 - 5.7 m3/h) Flow range: Head range: 0-18 ft (0 - 5.5 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) 4 Note: If the UP pump is equipped with a timer, the maximum liquid temperature is 150 °F (66 °C).
UP Series ALPHA2 Flow range: 0 - 21.5 gpm (0 - 4.9 m3/h) Head range: 0 - 19 ft (0 - 5.8 m) Motor: 4-pole, synchronous permanent magnet motor Max. liquid temperature (see table below): 230 °F (110 °C) Min. liquid temperature (see table below): 36 °F (2 °C) Max. system pressure: 150 psi (10 bar) Technical data 6 TM04 6025 0611 Closed (F, FR) and open systems (SF) Approximate power usage Min. [W] Max.
UP Series 6 Technical data ALPHA2 ALPHA2 15-55 line cord ALPHA2 15-55 terminal box F B F B C TM04 6012 4709 D TM06 8168 4816 D E E G G A A C ALPHA2 15-55 FR line cord ALPHA2 15-55 FR terminal box B B C F C E G E G A A F D TM06 8169 4816 TM04 6013 4709 D Product number 115 V Model ALPHA2 ALPHA2 ALPHA2 ALPHA2 ALPHA2 ALPHA2 15-55 15-55 15-55 15-55 15-55 15-55 F FR SF F/LC FR/LC SF/LC 99163903 99163932 99163937 99163906 99163934 99163972 Dimensions [inches (mm)] A 6.50 6.
UP Series ALPHA1 H [m] H [ft] 6 20 0 - 17 gpm (0 - 3.9 m3/h) Head range: 0 - 19 ft (0 - 5.8 m) 4-pole, synchronous permanent magnet motor Max. liquid temperature: 230 °F (110 °C) Motor: 18 5 Flow range: Technical data 6 Constant Pressure III 16 14 4 12 Constant Pressure II 8 2 6 Constant Pressure I 4 1 2 0 Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 150 psi (10 bar) 10 0 0 0.0 1 2 3 0.5 4 1.0 5 6 7 1.5 8 9 2.0 10 11 2.5 12 13 3.0 14 15 16 3.
UP Series 6 Technical data ALPHA1 ALPHA1 15-55 terminal box ALPHA1 15-55 line cord B F B F C D TM06 8961 1417 D TM06 8963 1417 E G E G A A C ALPHA1 15-55 FR line cord ALPHA1 15-55 FR terminal box B F B C F E E G G A A C D TM06 8964 1417 TM06 8962 1417 D Product number 115 V Model ALPHA1 ALPHA1 ALPHA1 ALPHA1 ALPHA1 ALPHA1 15-55 15-55 15-55 15-55 15-55 15-55 F FR SF F/LC FR/LC SF/LC 99287256 99287259 99287262 99285998 99287244 99287250 Dimensions [inches (mm)] A 6.50 6.
UP Series UPS 15-58 FC/FRC H [m] H [ft] 6 20 18 5 UPS15-58FC/FRC 60 Hz 3 2 16 14 4 Flow range: 0-17 gpm (0 - 3.9 m3/h) Head range: 0 - 19.5 ft (0 - 5.9 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Technical data 6 1 12 Model 3 Speed Volts Amps Watts 10 UPS 15-58 FC/FRC 8 2 6 115 0.75 0.66 0.55 87 80 60 Hp Capacitor 0.117 0.108 0.
UP Series 6 Technical data UP 15-100 F H [m] H [ft] UP15-100F 60 Hz 36 10 8 24 4 0 - 8.4 gpm (0 - 1.9 m3/h) Head range: 0-36 ft (0 - 11.0 m) Motor: 2-pole, single-phase Max. liquid temperature: 205 °F (96 °C) 32 28 6 Flow range: Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Closed system 20 16 Model 12 UP 15-100 F 8 Approvals Volts Amps Watts Hp Capacitor 115 1.1 135 0.181 12 μF / 170 V 4 0 0 0 0.0 1 0.2 2 0.4 3 0.6 4 0.8 5 1.0 1.
UP Series UP 26-64 F H [m] 8 Flow range: 0-32 gpm (0 - 7.3 m3/h) Head range: 0 - 24.5 ft (0 - 5.7 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) 18 Max. system pressure: 145 psi (10 bar) 16 Closed system H [ft] UP26-64F 60 Hz 26 24 7 22 6 5 20 Technical data 6 14 4 12 Model 3 10 UP 26-64 F 8 1 Watts Hp Capacitor 1.7 0.8 185 175 0.248 0.235 8 μF / 180 V 2.
