GRUNDFOS INSTRUCTIONS TPE Series 1000 Installation and operating instructions
English (US) English (US) Installation and operating instructions Original installation and operating instructions. 19. Megging 31 CONTENTS 20. 20.1 20.2 Technical data, single-phase motors Supply voltage Leakage current 31 31 31 21. 21.1 21.2 Technical data, three-phase motors Supply voltage Leakage current 31 31 31 22. Inputs/outputs 31 23. 23.1 23.2 Other technical data Torques Sound pressure level 32 32 32 24. Disposal 32 Page 1. Limited warranty 3 2.
Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 24 months from date of installation, but not more than 30 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repairing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture.
5.3 Ensuring motor cooling These installation and operating instructions apply to the Grundfos TPE pumps. The pumps are fitted with frequency-controlled permanent-magnet motors for single-phase or three-phase mains connection. Note In order to ensure sufficient cooling of the motor, the distance (D) between the end of the fan cover and a wall or other fixed objects must always be at least 0.16" (50 mm), irrespective of motor size. See fig. 1. 4.
6.2 Mains supply Carry out the electrical connection according to local regulations. 6.2.1 Single-phase supply voltage Check that the supply voltage and frequency correspond to the values stated on the nameplate. • 1 x 200-240 V - 10 %/+ 10 %, 60 Hz, PE. Warning Check that the supply voltage and frequency correspond to the values stated on the nameplate. Before making any connections in the terminal box, make sure that the power supply has been switched off for at least 5 minutes.
.3 Additional protection • 6.3.1 Single-phase motors 3 x 440-480 V - 10 %/+ 10 %, 60 Hz, PE. Caution Note In order to avoid loose connections, ensure that the terminal block for L1, L2 and L3 is pressed home in its socket when the supply cable has been connected.
6.4 Connection terminals The descriptions and terminal overviews in this section apply to both single-phase and three-phase motors. The advanced functional module is only available as an option. For maximum tightening torques, see section 23.1 Torques. The advanced module has these connections: The number of terminals depends on the functional module (FM). The fitted module can be identified on the motor nameplate. See fig. 8.
English (US) Terminal Type NC C1 Common NO Normally open contact NC Normally closed contact C2 Common NO Normally open contact 18 GND Ground 11 DI4/OC2 Digital input/output, configurable. Open collector: Max. 24 V resistive or inductive.
6.6.2 Replacing an existing motor • Use screened cables with a cross-sectional area of min. AWG 20 (0.5 mm2) and max. AWG 16 (1.5 mm2) for external on/off switch, digital inputs, setpoint and sensor signals. • • Connect the screens of the cables to frame at both ends with good connection. The screens must be as close as possible to the terminals. See fig. 10. If a screened 2-core cable is used in the existing installation, connect the cable as shown in fig. 12.
Caution The motor must not be installed more than 6562 ft (2000 m) above sea level. Warning The product may be so hot that only the buttons should be touched to avoid burns. Installation altitude is the height above sea level of the installation site. • Motors installed up to 3281 ft (1000 m) above sea level can be loaded 100 %.
English (US) 9. Standard control panel psi This control panel is fitted as standard on TPE pumps. 8.5 1 3 5 0 TM05 4848 3512 4 Stop Fig. 15 Setpoint set to 4.3 psi (3 m), differential-pressure control 9.1.2 Pump in constant-curve control mode In constant-curve control mode, the pump performance will lie between the max. and min. curve of the pump. See fig. 16. Fig. 14 Standard control panel Symbol Description Grundfos Eye Shows the operating status of the pump. See section 17.
10. Grundfos GO Remote • continuously to change over to the min. curve of the Press pump (bottom light field flashes). When the bottom light field is on, press for 3 seconds until the light field starts flashing. • To change back, press setpoint is indicated. continuously until the desired Example: Pump set to min. curve. Figure 18 shows that the bottom light field is flashing, indicating min. curve. The pump is designed for wireless radio or infrared communication with the Grundfos GO Remote.
English (US) 10.2 Menu overview for Grundfos GO Remote 10.2.1 Main menus Dashboard Status Resulting setpoint Actual controlled value Motor speed (rpm, %) Power consumption Energy consumption Acc.
