PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Contents CONTENTS .......................................................................................................................................................... 2 INTRODUCTION ................................................................................................................................................ 4 R&TTE DIRECTIVE DECLARATION ..................................................................................
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F 4 INPUT CONCENTRATOR ........................................................................................................................... 26 3A SMART CONCENTRATOR ...................................................................................................................... 27 XIB BUS ..................................................................................................................................................
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Introduction The installation manual provides the information essential for wiring and operating the system. Copies of the engineer manual, and all other Guardall manuals, can be downloaded from the Guardall web site, at www.guardall.com The documentation section of the Guardall web site is password protected, and you may have to apply for access using the on-line form provided on the site.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F EMC & LV Directives Declaration Apart from those products required to comply with the RTTE Directive, the remaining products described in this manual comply with the essential requirements and provisions of the EMC Directive 2004/108/EC and the LV Directive 2006/95/EC, based on application of the EU harmonised standards listed below.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Mains As the system uses hazardous voltages it is recommended that the mains supply connection follow national wiring rules and is carried out by a suitably qualified person. This equipment must be permanently connected to a mains fused spur (3A or 5A) using double insulated 3-core cable with each core being no less than 0.75mm2 (18AWG).
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F AUX DC Supply AUX DC Supply Technical Information The DC supply output is a Safety Extra-Low Voltage (SELV) circuit. This DC supply rating is for all the DC current requirements, including recharging the battery. The supply has the following rating: Item RX16i/ QX32i Output voltage (DC) Standby Battery 13.7V 5% 7Ah Maximum recharge time Power supply rating Battery Charge Limit Aux1 DC supply Fuse 24 hours 1.0A 0.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Getting Started In this manual you will learn how to; Identify the components of the PX system Connect components together Make simple configuration changes If you are new to the system it is recommended that you connect a basic system “on the bench” and familiarise yourself with programming the panel.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Once the keypad is replying then enter the default engineer PIN code, 9999, remembering to validate the PIN code by pressing . 00:00 Sat 02 Jan Enter-****** The PIN code digits are displayed as “*” characters.
PX Version 5.0 - QX/RX Version 4.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Order Codes Order code Inovonics Inovonics Part No. W76067 Description Radio module Inovonics(serial module + EE4000) W76245 EE5000 Inovonics repeater W76099 EE1215 W76094 EE1216 W76101 EE1233S Pendant Sgl. Button W76095 EE1233D Pendant Dbl. Button W76241 EE1223S 1 button water resistant pendant TX W76242 EE1223D 2 button water resistant pendant TX W76102 EE1235S Beltclip Trans.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F System Components A system comprises of the following components: 1. A control unit, which processes all the alarm information from the detection points. Outputs are provided to operate sounders, strobe and communication devices. Configuration information is stored in EEPROM. The manual details the features of the control panels. Most features in the PX panel range are common. The differences are shown in the table.
Audio LF CF Tamper Technical Specification 8 6 TX RX16i/QX32i GuardStation / Printer RS232 or Serial RS232 XiB Bus - 13 - 4 8 Concentrator GSR Data Comms Module 1.7km (unscreened cable) RX16i/QX32i Bus Connections PX Version 5.0 - QX/RX Version 4.
Comm Fail Tamper LF Strobe Audio Sounder External bus 8 8TX PX48i/PX80i/ PX250i Technical Specification (NOT on PX250i) GuardStation / Printer RS232 or Serial RS232 XiB Bus 4 - 14 - / Printer Serial Serial Module Output Module 8 1.7km (unscreened cable) GuardStation RS232 or 8 Concentrator Radio Module IP Module PX48i/PX80i/PX250i Bus Connections PX Version 5.0 - QX/RX Version 4.
Sounder Tamper Comm Fail Tamper LF Audio 8TX 2 Bus 4 Bus 3 Bus 2 Bus 1 PX500/ PX250HS Technical Specification PSTN/ GSM Module XiB Bus 1 4 - / Printer Serial Serial Module 15 - Output Module 8 1.7km (unscreened cable) GuardStation RS232 or 8 Concentrator Radio Module IP Module PX500/PX250HS Bus Connections Entry / Exit Proximity Readers Access Module Access PSU Smart Access Module PX Version 5.0 - QX/RX Version 4.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Technical Specification Technical Specification Parameter Temperature range Humidity Technical Specification Environmental Range -10 to 50 °C 10% to 90% relative humidity Cable Type The system has a 4-wire bus for all peripherals. The recommended cable type is 7-strand/0.2mm2 diameter un-screened cable, which has a resistance of 90 ohms/km and a core to core capacitance of 85nF/km.
