Install Instructions
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. Symbols used in this document
- 3. General information
- 4. Mechanical installation
- 5. Electrical installation
- 6. First start-up
- 7. Settings
- 8. Control panel
- 9. Overview of settings
- 10. Pump setting
- 11. Selection of control mode
- 12. Fault finding
- 13. Technical data
- 14. Disposal
- Español (MX)
- 1. Garantía limitada
- 2. Símbolos utilizados en este documento
- 3. Información general
- 4. Instalación mecánica
- 5. Instalación eléctrica
- 6. Arranque inicial
- 7. Configuración
- 8. Panel de control
- 9. Descripción de los ajustes
- 10. Ajuste de la bomba
- 11. Selección de un modo de control
- 12. Localización de averías
- 13. Datos técnicos
- 14. Eliminación
- Français (CA)
- 1. Garantie limitée
- 2. Symboles utilisés dans cette notice
- 3. Informations générales
- 4. Installation mécanique
- 5. Installation électrique
- 6. Première mise en service
- 7. Paramétrages
- 8. Panneau de commande
- 9. Aperçu des réglages
- 10. Réglage du circulateur
- 11. Sélection du mode de régulation
- 12. Grille de dépannage
- 13. Caractéristiques techniques
- 14. Mise au rebut
19
English (US)
11. Selection of control mode
System application Select this control mode
In systems with relatively large pressure losses in the distribution pipes and in air-conditioning and
cooling systems.
• Two-pipe heating systems with thermostatic valves and
– very long distribution pipes
– strongly throttled pipe balancing valves
– differential-pressure regulators
– large pressure losses in those parts of the system through which the total quantity of water flows (for
example boiler, heat exchanger and distribution pipe up to the first branching).
• Primary circuit pumps in systems with large pressure losses in the primary circuit.
• Air-conditioning systems with
– heat exchangers (fan coils)
– cooling ceilings
– cooling surfaces.
Proportional pressure
In systems with relatively small pressure losses in the distribution pipes.
• Two-pipe heating systems with thermostatic valves and
– dimensioned for natural circulation
– small pressure losses in those parts of the system through which the total quantity of water flows (for
example boiler, heat exchanger and distribution pipe up to the first branching) or
– modified to a high differential temperature between flow pipe and return pipe (for example district
heating).
• Underfloor heating systems with thermostatic valves.
• One-pipe heating systems with thermostatic valves or pipe balancing valves.
• Primary circuit pumps in systems with small pressure losses in the primary circuit.
Constant pressure
The pump can also be set to operate according to the max. or min. curve, like an uncontrolled pump:
• The max. curve mode can be used in periods in which a maximum flow is required. This operating
mode is for instance suitable for hot-water priority.
• The min. curve mode can be used in periods in which a minimum flow is required. This operating mode
is for instance suitable for manual night setback.
Constant curve
Q
H
Q
H
Q
H