Functions
MAGNA3
8
34
Factory setting
The pumps have been factory-set to AUTO
ADAPT
without Automatic Night Setback.
Start-up guide
The start-up guide is used for the general settings of
the pump. The start-up guide is started the first time
the pump is connected to the power supply.
Note: If there has been no user action after pump
start-up, the pump will automatically leave the start-up
guide after 15 minutes with the language set to
English.
The start-up guide can be run again in the "Settings"
menu. If the start-up guide is run again, all previous
settings will be lost.
"Home" menu
This menu gives an overview of up to four user-defined
parameters or a graphical illustration of a Q/H
performance curve.
This menu offers the following (factory setting):
• Shortcut to Control mode settings
• Shortcut to Setpoint settings
• Flow rate
• Head.
Fig. 43 "Home" menu
"Status" menu
This menu shows the status of the pump and system
as well as warnings and alarms.
Note: No settings can be made in this menu.
This menu offers the following:
• Operating status
• Pump performance
• Power and energy consumption
• Warning and alarm
• Heat energy meter
• Work log
• Fitted modules
• Date and time
• Pump identification
• Multi-pump system.
Fig. 44 "Status" menu
"Settings" menu
This menu gives access to all setting parameters. A
detailed setting of the pump can be made in this menu.
This menu offers the following setting options:
• Setpoint
• Operating mode
• Control mode
•FLOW
LIMIT
• Automatic Night Setback
• Relay outputs
• Setpoint influence
• Bus communication
• General settings.
Fig. 45 "Settings" menu
Home
StatusSettings