Install Instructions
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. Symbols used in this document
- 3. Abbreviations and definitions
- 4. General information
- 5. Mechanical installation
- 6. Electrical installation
- 7. Operating conditions
- 8. User interfaces
- 9. Standard control panel
- 10. Grundfos GO Remote
- 11. Description of selected functions
- 11.1 Setpoint
- 11.2 Operating mode
- 11.3 Set manual speed
- 11.4 Control mode
- 11.5 Analog inputs
- 11.6 Pt100/1000 inputs
- 11.7 Digital inputs
- 11.8 Digital inputs/outputs
- 11.9 Relay outputs
- 11.10 Analog output
- 11.11 Controller settings
- 11.12 Operating range
- 11.13 Setpoint influence
- 11.14 Monitoring functions
- 11.15 Special functions
- 11.16 Communication
- 11.17 General settings
- 12. Assist
- 13. Selection of control mode
- 14. Changing the position of the control panel
- 15. Bus signal
- 16. Priority of settings
- 17. Grundfos Eye
- 18. Signal relays
- 19. Megging
- 20. Technical data, single-phase motors
- 21. Technical data, three-phase motors
- 22. Inputs/outputs
- 23. Other technical data
- 24. Disposal
- Appendix
11
English (US)
9. Standard control panel
This control panel is fitted as standard on TPE pumps.
Fig. 14 Standard control panel
9.1 Setpoint setting
Set the desired setpoint of the pump by pressing or .
The light fields on the control panel will indicate the setpoint set.
9.1.1 Pump in differential-pressure control mode
The following example applies to a pump in an application where
a pressure sensor gives a feedback to the pump. If the sensor is
retrofitted to the pump, it must be set up manually as the pump
does not automatically register a connected sensor.
Figure 15 shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 4.3 psi (3 m) with a sensor
measuring range from 0 to 8.5 psi (0 to 6 m) The setting range is
equal to the sensor measuring range.
Fig. 15 Setpoint set to 4.3 psi (3 m), differential-pressure
control
9.1.2 Pump in constant-curve control mode
In constant-curve control mode, the pump performance will lie
between the max. and min. curve of the pump. See fig. 16.
Fig. 16 Pump in constant-curve control mode
Setting to max. curve:
•Press
continuously to change over to the max. curve of
the pump (top light field flashes). When the top light field is on,
press
for 3 seconds until the light field starts flashing.
• To change back, press
continuously until the desired
setpoint is indicated.
Example: Pump set to max. curve.
Figure 17 shows that the top light field is flashing, indicating max.
curve.
Fig. 17 Max. curve duty
TM05 4848 3512
Pos. Symbol Description
1
Grundfos Eye
Shows the operating status of the pump.
See section 17. Grundfos Eye for further
information.
2 - Light fields for indication of setpoint.
3 Changes the setpoint.
4
Enables radio communication with the
Grundfos GO Remote and other products of
the same type.
5
Makes the pump ready for operation/starts
and stops the pump.
Start:
If the button is pressed when the pump is
stopped, the pump will only start if no other
functions with higher priority have been
enabled. See section 16. Priority of
settings.
Stop:
If the button is pressed when the pump is
running, the pump will always be stopped.
When the pump is stopped via this button,
the "Stop" text next to the button will
illuminate.
1
2
3
4
5
Stop
TM06 0910 1214TM05 4895 2812TM05 4896 2812
0
8.5
4.3
psi
H
Q
H