DC Electronic Load PEL-3000 Series USER MANUAL VERSION: 1.
This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent of Good Will company. The information in this manual was correct at the time of printing. However, Good Will continues to improve products and reserves the rights to change specification, equipment, and maintenance procedures at any time without notice. Good Will Instrument Co., Ltd. No.
Table of Contents Table of Contents SAFETY INSTRUCTIONS ................................................... 3 GETTING STARTED ........................................................... 8 PEL-3000 Series Introduction ............... 10 Accessories .......................................... 12 Appearance .......................................... 15 First Time Use Instructions ................. 24 OPERATION .................................................................... 48 Basic Operation .............
PEL-3000 User Manual Replace the Clock Battery ................... 176 GPIB Installation ................................ 177 PEL-3000 Default Settings .................. 178 Frame Control Connector Contacts .... 181 Operating Mode Description .............. 186 Operating Area................................... 191 PEL-3000 Specifications ..................... 195 PEL-3000 Dimensions ........................ 207 Declaration of Conformity .................. 210 INDEX ........................................
SAFETY INSTRUCTIONS SAFETY INSTRUCTIONS This chapter contains important safety instructions that you must follow during operation and storage. Read the following before any operation to insure your safety and to keep the instrument in the best possible condition. Safety Symbols These safety symbols may appear in this manual or on the instrument. WARNING Warning: Identifies conditions or practices that could result in injury or loss of life.
PEL-3000 User Manual Safety Guidelines General Guideline CAUTION Do not place any heavy object on the instrument. Note: Only 2 units can be stacked vertically. Avoid severe impact or rough handling that leads to damaging the instrument. Do not discharge static electricity to the instrument. Use only crimped wires, not bare wires, for the terminals. Do not block the cooling fan opening. Do not disassemble the instrument unless you are qualified.
SAFETY INSTRUCTIONS Power Supply AC Input voltage range: 100~120VAC/200~240VAC (90~132VAC/180~250VAC) Frequency: 47~63Hz Power: PEL-3021: 90VA Max PEL-3041: 110VA Max PEL-3111: 190VA Max PEL-3211: 230VA Max To avoid electrical shock connect the protective grounding conductor of the AC power cord to an earth ground. Disconnect the power cord before cleaning. Use a soft cloth dampened in a solution of mild detergent and water. Do not spray any liquid.
PEL-3000 User Manual (Pollution Degree) EN 61010-1:2010 specifies the pollution degrees and their requirements as follows. The instrument falls under degree 2. Pollution refers to “addition of foreign matter, solid, liquid, or gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”. Storage environment Disposal 6 Pollution degree 1: No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
SAFETY INSTRUCTIONS Power cord for the United Kingdom When using the instrument in the United Kingdom, make sure the power cord meets the following safety instructions.
PEL-3000 User Manual GETTING STARTED This chapter provides a brief overview of the PEL-3000, the package contents, instructions for first time use and an introduction to the front panel, rear panel and GUI. PEL-3000 Series Introduction .......................................... 10 Model Line Up ......................................................................................................... 10 Main Features ..........................................................................................
GETTING STARTED (PEL-3211 Booster Pack) ......................................................................... 21 Display ....................................................................................................................... 23 First Time Use Instructions ............................................. 24 Rack Mount Kits ...................................................................................................... 24 Power Up and Self Test ........................................
PEL-3000 User Manual PEL-3000 Series Introduction The PEL-3000 Series is a family of high performance DC electronic loads positioned to test a wide range of different power sources. The DC electronic loads are fully programmable to simulate anything from basic static loads to complex dynamic loads. With the ability to operate independently or in parallel, the PEL-3000 Series is extremely robust and capable of molding to any test environment.
GETTING STARTED Main Features Performance Features Interface High slew rates of up to 16A/μS(PEL-3111) for a fast response speed High capacity when used in parallel: 5250W, 1050A (PEL-3111 x 5)/ 9450W, 1890A (PEL-3111 + PEL-3211 x 4) High resolution – 16 bit 7 operating modes: CC, CV, CR, CP, CC+CV, CR+CV, CP+CV Independent and parallel operation Fully programmable with normal and fast sequences Soft start Dynamic mode OCP, OVP and other protection features Remote
PEL-3000 User Manual Accessories Standard Accessories Part number Description 82EL-31110MB1 Quick Start Guide 82EL-31110EB1 User / Programming manual CD Region dependant Power cord PEL-011 Load input terminal Cover PEL-012 Terminal fittings: 2 sets of bolts/nuts/springs/washers (type: M8) M8 x 20 Spring washer Flat washer M8 nut Optional Accessories 12 Part number Description 3813-030D0501 CR123A 3V lithium battery for clock.
GETTING STARTED GTL-255 300mm Frame Link Cable (for linking units that are stacked) GTL-248 GPIB cable, 2.
PEL-3000 User Manual Package Contents Check the contents before using the instrument.
GETTING STARTED Appearance PEL-3000 Front Panel (PEL-3021/PEL-3041) Air inlet LCD Display Function keys Power key Main/Local FUNC/File Local Main File FUNC Help/Utility Utility Help Short P7 Preset Shift 175W 1.5 - 150V 0 - 35A P9 8 9 P5 P6 4 5 6 P1 P2 P3 1 2 P0 CAL.
