Install Instructions
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. Symbols used in this document
- 3. Abbreviations and definitions
- 4. General information
- 5. Mechanical installation
- 6. Electrical installation
- 7. Operating conditions
- 8. User interfaces
- 9. Standard control panel
- 10. Grundfos GO Remote
- 11. Description of selected functions
- 11.1 Setpoint
- 11.2 Operating mode
- 11.3 Set manual speed
- 11.4 Control mode
- 11.5 Analog inputs
- 11.6 Pt100/1000 inputs
- 11.7 Digital inputs
- 11.8 Digital inputs/outputs
- 11.9 Relay outputs
- 11.10 Analog output
- 11.11 Controller settings
- 11.12 Operating range
- 11.13 Setpoint influence
- 11.14 Monitoring functions
- 11.15 Special functions
- 11.16 Communication
- 11.17 General settings
- 12. Assist
- 13. Selection of control mode
- 14. Changing the position of the control panel
- 15. Bus signal
- 16. Priority of settings
- 17. Grundfos Eye
- 18. Signal relays
- 19. Megging
- 20. Technical data, single-phase motors
- 21. Technical data, three-phase motors
- 22. Inputs/outputs
- 23. Other technical data
- 24. Disposal
- Appendix
English (US)
26
13. Selection of control mode
System application Select this control mode
In systems with relatively small pressure losses in the distribution pipes.
• Two-pipe heating systems with thermostatic valves
– dimensioned for natural circulation
– with small pressure losses in those parts of the system through which the total quantity of
water flows (for example boiler, heat exchanger and distribution pipe up to the first
branching)
or
– modified to a high differential temperature between flow pipe and return pipe (for example
district heating).
• Underfloor heating systems with thermostatic valves.
• One-pipe heating systems with thermostatic valves or pipe balancing valves.
• Primary circuit pumps in systems with small pressure losses in the primary circuit.
Constant differential pressure
In systems with a fixed system characteristic.
Examples:
• one-pipe heating systems
• boiler shunts
• systems with three-way valves
• domestic hot-water circulation.
Constant temperature and constant
differential temperature
If an external controller is installed, the pump is able to change from one constant curve to
another, depending on the value of the external signal.
The pump can also be set to operate according to the max. or min. curve, like an uncontrolled
pump:
• The max. curve mode can be used in periods in which a maximum flow is required.
This operating mode is for instance suitable for systems with hot-water priority.
• The min. curve mode can be used in periods in which a minimum flow is required.
Constant curve
In systems requiring a constant flow, independently of pressure drop.
Examples:
• chillers for air-conditioning
• heating surfaces
• cooling surfaces.
Constant flow rate
In systems requiring a constant tank level, independently of the flow rate.
Examples:
• process water tanks
• boiler condensate tanks.
Constant level
In systems with pumps operating in parallel.
The multi-pump function enables the control of pumps connected in parallel (two to four
pumps) without the use of external controllers. The pumps in a multi-pump system
communicate with each other via the wireless GENIair connection or the wired GENI
connection.
"Assist" menu
"Setup of multi-pump system"
H
Q
H
Q
H
Q
Q
set
H
Q
H
Q