Brochure

Table Of Contents
Functions
MAGNA3
8
38
Available CIM modules
Module Fieldbus protocol Description Functions
CIM 050
TM05 3812 1612
GENIbus
The CIM 050 is a Grundfos communication
interface module used for communication
with a GENIbus network.
The CIM 050 has terminals for the GENIbus
connection.
CIM 100
TM05 3813 1612
LonWorks
The CIM 100 is a Grundfos communication
interface module used for communication
with a LonWorks network.
The CIM 100 has terminals for the LonWorks
connection.
Two LEDs are used to indicate the actual status
of the CIM 100 communication.
One LED is used for indication of correct
connection to the pump, and the other is used to
indicate LonWorks communication status.
CIM 150
TM05 3814 1612
PROFIBUS DP
The CIM 150 is a Grundfos communication
interface module used for communication
with a PROFIBUS network.
The CIM 150 has terminals for the PROFIBUS
DP connection.
DIP switches are used to set line termination.
Two hexadecimal rotary switches are used to set
the PROFIBUS DP address.
Two LEDs are used to indicate the actual status
of the CIM 150 communication.
One LED is used for indication of correct
connection to the pump, and the other is used to
indicate PROFIBUS communication status.
CIM 200
TM05 3815 1612
Modbus RTU
The CIM 200 is a Grundfos communication
interface module used for communication
with a Modbus RTU network.
The CIM 200 has terminals for the Modbus
connection.
DIP switches are used to select parity and stop
bits, to select transmission speed and to set line
termination.
Two hexadecimal rotary switches are used to set
the Modbus address.
Two LEDs are used to indicate the actual status
of the CIM 200 communication.
One LED is used for indication of correct
connection to the pump, and the other is used to
indicate Modbus communication status.
CIM 250
TM05 4432 2212
GSM/GPRS
The CIM 250 is a Grundfos communication
interface module used for GSM/GPRS
communication.
The CIM 250 is used to communicate via a
GSM network.
The CIM 250 has a SIM-card slot and an SMA
connection to the GSM antenna.
The CIM 250 also has an internal backup battery.
Two LEDs are used to indicate the actual status
of the CIM 250 communication. One LED is used
for indication of correct connection to the pump,
and the other is used to indicate GSM/GPRS
communication status.
Note: The SIM card is not supplied with the CIM
250. The SIM card from the service provider must
support data/fax service to use call service from
PC Tool or SCADA. The SIM card from the
service provider must support GPRS service to
use Ethernet service from PC Tool or SCADA.