Install Instructions
Table Of Contents
- English (US)
- 1. Limited warranty
- 2. Symbols used in this document
- 3. Abbreviations and definitions
- 4. General information
- 5. Mechanical installation
- 6. Electrical installation
- 7. Operating conditions
- 8. User interfaces
- 9. Standard control panel
- 10. Grundfos GO Remote
- 11. Description of selected functions
- 11.1 Setpoint
- 11.2 Operating mode
- 11.3 Set manual speed
- 11.4 Control mode
- 11.5 Analog inputs
- 11.6 Pt100/1000 inputs
- 11.7 Digital inputs
- 11.8 Digital inputs/outputs
- 11.9 Relay outputs
- 11.10 Analog output
- 11.11 Controller settings
- 11.12 Operating range
- 11.13 Setpoint influence
- 11.14 Monitoring functions
- 11.15 Special functions
- 11.16 Communication
- 11.17 General settings
- 12. Assist
- 13. Selection of control mode
- 14. Changing the position of the control panel
- 15. Bus signal
- 16. Priority of settings
- 17. Grundfos Eye
- 18. Signal relays
- 19. Megging
- 20. Technical data, single-phase motors
- 21. Technical data, three-phase motors
- 22. Inputs/outputs
- 23. Other technical data
- 24. Disposal
- Appendix
English (US)
32
Analog output (AO)
Current sourcing capability only.
Voltage signal:
• Range: 0-10 VDC.
• Minimum load between AO and GND: 1 kΩ.
• Short-circuit protection: Yes.
Current signal:
• Ranges: 0-20 and 4-20 mADC.
• Maximum load between AO and GND: 500 Ω.
• Open-circuit protection: Yes.
Tolerance: - 0/+ 4 % of full scale (max-point coverage).
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m)
Pt100/1000 inputs (PT)
Temperature range:
• Minimum -22 °F (-30 °C) (88 Ω/882 Ω).
• Maximum 356 °F (+180 °C) (168 Ω/1685 Ω).
Measurement tolerance: ± 2.7 °F (1.5 °C).
Measurement resolution: < 0.54 °F (0.3 °C).
Automatic range detection (Pt100 or Pt1000): Yes.
Sensor fault alarm: Yes.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Use Pt100 for short wires.
Use Pt1000 for long wires.
LiqTec sensor inputs*
Use Grundfos LiqTec sensor only.
Screened cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Power supplies (+5 V, +24 V)
+5 V:
• Output voltage: 5 VDC - 5 %/+ 5 %.
• Maximum current: 50 mADC (sourcing only).
• Overload protection: Yes.
+24 V:
• Output voltage: 24 VDC - 5 %/+ 5 %.
• Maximum current: 60 mADC (sourcing only).
• Overload protection: Yes.
Digital outputs (relays)
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
Screened cable: 20-12 AWG (0.5 - 2.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
Bus input
Grundfos GENIbus protocol, RS-485.
Screened 3-core cable: 20-16 AWG (0.5 - 1.5 mm
2
).
Maximum cable length: 1640 ft (500 m).
23. Other technical data
EMC (electromagnetic compatibility)
EN 61800-3.
Residential areas, unlimited distribution, corresponding to
CISPR 11, class B, group 1.
Industrial areas, unlimited distribution, corresponding to
CISPR 11, class A, group 1.
Contact Grundfos for further information.
Enclosure class
Standard: IP55 (IEC 34-5).
Optional: IP66 (IEC 34-5).
Insulation class
F (IEC 85).
23.1 Torques
23.2 Sound pressure level
The grey fields indicate that the motor is not yet available in this
MLE motor range, but is available in the previous MLE motor
range.
24. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
The waste battery should be disposed of through the national
collective schemes. If in doubt, contact your local Grundfos
company.
Subject to alterations.
Terminal Thread size
Max. torque
[lbf-ft (Nm)]
L1, L2, L3, L, N M4 1.3 (1.8)
NC, C1, C2, NO M2.5 0.4 (0.5)
1 to 26 and A, Y, B M2 0.4 (0.5)
Motor
[hp (kW)]
Max. speed
stated on
nameplate
[rpm]
Speed
[rpm]
Sound pressure level
ISO 3743
[dB(A)]
1-phase
motors
3-phase
motors
0.25 to 1.00
(0.12 to 0.75)
2000
1500 38 38
2000 42 42
4000
3000 53 53
4000 58 58
1.50
(1.10)
2000
1500
38
2000
42
4000
3000 53 53
4000 58 58
2.00
(1.50)
4000
3000 57 57
4000 64 64
3.00
(2.20)
4000
3000
57
4000
64