UP Series 6 Technical data UP 26 variable speed UP 26-64 F/VS H [m] 8 H [ft] 0-34 gpm (0 - 7.7 m3/h) Head range: 0 - 24.5 ft (0 - 7.5 m) Motor: 2-pole, single-phase Max. liquid temperature: 195 °F (91 °C) a. MIN - UP26-64F/VS b. MAX - UP26-64F/VS 60 Hz b 24 6 Flow range: Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) 20 Model 16 UP 26-64 F/VS Volts Amps Watts Hp Capacitor 115 1.7 185 0.
UP Series UP 26-96 F/SF + >P@ + >IW@ 83 ) 6) +] 0-28 gpm (0 - 6.4 m3/h) Head range: 0-30 ft (0 - 9.1 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Closed system (F) and open system (SF) Flow range: Model UP 26-96 F/SF Volts Amps Watts Hp Capacitor 115 230 1.7 0.8 205 205 0.275 0.275 10 μF / 180 V 2.
UP Series 6 Technical data UP 26 variable speed UP 26-96 F/VS H [m] 10 H [ft] a. MIN - UP26-96F/VS b. MAX - UP26-96F/VS 60 Hz 32 b 28 Flow range: 0-28 gpm (0 - 6.4 m3/h) Head range: 0-30 ft (0 - 9.1 m) Motor: 2-pole, single-phase Max. liquid temperature: 195 °F (91 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) 8 24 6 Model UP 26-96 F/VS 20 Volts Amps Watts Hp Capacitor 115 1.7 205 0.
UP Series UP 26-99 F/SF + >P@ Flow range: 0-34 gpm (0 - 7.7 m3/h) Head range: 0-32 ft (0 - 9.8 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max. system pressure: 145 psi (10 bar) Closed system (F) and open system (SF) + >IW@ 83 ) 6) +] Model UP 26-99 F/SF Amps Watts Hp Capacitor 115 230 2.15 1.07 245 245 0.329 0.329 10 μF / 180 V 2.
UP Series 6 Technical data UPS 26-99 FC/SFC + >P@ + >IW@ 836 )& 6)& +] Flow range: 0-33 gpm (0 - 7.5 m3/h) Head range: 0-29 ft (0 - 8.8 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max.
UP Series UP 26-116 F/SF + >P@ + >IW@ 83 ) 6) +] Motor: 2-pole, single-phase 32 °F (0 °C) Max. system pressure: 145 psi (10 bar) Closed system (F) and open system (SF) Model UP 26-116 F/SF Volts Amps Watts 230 1.8 385 Hp Capacitor 0.517 2.5 μF / 400 V Approvals 0-37 ft (0 - 11.3 m) 4 >86 *30@ 4 >Pñ K@ UP 26-116 F/SF TM03 5577 4516 Head range: Min.
UP Series 6 Technical data UP 26-120 U Flow range: 0-19 gpm (0 - 4.3 m3/h) Head range: 0-38 ft (0 - 11.6 m) Motor: 2-pole, single-phase Max. liquid temperature: 203 °F (95 °C) 32 Min. liquid temperature: 32 °F (0 °C) 28 Max. system pressure: 145 psi (10 bar) 24 Closed system H [m] H [ft] 12 40 UP26-120U 60 Hz 36 10 8 6 20 Model 16 4 UP 26-120 U 12 8 Amps Watts Hp Capacitor 115 230 2.15 1.07 215 220 0.289 0.295 10 μF / 180 V 2.5 μF / 400 V Approvals 4 0 0 0.
UP Series UPS 26-150 F/SF H [m] H [ft] 14 45 2 40 12 UPS26-150F/SF 60 Hz 3 35 1 10 Flow range: 0-53 gpm (0-12 m3/h) Head range: 0-46 ft (0-14 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max.
UP Series 6 Technical data UP 43-44 F/BF H [m] H [ft] UP43-44F/BF 60 Hz 14 4.0 13 Flow range: 0-68 gpm (0 - 15.4 m3/h) Head range: 0 - 13.5 ft (0 - 4.1 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 32 °F (0 °C) Max. system pressure: 145 psi (10 bar) 12 3.5 11 3.0 10 9 2.5 2.0 Closed system (F) and open system (BF) 8 7 6 1.5 Model 5 UP 43-44 F/BF 4 0.5 Watts Hp Capacitor 2.15 1.07 215 220 0.289 0.295 10 μF / 180 V 2.
UP Series UPS 43-44 FC/BFC H [m] H [ft] UPS43-44FC/BFC 60 Hz 14 2 12 3 0-63 gpm (0 - 14.3 m3/h) Head range: 0-14 ft (0 - 4.3 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) 3 4 Flow range: Technical data 6 10 Min. liquid temperature: 32 °F (0 °C) Max.
