Installation Instructions
PX Version 5.0 - QX/RX Version 4.51 Installation Manual – Issue F
- 6 -
Mains
As the system uses hazardous voltages it is recommended that the mains supply connection follow
national wiring rules and is carried out by a suitably qualified person. This equipment must be
permanently connected to a mains fused spur (3A or 5A) using double insulated 3-core cable with
each core being no less than 0.75mm
2
(18AWG).The mains cable should be clamped securely with
the cable clamps provided within the equipment/installation kit and the insulation around the inner
cores shall not touch the case when they are inserted into the mains terminal block. Knockouts are
provided on the top, bottom and sides of this equipment and these are intended for conduit or cable
glands. As a mains switch is not provided on the equipment, a readily accessible disconnect device
shall be incorporated in the building installation wiring. Where there is doubt as to the phase of this
wiring, the device, when operated, will disconnect both poles simultaneously.
Item RX16i/
QX32i
PX48i/
PX80i/
PX250i
PX500/
PX250HS
3A Smart
Concentrator
Smart Access
Module
External power source 230VAC +/- 10%, 50Hz
Input current rating (AC) 140mA 220mA 320mA 330mA 160mA
Mains Fuse F315mA 250V F400mA 250V T630mA 250V T630mA 250V F400mA 250V
Battery Disposal
It is the responsibility of the installer to dispose of batteries according to the local laws and regulations
of their region. Contact your local waste management office for information on battery recycling or
disposal.
If you are not able to identify the applicable rules in your area, please check the instructions which will
be available from the battery manufacturer.