Installation Instructions
PX/QX/RX Version 4.30 Installation Manual – Issue C
- 24 -
3A Smart Concentrator
The 3A Smart concentrator can be used with a single battery or 2 batteries. If 2 batteries are used they
should be of the same type and capacity. If a single battery is used it should be connected to the Batt
1 terminals. The case can accommodate 7Ah or 18Ah batteries. Deep discharge protection is
provided for each battery.
8K2
8K2
Alarm
Tamper
8K2
8K2
Alarm
Tamper
Case Tamper
FS3 (2.5A)
Batt 1
ISP
Cct7 Cct 8
Cct 1
Cct 2
Cct 3
Cct 4
Cct 5
Cct 6
-
+
A
B
Battery 1
(7 or 18 Ah)
ac
~
~
If an input is not used the circuit can be
switched off. There is no requirement to
terminate the input with the EOL resistors.
Each input can be mapped to any circuit
number. By default, inputs 1-10 are mapped to
circuits 1-10.
Link 5
Fuse Rating Function
Mains block F630mA 230v supply
FS1 F1.6A Aux. 1 DC output (monitored)
FS2 F1.6A Aux. 2 DC output (monitored)
FS3 F2.5A Battery 1
FS4 F2.5A Battery 2
FS5 F800mA XiB out
FS6 F2.5A Overvoltage protection
Link 2
(Tamper
Disable)
OTW
Tamper
Link 1
6
1
ONOFF
ADDRESS
+
-
+
-
FS1(1.6A)
FS2(1.6A)
Outputs 1-4
current limited to
250 mA
-
+
A
B
XiB Bus
Max 1700 m
FS4 (2.5A)
Batt 2
+
-
+
-
Battery 2
(7 or 18 Ah)
Tamper
XiB bus in (from
control panel)
XiB bus out
(isolated)
Address DIL Switch
6 5 4 3 2 1
1 0 0 0 0 0 0
2 0 0 0 0 0 1
3 0 0 0 0 1 0
4 0 0 0 0 1 1
5 0 0 0 1 0 0
6 0 0 0 1 0 1
7 0 0 0 1 1 0
8 0 0 0 1 1 1
9 0 0 1 0 0 0
10 0 0 1 0 0 1
11 0 0 1 0 1 0
12 0 0 1 0 1 1
13 0 0 1 1 0 0
14 0 0 1 1 0 1
15 0 0 1 1 1 0
16 0 0 1 1 1 1
17 0 1 0 0 0 0
18 0 1 0 0 0 1
19 0 1 0 0 1 0
20 0 1 0 0 1 1
21 0 1 0 1 0 0
22 0 1 0 1 0 1
23 0 1 0 1 1 0
24 0 1 0 1 1 1
25 0 1 1 0 0 0
26 0 1 1 0 0 1
27 0 1 1 0 1 0
28 0 1 1 0 1 1
29 0 1 1 1 0 0
30 0 1 1 1 0 1
31 0 1 1 1 1 0
32 0 1 1 1 1 1
33 1 0 0 0 0 0
34 1 0 0 0 0 1
35 1 0 0 0 1 0
36 1 0 0 0 1 1
37 1 0 0 1 0 0
38 1 0 0 1 0 1
39 1 0 0 1 1 0
40 1 0 0 1 1 1
41 1 0 1 0 0 0
42 1 0 1 0 0 1
43 1 0 1 0 1 0
44 1 0 1 0 1 1
45 1 0 1 1 0 0
46 1 0 1 1 0 1
47 1 0 1 1 1 0
48 1 0 1 1 1 1
49 1 1 0 0 0 0
50 1 1 0 0 0 1
51 1 1 0 0 1 0
52 1 1 0 0 1 1
53 1 1 0 1 0 0
54 1 1 0 1 0 1
55 1 1 0 1 1 0
56 1 1 0 1 1 1
57 1 1 1 0 0 0
58 1 1 1 0 0 1
59 1 1 1 0 1 0
60 1 1 1 0 1 1
61 1 1 1 1 0 0
62 1 1 1 1 0 1
63 1 1 1 1 1 0
64 1 1 1 1 1 1
OP4
OP3
OP2
OP1
FS5 (800mA)
Link 4
Link 3
FSx(2.5A)
Over Voltage
LK1 Connect 0v to earth
LK2 Tamper disable
LK3 Batttery 1 deep discharge relay bypass
LK4 Batttery 2 deep discharge relay bypass
LK5 fiited 2A aux current/1A battery charge current
LK5 not fitted 1.5A aux current/1.5A battery charge current
LK8 External tamper disable
LK9 Case tamper disable
Link 8
(Ext.
Tamper
Disable)
Charge voltage
13.7v+/-2%, temp.
compensated
14v +/-5%,
2A/1.5A max.
(Refer to LK5)
-
+
+
-
Link 9
(Case
Tamper
Disable)