Installation Instructions

PX/QX/RX Version 4.30 Installation Manual – Issue C
- 7 -
Once the keypad is replying then enter the default engineer PIN code, 9999, remembering to validate
the PIN code by pressing
.
00:00 Sat 02 Jan
Enter-******
The PIN code digits are displayed as “*” characters.
Mains
As the system uses hazardous voltages it is recommended that the mains supply connection follow
national wiring rules and is carried out by a suitably qualified person. This equipment must be
permanently connected to a mains fused spur (3A or 5A). The mains cable should be clamped
securely with the cable clamps provided within the equipment/installation kit. Knockouts are provided
on the top, bottom and sides of this equipment and these are intended for conduit or cable glands. As
a mains switch is not provided on the equipment, a readily accessible disconnect device shall be
incorporated in the building installation wiring. Where there is doubt as to the phase of this wiring , the
device, when operated, will disconnect both poles simultaneously.
Mains Supply
Item RX16i/QX32i PX48i/PX80i PX500/
PX250HS
3A Smart
Concentrator
External power source 230VAC +/- 10%, 50Hz
Input current rating (AC) 140mA 220mA 260mA 330mA
Mains Fuse F315mA 250V F400mA 250V T630mA 250V T630mA 250V
Aux. DC Supply
The DC supply output is a Safety Extra-Low Voltage (SELV) circuit. This DC supply rating is for all the
DC current requirements, including recharging the battery. The supply has the following rating:
Item RX16i/
QX32i
PX48i/
PX80i
PX500/
PX250HS
3A Smart
Concentrator
Output voltage (DC)
13.8V ± 5% 14V ± 5% 14V ± 0.1V 14V ± 5%
Standby Battery 7Ah 7Ah,
18 Ah
7Ah, 12Ah
or 18Ah
2 off 18Ah
Maximum recharge time 24 hours 24 hours 24 hours 24 hours
Power supply rating 1.0A 1.50A 2.5A 3.0A
Battery Charge Limit 0.5A 0.75A 0.78A 0.75A per
battery
Quiescent current 85mA 85mA 80mA 100mA
Aux. DC supply (Fuse 1) F800mA
250V
F800mA
250V
F800mA
250V
F1.6A 250V
Aux. DC supply (Fuse 2) F800mA
250V
F800mA
250V
F800mA
250V
F1.6A 250V
External Bus Aux. DC F800mA
250V
(Fuse 4)
F800mA
250V
(Fuse 4)
F800mA 250V
(Fuse 5)
Battery F1.6A 250V
(Fuse 3)
F2.5A 250V
(Fuse 3)
F2.5A
250V
(Fuse 9)
F2.5A 250V
(Fuses 3 & 4)
Internal Bus/Audio/Aux.
DC (Fuse 5)
XiB Bus 1-4 F800mA
250V
All wiring in this enclosure requires to be V-2, IEC approved or PVC type. All installation wiring within
this equipment should utilise plastic cable ties to bundle cables so as to provide strain relief for the
cable.