User's Manual

www.mcohome.com User Manual
MCOHome Technology Co., Ltd
4
Temperature Unit Setting
In normal display, press and then will flash, then hold can switch between celsius
and fahrenheit.
Note: In fahrenheit unit mode, will not be shown on the display.
Temp. Sensor Error
If temperature sensor does not work, “E1” displays, fan stops and valve closes automatically.
Parameter Setting
Under the shutdown state, press & hold M to enter parameter setting menu. The password is 5138 and
press M to enter.
No. Function Range Default
Remark
P-01
Screen
Brightness
0-1 0
0: Dim without key touch
1: Always on
P-02
Fan work mode
0-1 0
0: fan and valve will be shutdown if room temp.
reaches setting temp.;
1: only valve will be shutdown if room temp. reaches
setting temp. The fan will continuously work in low
speed.
P-03
Reserve
P-04
Temp. Unit 0-1 0 0: Celsius 1: Fahrenheit
P-05
Beep 0-2 1 0 : Mute 1: Low 2: High
P-06
Power Failure
Memory
0-2 0
When power on again:
0:device will be in shutdown state (OFF);
1: device will be in working interface;
2: device will stay the status before power failure.
P-07
Temp.
Calibration
-5.0 ~
+5.0
0
P-08
Temp. upper
limit
5-99.5
35
Upper limit always > lower limit
P-09
Temp. lower
limit
5-99.5
5
P-10
Factory restore
53 Write 55
Z-Wave Operation
Including & Excluding of Z-Wave network
Under the shutdown state, press & hold to enter interface for inclusion or exclusion of
Z-Wave network. Before device included into network, “- - -” will display on the screen. Then
press once, device will enter learning mode to get a node ID. If inclusion is success, a node
ID will display on the screen in a few seconds.
A node ID can always inform us whether the device is in the network or not.
Note: Follow the same steps to exclude the device from the network.