English (US) Settings Section Page Setpoint 11.1 Setpoint 15 Operating mode 11.2 Operating mode 15 Control mode 11.4 Control mode 15 Controller 11.11 Controller settings 20 Operating range 11.12 Operating range 21 Ramps 11.15.2 Ramps 24 Pump number 11.16.1 Pump number 24 11.5 Analog inputs 18 11.6 Pt100/1000 inputs 18 11.7 Digital inputs 19 11.8 Digital inputs/outputs 19 Predefined setpoint 11.13.2 Predefined setpoints 24 Analog output 11.
11.4 Control mode 11.1 Setpoint Possible control modes: The setpoint for all control modes can be set in this submenu when the desired control mode has been selected. See section 11.4 Control mode. 11.2 Operating mode Possible operating modes: • Normal The pump runs according to the selected control mode. • Stop The pump stops. • Min. The min. curve mode can be used in periods in which a minimum flow is required. • • • Const. pressure (constant pressure) • Const. temp.
11.4.3 Constant differential pressure This control mode ensures a constant temperature. Constant temperature is a comfort control mode that can be used in domestic hot-water systems to control the flow to maintain a constant temperature in the system. See fig. 23. When this control mode is used, no balancing valves must be installed in the system. The pump maintains a constant differential pressure, independently of the flow in the system. See fig. 25.
11.4.5 Constant flow rate The pump maintains a constant differential temperature in the system and the pump performance is controlled according to this. See fig. 27. The pump maintains a constant flow in the system, independently of the head. See fig. 29. H H Q Q set Fig. 29 Constant flow rate Fig.
Available inputs depending on the functional module fitted in the pump: • One external level sensor. – emptying function. FM 300 (advanced) Function (terminal) L Analog input 1, setup (4) ● Analog input 2, setup (7) ● Analog input 3, setup (14) ● To set up an analog input, make the settings below. Function • One external level sensor. – filling function. The analog inputs can be set to these functions: L • Not active • Feedback sensor • Ext. setpoint infl. See section 11.
11.8 Digital inputs/outputs Available inputs depending on the functional module fitted in the pump: Available inputs/outputs depending on the functional module fitted in the pump: Function (terminal) FM 300 (advanced) English (US) 11.
English (US) 11.9 Relay outputs Function (terminal) 11.11 Controller settings FM 300 (advanced) The pumps have a factory default setting of gain (Kp) and integral time (Ti). Relay output 1 (NC, C1, NO) ● However, if the factory setting is not the optimum setting, the gain and the integral time can be changed: Relay output 2 (NC, C2, NO) ● • Set the gain (Kp) within the range from 0.1 to 20. • Set the integral-action time (Ti) within the range from 0.1 to 3600 s.
Ti t L2 -0.5 10 + 5L2 Set the operating range as follows: • Set the min. speed within the range from fixed min. speed to user-set max. speed. • Set the max. speed within the range from user-set min. speed to fixed max. speed. The range between the user-set min. and max. speeds is the operating range. See fig. 34. Note t t t Speeds below 25 % may result in noise from the shaft seal. 100 % (110 %) L2 L2 = Distance ft (m) between heat exchanger and sensor.
At a lower sensor value of 0 psi, a set setpoint of 29 psi and an external setpoint of 60 %, the actual setpoint is 0.60 x (29 - 0) + 0 = 17.4 psi. Actual setpoint = actual input signal x (setpoint - lower value) + lower value. [PSI] Upper value Actual setpoint Lower value – Linear with Min. In the input signal range from 20 to 100 %, the setpoint is influenced linearly. If the input signal is below 10 %, the pump will change to operating mode "Min.".
"Inverse with Stop" and "Inverse with Min." • – Inverse with Stop In the input signal range from 0 to 80 %, the setpoint is influenced inversely. If the input signal is above 90 %, the pump will change to operating mode "Stop". If the input signal is reduced below 85 %, the operating mode will be changed back to "Normal". See fig. 39. – Inverse with Min. In the input signal range from 0 to 80 %, the setpoint is influenced inversely.
11.15.2 Ramps Seven predefined setpoints can be set and activated by combining the input signals to digital inputs 2, 3 and 4 as shown in the table below. The setting of ramps is only relevant in the case of constant-curve operation.
