After inclusion, turn off the device and then turn it on. Now the device is ready to be operated by
controller/ gateway in Z-Wave network.
Association Group
Thermostat supports 1 association group. A gateway is suggested to associate with this
group. Then if any changes happen, such as: temperature, working mode, fan state etc., the
thermostat will report to this associated device (gateway). When the detected temperature change
≥0.5℃, device will send unsolicited report to the gateway.
Command Class supported by the device:
COMMAND_CLASS_BASIC;
COMMAND_CLASS_THERMOSTAT_SETPOINT;
COMMAND_CLASS_THERMOSTAT_MODE;
COMMAND_CLASS_THERMOSTAT_FAN_MODE;
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE;
COMMAND_CLASS_SENSOR_MULTILEVEL;
COMMAND_CLASS_ASSOCIATION;
COMMAND_CLASS_VERSION;
COMMAND_CLASS_MANUFACTURER_SPECIFIC
Z-Wave Parameters Setting:
Add
Function Byte
Options Default
Remark
1
Upload temperature
format automatically
1
0x00Celsius
0x01Fahrenheit 0x02Follow
the main display
0x02
2
Upload temperature
automatically
1
0x00 OFF
0x01 Upload the difference
value only
0x02 Timing upload mode only
0x03 Upload the
difference+timing upload mode
0x03
3
Upload temperature
difference
2
Base on 0.1℃unit, 0x0005 by
default, 5*0.1℃=0.5℃,
0x0003~0x03E8
0x0005
0.5℃