UP Series 6 Technical data UP 43-70 F H [m] 8 H [ft] UP43-70F 60 Hz 26 24 7 22 6 0-85 gpm (0 - 19.3 m3/h) Head range: 0 - 24.5 ft (0 - 7.5 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 14 °F (-10 °C) Max. system pressure: 145 psi (10 bar) 20 18 5 Flow range: Closed system 16 14 4 12 3 Model Volts Amps Watts Hp Capacitor 115 230 3.4 1.8 400 400 0.537 0.
UP Series UP 43-75 F/BF H [m] 8 Flow range: 0-41 gpm (0 - 9.3 m3/h) Head range: 0-25 ft (0 - 7.6 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) 18 Max. system pressure: 145 psi (10 bar) 16 Open system H [ft] UP43-75F/BF 60 Hz 26 24 7 22 6 5 20 Technical data 6 14 4 12 3 Model 10 UP 43-75 F/BF 8 1 Watts Hp Capacitor 2.15 1.07 215 220 0.289 0.295 10 μF / 180 V 2.
UP Series 6 Technical data UPS 43-100 F/SF H [m] 10 H [ft] UPS43-100F/SF 32 60 Hz 3 2 28 1 8 24 6 Flow range: 0-65 gpm (0 - 14.8 m3/h) Head range: 0-31 ft (0 - 9.5 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 36 °F (2 °C) Max.
UP Series UP 43-110 F H [m] H [ft] UP43-110F 36 10 60 Hz 32 28 Flow range: 0-98 gpm (0 - 22.3 m3/h) Head range: 0-37 ft (0 - 11.3 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 14 °F (-10 °C) Max. system pressure: 145 psi (10 bar) Technical data 6 Closed system 8 24 Model 20 6 UP 43-110 F 16 4 12 Volts Amps Watts Hp Capacitor 115 230 5.1 2.7 590 590 0.792 0.
UP Series 6 Technical data UPS 50-44 F H [m] H [ft] 3 UPS50-44F 60 Hz 14 4.0 2 13 12 3.5 11 3.0 1 10 Flow range: 0-65 gpm (0 - 14.8 m3/h) Head range: 0 - 14.4 ft (0 - 4.4 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 32 °F (0 °C) Max. system pressure: 145 psi (10 bar) 9 2.5 2.0 8 Model 7 Speed Volts Amps Watts III 6 1.5 3 0.261 1.6 181 0.243 I 1.3 147 0.198 III 0.90 195 0.262 0.81 182 0.244 0.74 147 0.
UP Series UPS 50-60 F/SF H [m] H [ft] 22 UPS 50-60 F/SF 60 Hz 3 2 5 Head range: 0-21 ft (0 - 6.4 m) Motor: 2-pole, single-phase 18 Min. liquid temperature: 36 °F (10 °C) 16 Max. system pressure: 145 psi (10 bar) 14 Closed or open system 4 1 12 10 3 0-120 gpm (0 - 27.3 m3/h) Max.
UP Series 6 Technical data UP 50-75 F H [m] 8 H [ft] UP50-75F 60 Hz 26 24 7 22 6 20 18 5 Flow range: 0-41 gpm (0 - 9.3 m3/h) Head range: 0-25 ft (0 - 7.6 m) Motor: 2-pole, single-phase Max. liquid temperature: 230 °F (110 °C) Min. liquid temperature: 32 °F (0 °C) Max. system pressure: 145 psi (10 bar) Closed system 16 14 4 12 3 Model 10 8 1 Watts Hp Capacitor 115 2.15 215 0.289 10 μF / 180 V 230 1.07 220 0.295 2.
UP Series 7 Accessories 7. Accessories Digital timer For pumps with line cord only. Specifications (current model): Indoor 7-day digital timer with line cord with 3-prong plug Supply voltage: 125 VAC, 60 Hz, 15 A, 1875 W resistive 8 A, 1000 W tungsten, 500 VA electronic ballast 120 VAC, 60 Hz, 8.3 A standard ballast 1/2 HP motor load TM07 2374 3318 Contact rating: 15 A Fig.
UP Series 7 4.25 in. (108 mm) 2.95 in. (75 mm) Specifications: Type: 24-hour, 3-position On/Timer/Off 15-minute interval. • Supply voltage: 120 VAC • power consumption: 1 VA. Switch rating: SPDT • Resistive: 21 A/6 A • tungsten: 1350 W. • inductive: 1 hp @ 120 VAC; 2 hp @ 240 VAC. Wiring connections: 1/4" quick-connects. 3.77 (96) Installation TM03 4406 1311 2.85 (73) 1.6 in. (41 mm) Accessories Previous model timers (analog) Indoor, wired and mounted on the UP terminal box. Features 1.
