User Manual User Manual
INTERFACE
235
Configure Channel Control interface
Channel control
configuration
Connector
Screwless connector.
Wire Gauge
22-28 AWG (24 AWG
recommended).
Wire connection
10 mm strip gauge for
connection.
Input
0-10V.
Pin Assignment
1
GND
Negative potential of the load
input terminal.
2
I MON (OUTPUT)
Load input current monitor;
where 0V = 0% of input current
and 10V = 100% of input
current.
3
V MON (OUTPUT)
Load input voltage monitor;
where 0V = 0% of input voltage
and 10V = 100% of input
voltage.
4
Ext Voltage ref
(INPUT)
External voltage reference;
Where 0V=0% of rating
voltage/current and 10V =
100% of rating voltage/current.
The external voltage reference
is for CC and CV mode.