View 4 Zone Keypad Module Bus Data Communications
3. Observe the time display on the LCD screen of the module. The character used to separate the hours from the minutes
is used to display the communication status according to the following table:
Character Meaning Possible Causes
:
Online All is OK
;
Module does not see messages addressed to itself on
SNAPP bus, (not enrolled)
Module serial # may have been incorrectly
entered at the main control
_
No bus communications at all cable, connections, or module fault
Specifications:
System Architecture
RS485 communications from Module to MONITOR main panel.
Single Output
Switches to negative when activated. This is not a positive “voltage going high” output.
4 Programmable Protection Point Input Types:
h Normally Closed
h Normally open with 2.2K End of Line resistor.
Enclosure Dimensions and Mounting:
4.6” (117 mm) wide, 5.4” (137mm) high, 1.125” (29 mm) deep , (1.29” (33 mm) deep with optional trunking spacer plate)
Suitable for mounting over North American single gang electrical box or surface mount on drywall etc.
Material:
Moulded Plastic, White.
Environmental:
-10°C to 55°C (14°F to 131°F)
Humidity Range:
10% to 93%
FCC Compliance Statement:
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:(1) This device may not cause harmful
interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and the receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by GUARDALL could void the user's authority to operate this equipment.
Canadian Compliance Statement:
This Class B digital apparatus complies with Canadian ICES-003.