User's Manual
 31
6.7.1 ELECTRICAL JUNCTION BOX
Install an approved, square electrical junction box 
with a blank cover on the interior or exterior wall 
of the area planned for installation of the generator 
(NOT on the generator). Route the generator's AC 
output leads into this junction box through approved 
flexible conduit. This is the point of first termination 
for generator AC output leads.
6.7.2 WIRING
•  Wiring should be of stranded copper to reduce the 
chance that vibration may cause breakage.
• Wire gauge size should be large enough to handle at 
least 115 percent of the installed generator's rated 
maximum current.
• If neutral conductors are used, they must be the 
same size as other leg wires.
•  Route power supply conductors from generator AC 
output leads T1 (red), T2 (white), T3 (black) and 
the green ground wire through approved flexible 
conduit to the electrical junction box on the com-
partment wall.
• If flexible metal conduit is used between the gen-
erator and the compartment junction box, the con-
duit end that terminates the compartment junction 
box must be vapor-sealed. Flexible metal conduit 
is NOT vapor tight along its entire length.
• From the junction box, route power supply wires 
through approved conduit to either (a) double-pole, 
double-throw transfer switch, or (b) approved iso-
lation receptacle. Connecting to a transfer switch 
or isolation receptacle must prevent vehicle electri-
cal circuits from being connected to two different 
power supplies at the same time (such as genera-
tor and dockside power).
•  Conductors must be rated 221° F (105° C) or must 
be of a larger conductor size.
6.7.3  GENERATOR AC CONNECTIONS
Generator AC output leads T1 (red), T2 (white) and 
T3 (black) come out of the generator as shown in 
Figure 6.14. Leads T1 (red) and T3 (black) are “hot,” 
while T2 (white) is the grounded neutral lead. There 
is also a green lead that connects to ground in the 
junction box of the recreational vehicle.
Line T1 (red) to T2 (white) is protected against 
overload by a circuit breaker (CB1). Use this line-
to-neutral connection separately to operate 120-volt, 
single-phase, 60 Hertz, AC loads. Line T3 (black) to 
T2 (white) also is protected against overload by a cir-
cuit breaker (CB2). Use this line-to-neutral connec-
tion separately to operate similar loads. However, be 
sure the total unit load does not exceed the maximum 
rating of the generator. The neutral line (T2, white) on 
all units is a grounded neutral.
Figure 6.14 – Generator AC Output Leads
T3
T2
T1
Green
(Ground)
 Do NOT connect electrical loads in excess of any 
circuit breaker rating or problems will develop 
with circuit breaker tripping, which causes a loss 
of AC output. Also, do NOT exceed the gener-
ator's rated wattage capacity. Add the watts 
or amperes of all lighting, appliance, tool and 
motor loads the generator will operate at one 
time. This total should be less than the unit's 
rated wattage/amperage capacity.
6.7.4 CONDUIT
Route the connections between the generator and the 
junction box through approved, flexible conduit. The 
following general rules apply:
• Cut wiring to the required length and allow extra 
wire for junction box connections.
• Carefully prepare conduit ends to prevent sharp 
edges from cutting through wiring insulation.
•  Route conduit so it does not interfere with genera-
tor movement.
•  If using metallic conduit, vapor seal the end of the 
conduit where it enters the junction box. Do this 
because flexible metallic conduit is not vaporproof 
along its entire length.
6.7.5 ISOLATING DIFFERENT POWER 
SOURCES
Connections from the junction box must terminate in 
a double-pole, double-throw transfer switch (Figure 
6.15). An alternate method for isolating different 
power sources is by using an isolating receptacle 
(Figure 6.16). Whichever method is used, be certain 
that both power sources are NOT connected at the 
same time.
Section 6 – Installation
Recreational Vehicle Generators










