Install Instructions
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. Symbols used in this document
- 3. Abbreviations and definitions
- 4. General information
- 5. Mechanical installation
- 6. Electrical installation
- 7. Operating conditions
- 8. User interfaces
- 9. Standard control panel
- 10. Grundfos GO Remote
- 11. Description of selected functions
- 11.1 Setpoint
- 11.2 Operating mode
- 11.3 Set manual speed
- 11.4 Control mode
- 11.5 Analog inputs
- 11.6 Pt100/1000 inputs
- 11.7 Digital inputs
- 11.8 Digital inputs/outputs
- 11.9 Relay outputs
- 11.10 Analog output
- 11.11 Controller settings
- 11.12 Operating range
- 11.13 Setpoint influence
- 11.14 Monitoring functions
- 11.15 Special functions
- 11.16 Communication
- 11.17 General settings
- 12. Assist
- 13. Selection of control mode
- 14. Changing the position of the control panel
- 15. Bus signal
- 16. Priority of settings
- 17. Grundfos Eye
- 18. Signal relays
- 19. Megging
- 20. Technical data, single-phase motors
- 21. Technical data, three-phase motors
- 22. Inputs/outputs
- 23. Other technical data
- 24. Disposal
- Appendix
17
English (US)
11.4.4 Constant differential temperature
The pump maintains a constant differential temperature in the
system and the pump performance is controlled according to this.
See fig. 27.
Fig. 27 Constant differential temperature
This control mode requires either two external temperature
sensors or one external differential-temperature sensor as shown
in the examples below:
Fig. 28 Constant differential temperature
11.4.5 Constant flow rate
The pump maintains a constant flow in the system, independently
of the head. See fig. 29.
Fig. 29 Constant flow rate
This control mode requires an external flow sensor as shown in
the example below:
Fig. 30 Constant flow rate
11.4.6 Constant level
The pump maintains a constant level, independently of the flow
rate. See fig. 31.
Fig. 31 Constant level
This control mode requires an external level sensor.
The pump can control the level in a tank in two ways:
• as an emptying function where the pump draws the liquid from
the tank.
• as a filling function where the pump pumps the liquid into the
tank.
See fig. 32.
The type of level control function depends on the setting of the
built-in controller. See section 11.11
Controller settings
.
TM05 7954 1713
Examples
• Two external temperature sensors.
• One external differential-temperature sensor.
H
Q
△t
t
t
t
t
TM05 7955 1713
Example
• One external flow sensor.
TM05 7941 1613
H
Q
Q
set
Q
H
Q