Example
See fig. 35.
At a lower sensor value of 0 psi, a set setpoint of 29 psi and an
external setpoint of 60 %, the actual setpoint is 0.60 x (29 - 0) + 0
= 17.4 psi.
Actual setpoint = actual input signal x (setpoint - lower value) +
lower value.
Fig. 35 Example of setpoint influence
Types of setpoint influence
Not active
Linear function
Linear with Stop
Linear with Min.
Inverse function
Inverse with Stop
Inverse with Min.
Influence table
Influence table with Stop at Min.
Influence table with Stop at Max.
These functions can be selected:
Not active
When set to "Not active", the setpoint will not be influenced
from any external function.
Linear function
The setpoint is influenced linearly from 0 to 100 %. See fig. 36.
Fig. 36 Linear function
•"Linear with Stop" and "Linear with Min."
Linear with Stop
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig. 37.
Linear with Min.
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Min.".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig. 37.
Fig. 37 "Linear with Stop" and "Linear with Min."
Inverse function
The setpoint is influenced inversely from 0 to 100 %.
See fig. 38.
Fig. 38 Inverse function
TM06 0854 1014
TM05 6280 4612
100
0
0 100
0
17.4
29
[PSI]
Setpoint influence [%]
External
setpoint
signal [%]
Actual
input
signal
Actual setpoint
Setpoint
Upper value
Lower value
100
0
100
20 40 60 80
Setpoint influence [%]
External input
[%]
TM05 6281 4612TM05 6283 4612
100
0
100
20 40 60 80
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop
100
0
100
20 40 60 80
Setpoint influence [%]
External input
[%]