Query Example
GSB1:MEAS?
> 12345678<cr><lf>
>GSB-01:PXXPXXXX<cr><lf>
>GSB-02:XFXXXFXX<cr><lf>
>GSB-XX:XXXXXXXX<cr><lf>
>GSB-XX:XXXXXXXX<cr><lf>
Indicates that channel 1 and 4 have passed for the
GSB-01 and that channel 2 and 6 have failed for the
GSB-02.
GSB<X>:HI
Set
Query
Description
Sets or queries the HI settings for each scanner box
for a selected MANU test number.
Syntax
Query Syntax
GSB<X>:HI <string>
GSB<X>:HI?
Parameter
<X>
1~100 (MANU number)
Parameter/Return
parameter
<string>
8 character Hex code of a binary number
(16 digits), prepended with āSā.
HI = binary 1, other = binary 0.
First 2 Hex/8 binary digits = 1
st
scanner
box, second 2 Hex/8 binary digits = 2
nd
scanner box, third 2 Hex/8 binary digits
= 3
rd
scanner box, 4
th
2 Hex/8 binary
digits = 4
th
scanner box.
String format:
Hex code
Binary
Ch1 ~ CH8
1
st
scanner
Ch1 ~ CH8
2
nd
scanner
Ch1 ~ CH8
3
rd
scanner
Ch1 ~ CH8
4
th
scanner
XXXXXXXX:XXXXXXXX:XXXXXXXX:XXXXXXXX
XX:XX:XX:XX
Example1
GSB1: HI S80000000
Sets Channel 1 of scanner 1 to HI. All other channels
are off. (8000000 Hex =
10000000000000000000000000000000 binary)