English (US) 12. Assist 12.1 Setup of multi-pump system The multi-pump function enables the control of pumps connected in parallel pumps without the use of external controllers. The pumps in a multi-pump system communicate with each other via the wireless GENIair connection or the wired GENI connection. A multi-pump system is set up via a selected pump, i.e. the master pump (first selected pump). All Grundfos pumps with a wireless GENIair connection can be connected to the multi-pump system.
English (US) 13. Selection of control mode System application Select this control mode In systems with relatively small pressure losses in the distribution pipes.
It is possible to turn the control panel 180 °. Follow the instructions below. Note English (US) 4. Turn the plastic cover 180 °. 14. Changing the position of the control panel Do not twist the cable more than 90 °. Fig. 44 Loosening the screws TM05 5354 3612 TM05 5351 3612 1. Loosen the four screws (T25) holding the terminal box cover. Fig. 47 Turning the plastic cover 5. Re-position the plastic cover correctly on the four rubber pins (pos. C). Make sure that the locking tabs (pos.
English (US) 15. Bus signal The motor enables serial communication via an RS-485 input. The communication is carried out according to the Grundfos GENIbus protocol and enables connection to a building management system or another external control system. Via a bus signal, it is possible to remote-set motor operating parameters, such as setpoint and operating mode.
English (US) 17. Grundfos Eye The operating condition of the pump is indicated by the Grundfos Eye on the control panel. See fig. 50, pos. A. TM05 5993 4312 A Fig. 50 Grundfos Eye Grundfos Eye Indication Description No lights on. Power off. Motor not running. Two opposite green indicator lights rotating in Power on. the direction of rotation of the motor when Motor running. seen from the non-drive end. Two opposite green indicator lights permanently on. Power on. Motor not running.
English (US) 18. Signal relays The motor has two outputs for potential-free signals via two internal relays. The signal outputs can be set to "Operation", "Pump running", "Ready", "Alarm" and "Warning". The functions of the two signal relays appear from the table below: Contact position for signal relays when activated Description Grundfos Eye Operation Pump running Ready Alarm Warning Power off. Off C NO NC C NO NC C NO NC C NO NC C NO NC Normal, Min. or Max.
Caution 22. Inputs/outputs Megging of an installation incorporating MLE motors is not allowed, as the built-in electronics may be damaged. Ground reference (GND) All voltages refer to GND. All currents return to GND. Absolute maximum voltage and current limits 20. Technical data, single-phase motors Exceeding the following electrical limits may result in severely reduced operating reliability and motor life: 20.1 Supply voltage • Relay 1: 1 x 200-240 V - 10 %/+ 10 %, 60 Hz, PE.
English (US) Analog output (AO) 23. Other technical data Current sourcing capability only. EMC (electromagnetic compatibility) Voltage signal: EN 61800-3. • Range: 0-10 VDC. • Minimum load between AO and GND: 1 kΩ. • Short-circuit protection: Yes. Residential areas, unlimited distribution, corresponding to CISPR 11, class B, group 1. Current signal: Industrial areas, unlimited distribution, corresponding to CISPR 11, class A, group 1. • Ranges: 0-20 and 4-20 mADC.
1. Installation in the USA and Canada Note Appendix Appendix Location of identification numbers In order to maintain the cURus approval, follow these additional installation instructions. The UL approval is according to UL 1004-1. Stop For USA This product complies with the Canadian Electrical Code and the US National Electrical Code. This product has been tested according to the national standards for Electronically Protected Motors: TM05 7572 1213 1.1 Electrical codes Identification numbers Fig.
17100 West 118th Terrace Olathe, Kansas 66061 Phone: (913) 227-3400 Fax: (913) 227-3500 www.grundfos.us GRUNDFOS Canada GRUNDFOS México 2941 Brighton Road Oakville, Ontario L6H 6C9 Canada Phone: +1-905 829 9533 Telefax: +1-905 829 9512 Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto C.P. 66600 Apodaca, N.L. México Phone: 011-52-81-8144 4000 Fax: 011-52-81-8144 4010 www.grundfos.ca www.grundfos.
ECM: 1135163 www.grundfos.com www.grundfos.us The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide.