Install Instructions
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. Symbols used in this document
- 3. Abbreviations and definitions
- 4. General information
- 5. Mechanical installation
- 6. Electrical installation
- 7. Operating conditions
- 8. User interfaces
- 9. Standard control panel
- 10. Grundfos GO Remote
- 11. Description of selected functions
- 11.1 Setpoint
- 11.2 Operating mode
- 11.3 Set manual speed
- 11.4 Control mode
- 11.5 Analog inputs
- 11.6 Pt100/1000 inputs
- 11.7 Digital inputs
- 11.8 Digital inputs/outputs
- 11.9 Relay outputs
- 11.10 Analog output
- 11.11 Controller settings
- 11.12 Operating range
- 11.13 Setpoint influence
- 11.14 Monitoring functions
- 11.15 Special functions
- 11.16 Communication
- 11.17 General settings
- 12. Assist
- 13. Selection of control mode
- 14. Changing the position of the control panel
- 15. Bus signal
- 16. Priority of settings
- 17. Grundfos Eye
- 18. Signal relays
- 19. Megging
- 20. Technical data, single-phase motors
- 21. Technical data, three-phase motors
- 22. Inputs/outputs
- 23. Other technical data
- 24. Disposal
- Appendix
19
English (US)
11.7 Digital inputs
Available inputs depending on the functional module fitted in the
pump:
To set up a digital input, make the settings below.
Function
Select one of these functions:
• Not active
When set to "Not active", the input has no function.
• External stop
When the input is deactivated (open circuit), the pump will
stop.
• Min. (min. speed)
When the input is activated, the pump will run at the set min.
speed.
• Max. (max. speed)
When the input is activated, the pump will run at the set max.
speed.
• External fault
When the input is activated, a timer will be started. If the input
is activated for more than 5 seconds, the pump will be stopped
and a fault will be indicated.
• Alarm resetting
When the input is activated, a possible fault indication will be
reset.
• Dry running
When this function has been selected, lack of inlet pressure or
water shortage can be detected.
When lack of inlet pressure or water shortage (dry running) is
detected, the pump will be stopped. The pump cannot restart
as long as the input is activated.
This requires the use of an accessory, such as these:
– a pressure switch installed on the suction side of the pump
– a float switch installed on the suction side of the pump.
• Accumulated flow
When this function has been selected, the accumulated flow
can be registered. This requires the use of a flowmeter which
can give a feedback signal as a pulse per defined flow of
water.
See section 11.15.1
Pulse flowmeter setup
.
• Predefined setpoint digit 1 (applies only to digital input 2).
When digital inputs are set to predefined setpoint, the pump
will operate according to a setpoint based on the combination
of the activated digital inputs.
See section 11.13.2
Predefined setpoints
.
The priority of the selected functions in relation to each other
appears from section 16. Priority of settings. A stop command will
always have the highest priority.
11.8 Digital inputs/outputs
Available inputs/outputs depending on the functional module
fitted in the pump:
To set up a digital input/output, make the settings below.
Mode
The digital input/output 3 and 4 can be set to act as digital input
or digital output:
• Digital input
• Digital output.
Function
The digital input/output 3 and 4 can be set to these functions:
Possible functions, digital input/output 3
Possible functions, digital input/output 4
Function (terminal)
FM 300
(advanced)
Digital input 1, setup (2 and 6) ●
Digital input 2, setup (1 and 9) ●
Function (terminal)
FM 300
(advanced)
Digital input/output 3, setup (10 and 16) ●
Digital input/output 4, setup (11 and 18) ●
Function if input Function if output
• Not active
• External stop
• Min.
• Max.
• External fault
• Alarm resetting
• Dry running
• Accumulated flow
• Predefined setpoint digit 2
• Not active
• Ready
• Alarm
• Operation
• Pump running
• Warning
• Limit 1 exceeded
• Limit 2 exceeded
Function if input Function if output
• Not active
• External stop
• Min.
• Max.
• External fault
• Alarm resetting
• Dry running
• Accumulated flow
• Predefined setpoint digit 3
• Not active
• Ready
• Alarm
• Operation
• Pump running
• Warning
• Limit 1 exceeded
• Limit 2 exceeded