User's Manual

41 / 56 ZONESCAN net
Version 1.4
Figure 39 Settings > Repeater
Warning when not reachable for:
Define the number of days after which a warning is displayed if a repeater
was not reached.
Preset: 3 days
Problem when not reachable for:
Define the number of days after which an error is displayed if a repeater
was not reached.
Preset: 6 days
Warning when below:
Enter the charge state of the batteries of the repeaters below which a
warning is displayed.
Preset: 2.80 V
Problem when below:
Enter the charge state of the batteries of the repeaters below which an
error is displayed.
Preset: 2.60 V
Minimum temperature limit:
Enter the lower temperature value below which a warning or an error is
displayed.
Preset: -30.0°C
Maximum temperature limit:
Enter the upper temperature value above which a warning or an error is
displayed.
Preset: 70.0°C
Warning when temp. below minimum for:
Enter the number of days after which a warning is displayed if the
Reachability Warning
Limits
Battery Voltage
Warning Limits
Temperature Warning
Limits