PX Version 5.0 - QX/RX Version 4.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F The power supply standby capacity specified in EN 50131-1 is shown in the table. PD6662:2010 allows Grade 3 Installations to have a standby time of 24 hours, which can be reduced to 12 hours providing that Mains Failure is being signalled to the ARC as a separate message or channel.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Technical Specification EOL Resistor Connections Type 1 EOL Network (Guardall) Type 2 EOL Network 1 1 Alarm Tamper Alarm 8K2 R1 8k2 R2 Tamper C The EOL resistors are fitted in the detector as shown. This wiring arrangement applies to all EOL inputs in the system. Note: The diagram shows the default values of 8k2//8k2. The EOL resistor value can be programmed (Refer to the system options for details.).
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Diagnostics Diagnostics Accuracy The accuracy of the diagnostic system is typically less than 1%, with a maximum error 2.5%. This accuracy can only be achieved by programming the correct value of the 5V-reference voltage (option 69 on the main menu).
PX Version 5.0 - QX/RX Version 4.
PX Version 5.0 - QX/RX Version 4.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F PX500/PX250HS Control Unit PX500/PX250HS Control Unit Installation The PX 500 control panel is supplied with a spares bag containing the following items: Battery lead Cable clamp 2.5A fuse 800mA fuse x 8 (PX500/HS) Screw No 6 x 19mm 2 Screws No 6 x 9.5mm 2 ty-wraps 4 PCB stand-offs for fitting a XiB peripheral inside the case Various 2, 3, 4 and 5 way plug-on connectors 8k2 resistor x 2 Thermistor cable assembly.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F PX500/PX250HS PCB Connections (PX500/PX250HS) All PCB connections are plug-on screw down terminal blocks. The function and position of each terminal is described in the following page. LK8: Fit link to disable Case Tamper Case Tamper LK8 DataFlash 5 volt reference LK5 Battery max 18 Ah via FS9 a.c. FS1 800mA (Aux 1) FS2 800mA (Aux 2) ~ via FS1 ++ - - ++ - - 1234 5678 Comunicator Outputs Aux d.c.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F 8 Input Concentrator Outputs 3&4 of 4-output concentrator may only be programmed on a contol panel fitted with version 3.10 or later.
PX Version 5.0 - QX/RX Version 4.
Cct 3 Cct 2 Cct 1 Link 8 (Ext. Tamper Disable) Cct 4 8K2 Tamper 8K2 Alarm Cct 8 Link 2 (Tamper Disable) ISP - 27 - + - AB FS5 (800mA) BA- + XiB Bus Max 1700 m XiB bus out (isolated) XiB bus in (from control panel) ON 1 OP4 OP3 OP2 OP1 Outputs 1-4 current limited to 250 mA OTW Tamper If an input is not used the circuit can be Tamper switched off. There is no requirement to Link 9 terminate the input with the EOL resistors. (Case Each input can be mapped to any circuit Tamper number.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F 3A Smart Concentrator XiB Bus The 3A Smart Concentrator has 2 XiB connectors, XiB in and XiB out. The XiB in connector must be used to connect the XiB bus from the panel. All 4 wires may be connected but the XiB in + terminal is not connected to the XiB out + terminal. The XiB out connector is used to connect all XiB peripherals that are to be powered from the 3A Smart Concentrator.
PX Version 5.0 - QX/RX Version 4.
