•"Inverse with Stop" and "Inverse with Min."
Inverse with Stop
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Stop".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal".
See fig. 39.
Inverse with Min.
In the input signal range from 0 to 80 %, the setpoint is
influenced inversely.
If the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating
mode will be changed back to "Normal".
See fig. 39.
Fig. 39 "Inverse with Stop" and "Inverse with Min."
Influence table
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
Fig. 40 Influence table
Influence table with Stop at Min.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
If the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal".
See fig. 41.
Fig. 41 Influence table with Stop at Min.
Influence table with Stop at Max.
The setpoint is influenced by a curve made out of two to eight
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
If the input signal is above 90 %, the pump will change to
operating mode "Min.".
If the input signal is reduced below 85 %, the operating mode
will be changed back to "Normal".
See fig. 42.
Fig. 42 Influence table with Stop at Max.
TM05 6283 4612TM05 6284 4612
100
0
100
20 40 60 80
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop
100
0
100
20 40 60 80
Setpoint influence [%]
External
input [%]
TM05 6285 4612TM05 6286 4612
100
0
100
20 40 60 80
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop
100
0
100
20 40 60 80
Setpoint influence [%]
External
input [%]
Normal
Min. or
Stop