Install Instructions
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. Symbols used in this document
- 3. Abbreviations and definitions
- 4. General information
- 5. Mechanical installation
- 6. Electrical installation
- 7. Operating conditions
- 8. User interfaces
- 9. Standard control panel
- 10. Grundfos GO Remote
- 11. Description of selected functions
- 11.1 Setpoint
- 11.2 Operating mode
- 11.3 Set manual speed
- 11.4 Control mode
- 11.5 Analog inputs
- 11.6 Pt100/1000 inputs
- 11.7 Digital inputs
- 11.8 Digital inputs/outputs
- 11.9 Relay outputs
- 11.10 Analog output
- 11.11 Controller settings
- 11.12 Operating range
- 11.13 Setpoint influence
- 11.14 Monitoring functions
- 11.15 Special functions
- 11.16 Communication
- 11.17 General settings
- 12. Assist
- 13. Selection of control mode
- 14. Changing the position of the control panel
- 15. Bus signal
- 16. Priority of settings
- 17. Grundfos Eye
- 18. Signal relays
- 19. Megging
- 20. Technical data, single-phase motors
- 21. Technical data, three-phase motors
- 22. Inputs/outputs
- 23. Other technical data
- 24. Disposal
- Appendix
English (US)
16
11.4.2 Constant temperature
This control mode ensures a constant temperature.
Constant temperature is a comfort control mode that can be used
in domestic hot-water systems to control the flow to maintain a
constant temperature in the system. See fig. 23. When this
control mode is used, no balancing valves must be installed in the
system.
Fig. 23 Constant temperature
This control mode requires an external temperature sensor as
shown in the examples below:
Fig. 24 Constant temperature
11.4.3 Constant differential pressure
The pump maintains a constant differential pressure,
independently of the flow in the system. See fig. 25. This control
mode is primarily suitable for systems with relatively small
pressure losses.
Fig. 25 Constant differential pressure
This control mode requires either an external differential-pressure
sensor or two external pressure sensors as shown in the
examples below:
Fig. 26 Constant differential pressure
TM05 7900 1613
Examples
• One external temperature sensor.
H
Q
t
t
t
TM05 7901 1613
Examples
• One external differential-pressure sensor.
• Two external pressure sensors.
H
Q
p
p
p
p
p
p
p
p