Submittal Sheet

FLOW RANGE: 0 to 8.5 U.S. GPM MIN. FLUID TEMPERATURE: 36°F (2°C)
HEAD RANGE: 0 to 33.5 Feet
MOTORS: 2 Pole, Single Phase
MAXIMUM FLUID TEMPERATURE: 205°F (96°C), Maximum design temperature.
FOR CLOSED SYSTEMS - 230°F (110°C)
Ambient Air Temp. 95°F (35°C) 130°F (55°C) 140°F (60°C) 160°F (71°C)
Maximum Water Temp. 205°F (96°C) 195°F (90°C) 185°F (85°C) 175°F (79°C)
MAXIMUM WORKING PRESSURE: 145 PSI
MINIMUM REQUIRED INLET PRESSURE:
Temperature 205°F (96°C) 190°F (88°C) 140°F (60°C)
Pressure 20 Ft. (11m) 9.0 Ft. (2.8m) 3.0 Ft. (0.9m)
8.7 psi 4.0 psi 1.3 psi
QUANTITY TAG NO. MODEL NO. GPM FEET VOLT PHASE COMMENTS
JOB or CUSTOMER:
ENGINEER:
CONTRACTOR:
SUBMITTED BY: DATE:
APPROVED BY: DATE:
ORDER NO: DATE:
SPECIFICATION REF:
Mounting Positions
Technical Data
Submittal Data
Wet-Rotor, In-Line, Single Stage, Maintenance Free,
Circulator Pumps
FOR INDOOR USE ONLY
Recommended
Optional
DO NOT
Mount Motor Shaft
in Vertical Position
SERIES UP
CLOSED SYSTEMS
UP15-100F
Dimensions, and Weights
DESCRIPTION MATERIAL
Inlet Cone, Bearing Plate, Bearing Retainers,
Rotor Can, Rotor Cladding, Shaft Retainer. 304 Stainless Steel
Stator Housing Aluminum
Shaft, Upper & Lower Radial Bearings Aluminum Oxide Ceramic
Thrust Bearing Metal Impregnated Carbon
O'Ring & Gaskets EP (Ethylene Propylene
Rubber)
Pump Housing (Volute) Cast Iron
Impeller PP (Polypropylene 30%
Glass Filled)
Terminal Box Noryl®
NOTES: All dimensions are in inches. "F*" dimension is the flange bolt centerline to centerline. Subject to change without notice.
L-UP-TL-045 Rev. 03/02
PRINTED IN USA
Materials of Construction
Electrical Data
MODEL VOLTS AMPS WATTS HP CAPACITOR
UP15-100F 115 1.1 135
1
/25 12µF/180V
Closed System Model A B C D E F* and Sizes Wt. (Lbs.)
UP15-100F 6
1
/2 5
1
/4 44
3
/16 3
1
/4 3
5
/32 Flange -(2)
1
/2 Dia. Bolt Holes 7
1
/4
Connection Type
Shipping
0
10
20
30
40
0246810
CAPACITY (U.S. GPM)
HEAD (FT.)
UP15-100F
60HZ
E
Visit our website at www.grundfos.com

Summary of content (1 pages)