UP Series 7 Specifications: • • • • Description: thermostatic switch type: Bi-metallic disc, snap-acting enclosure: environmentally sealed mounting: – clip-on mount for 1/2" (12.7 mm) inner diameter copper tube (5/8" (15.9 mm) outer diameter) – clip-on mount for 3/4" (19.1 mm) inner diameter copper tube (7/8" (22.2 mm) outer diameter). • contact rating: – 10 A @ 120 VAC, 60 Hz resistive – 5 A @ 240 VAC, 60 Hz resistive. Accessories Aquastat 1.082 in. dia. 2.80 (71) 0.50 in. ± 0.045 (12.7 mm ± 1.14) 2.
UP Series 7 Accessories Packaged dielectric isolating valve sets D B C TM04 9909 0311 F E Pump connection Pipe connection type and size Bronze GF 15/26 flange NPT TM05 7999 3507 A Product number Sweat 1/2" 3/4" 1" 1 1/4" 1 1/2" 1/2" 3/4" 1" 1 1/4" 1 1/2" Approx. Face to face shipping [A] weight (1 kit) 2.8 (1.3) 6.9 (3.1) 9.9 (4.5) 10.6 (4.8) 10.8 (4.9) 2.9 (1.3) 7.7 (3.3) 9.9 (4.5) 10.6 (4.8) 10.8 (4.
UP Series 7 GF 15/26/40/43 Accessories Packaged fitting sets GF 50 Pipe connection 2" NPT (51 mm) A B D C TM04 9808 0111 D Pipe connection E F GU 125 union TM04 9810 0111 A B Isolating valve GU 125 union Pipe connection Pipe connection D D A Pump connection GF 15/26 Cast iron GF 40/43 GF 50 GF 15/26 GF 40/43 Bronze GF 50 GU 125 union Isolating valves, bronze GU 125 union Pipe connection NPT Sweat Compression 3/4" 1" 1 1/4" 1 1/2" 1 1/2" 2" (4-bolt flange) 3/4" 1" 1 1/4" 1 1/2" 2" (
UP Series 7 Accessories UP-ZV zone valves Specifications Grundfos UP-ZV 24 V, 2-way motorized zone valves for hydronic heating or chilled water applications. Standard features: • In-line removable actuator for ease of installation and service • manual open/close lever • sealed end switch • silent close-off technology • high gear ratio • forged brass housing • removable service cap • high Cv rating. TM04 9803 0111 Approvals Technical data Max.
UP Series 7 Connection size 1/2" sweat 3/4" sweat 1" sweat 3/4" NPT Max. close-off ΔP Flow coefficient 3.5 7.5 7.5 3.5 Cv Cv Cv Cv (3.0 (6.5 (6.5 (3.0 Accessories UP-ZV flow characteristics Kv) Kv) Kv) Kv) 30 psi (2 bar) 20 psi (1.4 bar) 20 psi (1.4 bar) 30 psi (2 bar) SWEAT MODELS TM04 9804 0111 NPT MODELS Dimensions [inches (mm)] Connections A 1/2" sweat 1.31 (33) 3/4" sweat 1.38 (35) 1" sweat 1.69 (43) 3/4" NPT 1.81 (46) B C 2.63 (67) 0.94 (24) D E F G H I 3.44 (87) 4.
UP Series 8 Grundfos Product Center 8. Grundfos Product Center Online search and sizing tool to help you make the right choice. http://product-selection.grundfos.com "SIZING" enables you to size a pump based on entered data and selection choices. "REPLACEMENT" enables you to find a replacement product. Search results will include information on • the lowest purchase price • the lowest energy consumption • the lowest total life cycle cost. "CATALOG" gives you access to the Grundfos product catalog.
© Copyright Grundfos Holding A/S ECM: 1265481 Grundfos Kansas City 17100 West 118th Terrace Olathe, Kansas 66061 Phone: 913-227-3400 Fax: 913-227-3500 www.grundfos.us Grundfos Canada 2941 Brighton Road Oakville, Ontario L6H 6C9 Canada Phone: +1-905-829-9533 Fax: +1-905-829-9512 www.grundfos.ca Grundfos México Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto C.P. 66600 Apodaca, N.L. Mexico Phone: 011-52-81-8144 4000 Fax: 011-52-81-8144 4010 www.grundfos.