PX Version 5.0 - QX/RX Version 4.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Serial Module Engineer Keypad 8 Tamper disable ON 1 + B A - Address RX V+ 0v TX 1 2 DIL Switch 8 7654321 XXXX0000 XXXX0001 A serial module can be added at any time to a powered system but must be added to the system size before it will operate. The function switches only apply to versions up to v3.20.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F 10BaseT Data Comms Module Address 1 2 DIL Switch 87654321 00000000 00000001 The data comms module address can be set to 1 or 2 only. If a serial module is connected to the system then the serial module and data comms module addresses must be unique.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Keypad buzzer Case Tamper Disable ISP port PC1460 To set the address, create a case tamper and the press and hold down the ? button for a few seconds. Enter the address number when prompted. OP1 - 10mA max.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Mini Keypad The mini LCD proximity keypad is supported from v4.20.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Access Module Door Relay (8A) NVM1 NVM2 Tamper 8K2 DIL SW 8 - Tamper Disable DIL SW7 - Default config DIL SW6 - Not used Tamper To default the access module configuration power up with SW7 ON and return SW7 to the Off after a few seconds. Exit Reader Black, 0 Volt Smart PSU Interface Case Tamper 250 mA FS 2 250 mA 12 V 5V Reader supply voltage - Select 12v for Guardall readers.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Access Module Smart Access Module The smart access module includes a standard access module PCB and a power supply PCB. Only the power supply PCB is shown in the diagram. Red To Access Module The Smart Access Module 0V connection must be connected to the PX panel. + - AUX1 AUX2 Do not connect the Smart Access Module 12V to the PX panel. 1 Battery max. 7 Ah 2.5A - + ~ ~ a.c.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Proximity Reader Proximity Reader Access Module Connections ON OFF 8 NVM2 The diagram shows a Guardall reader. Other types of reader may be used. Refer to the engineer programming manual (System/card types) for details. 1 NVM1 XiB Comms Exit Reader Smart PSU Interface Black, 0 Volt Case Tamper 250 mA Entry Reader FS 2 250 mA 12 V 5V Reader supply voltage - Select 12v for Guardall readers.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Proximity Reader Function Door LOCKED Door UNLOCKED INVALID card, Access DENIED or Access ACCEPTED but door not opened.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Proximity Reader Keypad Connections To Drive an LED directly from a keypad connect either the brown wire (Green LED) or the green wire (Red LED) to the OP terminal of the keypad. The keypad output can be programmed for set, entry/exit or any other output function. A B D1 D0 Max. 150m + - The diagram shows a Guardall reader. Other types of reader may be used. Refer to the engineer programming manual (System/card types) for details.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Radio Module The radio module is fitted with 2 PCBs; a RF module and a serial interface for connection to the control panel XiB bus. The serial interface PCB is multi-function and for operation as a radio interface DIL switches 6 and 8 must be on and DIL switch 7 off. DIL switches 1-5 are used to select the radio module address. The diagram shows the Inovonics receiver module (W76067).
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F PSTN/GSM/Dual Comms module Statutory Requirements Hereby Guardall, declares that the Dual Comms module and PSTN module is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. If you have any doubts concerning the suitability, connection or uses of this apparatus then consult a suitably qualified person before continuing.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F Introduction The Dual Comm module, GSM module and the PSTN module may be used with any Guardall control panel. Feature Transmission Frequency Band Transmit Power Data Supported SIM card Implementation Voice and Data Dual Band EGSM900 and EGSM1800 Class 4 (2W) for EGSM 900MHz Class 1 (1W) for EGSM 1800MHz 9.6Kbps 3V cards There are a number of important points to consider when using one of the new module types with an existing panel: 1.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F GSM Antenna Avoid running cables near to the GSM antenna SIM Card Slot OFF ON 1 GSM DIL Switch Function 54321 0 0 0 0 0 PSTN primary 1 0 0 0 0 GSM primary 5 TB B B A - GND Line A + - A B + XiB Bus Telephone XiB Case OTW Hook BL Tamper Disable Optional Speech/Audio interface board TA Telephone line Engineer Keypad When power is applied to the system the GSM module will power up in 3 stages: 1.
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F LEDs Function XiB Comms Colour Green Hook Line monitor GSM Status Red Green Yellow State OFF ON Slow FLASH Quick FLASH ON ON Quick flash Slow flash ON Meaning No power Communication error Operating normally Active Line seized Valid Exchange voltage level present Network search Registered Active call Reporting Formats The available reporting formats for each route is shown in the table.
www.guardall.com Part Number: 320994-F Copyright © 2012 by United Technologies CCS.