performance of electronic equipment.Electromagnetic interference not only
affects the normal operation of electronic equipment, but even causes damage to
certain components in electronic equipment. With the increase in automation, the
arrangement of electrical and electronic equipment becomes more complicated,
and the risk of interaction between devices is increased.Electromagnetic
interference mainly consists of three parts: interference source, coupling path
and interference receiver. When applying the implementation plan in the field, it
is necessary to identify the most frequent sources of interference and the possible
coupling paths that exist, so as to take corresponding measures to reduce the risk
of electromagnetic interference and ensure the normal operation of the
equipment.
In order to ensure electromagnetic compatibility enough, the following rules
must be observed:
1The device is shielded by the outer casing. The reader-related equipment
is installed in the cabinet and grounded through the rack to shield the external
magnetic field.
2The equipment is well grounded.Good grounding can ensure the clean
power supply of the equipment, and on the other hand, it can prevent the
excessive impact voltage from being damaged when the equipment fails, and
damage the reader.
3Cable shielding. For sites with complex electromagnetic environments,
shielded communication cables must be used to avoid interference signals being
coupled to the cables.
4Signal and line filtering. Install the filter in the power inlet or cabinet
inlet direction to avoid interference from the power source into the device.
3.5.2 Power supply and wiring requirements
In an industrial environment, a major source of interference in equipment circuits is
caused by unreasonable ground lines. Therefore, proper grounding is an important
method to suppress noise and prevent interference, and is the key to ensure the normal
operation and read/write success rate of the reader.
Under normal circumstances, the reader device power supply voltage is 24V, which is
a weak current. When wiring, connect the power supply line of the reader and the 485
power supply line from the weak current slot, and the cable slot must be connected to
the standard earth“0”Level.
Note: If the grounding of the slot and shield is not guaranteed to be
the standard "0" potential, you need to provide independent power
for the RFID or add a filter to the power supply.