Submittal Sheet

Nomenclature
B - Brass, lead free pump housing
5 - ½" Copper Pipe, Female sweat fittings
N5 - ½" NPT - Female thread fitting
U - Union connection, 1¼" NPSM with
Isolation valve & check valve.
A - Thermostat
T - 12-hour timer
LC - Line cord and plug
FOR OPEN SYSTEMS - 140°F (60°C) Is the maximum recommended fluid temperature
to avoid precipitation of calcium in water.
Ambient Air Temp. 149°F (65°C) 169°F (75°C)
Maximum Water Temp. 203°F (95°C) 176°F (80°C)
MINIMUM REQUIRED INLET PRESSURE:
Temperature 203°F (95°C) 185°F (85°C)
Pressure 9 Ft. (2.8m) 1.6 Ft. (0.5m)
4.0 psi 0.7 psi
MOTOR: A green light on the motor is on
when power is supplied to the pump.
TIMER: 12-hour AM/PM, 20 minute interval.
3 positions (ON/TIMER/OFF).
Mounting Positions
QUANTITY TAG NO. MODEL NO. GPM FEET VOLT PHASE COMMENTS
JOB or CUSTOMER:
ENGINEER:
CONTRACTOR:
SUBMITTED BY: DATE:
APPROVED BY: DATE:
ORDER NO: DATE:
SPECIFICATION REF:
Submittal Data 60 Cycle
Wet-Rotor, In-Line, Single Stage, Maintenance Free,
Circulator Pumps
FOR INDOOR USE ONLY
DO NOT
Mount in this
Position
Series UP
Comfort
Dimensions and Weights
UP 10-16B5/BN5 UP 10-16BU
Technical Data
FLOW RANGE: 0 – 3 U.S. GPM MINIMUM FLUID TEMPERATURE: 36°F (2°C)
HEAD RANGE: 0 – 5.4 Feet MAXIMUM FLUID TEMPERATURE: 203°F (95°C)
MOTORS: Single Phase, 115V MAXIMUM WORKING PRESSURE: 145 PSI
Model Type L1 L2 H1 H2 H3 H4 B1 B2 Wt. Lbs Connection
UP 10-16 B5/LC 3 1/8 1 1/2 5 1/4 33 1/3 2.9 Sweat 1/2"
UP 10-16 B5/TLC 3 1/8 3 1/2 1 1/2 8 1/16 33 1/3 3.4 Sweat 1/2"
UP 10-16 B5/ATLC 3 1/8 3 1/2 1 1/2 8 1/16 33 1/3 3.4 Sweat 1/2"
UP 10-16 BN5/LC 3 1/8 1 1/2 5 1/4 33 1/3 2.9 NPT 1/2"
UP 10-16 BN5/TLC 3 1/8 3 1/2 1 1/2 8 1/16 33 1/3 3.4 NPT 1/2"
UP 10-16 BN5/ATLC 3 1/8 3 1/2 1 1/2 8 1/16 33 1/3 3.4 NPT 1/2"
UP 10-16 BU/LC 4 1/3 1 7/8 5 1/4 33 1/3 3.4 Union - 11/4" NPSM
UP 10-16 BU/TLC 4 1/3 1 7/8 8 1/16 33 1/3 3.8 Union - 11/4" NPSM
UP 10-16 BU/ATLC 4 1/3 1 7/8 8 1/16 33 1/3 3.8 Union - 11/4" NPSM