PEL-3000 User Manual (PEL-3211 Booster Pack) LINK Air Inlet The air inlet has a removable dust filter LCD display 3.5 inch LCD display STBY Function keys The function keys directly correspond to the soft menu keys at the bottom of the display. Turns the unit on or puts the unit into standby mode. Use the power switch on the rear panel to turn the unit off. ON/STBY Main/Local Main Main: Sets the operating mode: CC, CV, CR, CP mode.
GETTING STARTED File Help/Utility FUNC Help Help: Access the help menu. Utility Shift Short File (Shift + FUNC): Accesses the file system. Shift Short Help Utility (Shift + Help): Access the utility menu. Pressing the Short key will simulate shorting the input terminals. The Short key will be lit when active. Load on/off Load On/ Off Turns the load on or off. The Load On/Off key will be lit when active. Use the scroll wheel to navigate the menu system or to edit parameters.
PEL-3000 User Manual Number pad P7 P8 7 8 P9 9 P4 P5 P6 4 5 6 P1 P2 P3 1 2 3 P0 CAL. Lock 0 Clear Number pad: Used to enter numerical values. P0~P9 (Preset + Number keys): Loads one of 10 preset settings. Clear/Lock Lock Clear Clear: Clears the current parameter values. Lock (Shift + Clear): Locks the front panel keys and selector knob. Shift Preset USB Port 18 Shift Preset Shift: Used in conjunction with other keys to select secondary functions.
GETTING STARTED Front panel input terminals 175W 1.5 - 150V 0 - 35A Negative terminal. IMON Out I MON OUT TRIG OUT TRIG OUT Positive terminal. Current monitor BNC terminal: Output connector used to monitor the current by outputting a voltage. An output voltage of 1V corresponds to the full scale current for the H and L ranges. 0.1V corresponds to the full scale current in the M range. Trigger out BNC terminal: Outputs a pulse signal during sequence or dynamic operation.
PEL-3000 User Manual Rear Panel PEL-3021 / PEL-3041 Frame control ports, J1, J2 Remote sense inputs Rear panel inputs FRAME CONT SER. NO. LB J1 J2 WARNING TO AVOID ELECTRIC SHOCK THE POWER CORD PROTECTIVE GROUNDING CONDUCTOR MUST BE CONNECTED TO GROUND. RS232C NO OPERATOR SERVICEABLE COMPONENTS INSIDE. RS232C port DO NOT REMOVE COVERS. REFER SERVICING TO QUALIFIED PERSONNEL. GPIB AC 100 - 120 VAC 200 - 240 VAC 47 - 63 Hz 90 VA MAX.
GETTING STARTED (PEL-3211 Booster Pack) RS232C Port The USB B, RS232C and GPIB port are used for remote control. GPIB USB B USB B port Frame control ports, J1, J2 RS232C 9 pin DSUB port. GPIB 24 pin female. FRAME CONT J1 J2 J1: The J1 connector is assigned to external control. J2: The J2 connector is used for parallel operation control.
PEL-3000 User Manual Exhaust fan The exhaust fan is used to expel the heat from the unit. Please ensure there is at least 20cm distance between any object and the fan. Rear Panel Input terminals Rear Panel Input Terminals. Electrically connected to the front panel input terminals. Accepts M8 bolts or M4/M3 sized screws. See page 34 for connection details. Remote Sensing Terminals Sensing terminals for remote sense. See page 35. Accepts M3 sized screws.
GETTING STARTED Display Date Mainframe status panel RS232 LOAD 03/Sep/2012 Measurement area Setting area 0.000 V 0.000 A 0.00 w CC A Value 0.000 A CC B Value 0.000 A SlewRate 2500.00 mA/us Mode CV I Range H 35A V Range L 15V Function Static Fine Operation status panel A Value Configure Softkeys Setting area The setting area is used to display and edit the settings for the current mode/function. Measurement area Displays the voltage, current and power values. Date Displays the date.
PEL-3000 User Manual First Time Use Instructions Use the procedures below when first using the PEL-3000 to install the rack mount kit, power up the instrument, set the internal clock, restore the factory default settings and check the firmware version. Lastly, the Conventions section will introduce you to the basic operating conventions used throughout the user manual. Rack Mount Kits Description The PEL-3000 has a number of rack mount options for installation.
GETTING STARTED 128 GRA-413 (EIA standard) 48 2.6 53 2 .5 149 GRA-413 (JIS standard) 48 2.6 53 2 .
PEL-3000 User Manual 132 GRA-414-E (EIA standard) 47 7.6 38 2.5 149 GRA-414-J (JIS standard) 47 26 7.6 38 2.
GETTING STARTED Power Up and Self Test Steps 1. Insert the AC power cord into the power socket. 2. Turn the external power switch on. (O → —) 3. If the unit doesn’t turn on, press the On/Standby key. The ON/STBY key will go from standby (red) to on (green). 4. The unit will show the splash screen and then load the settings from when the unit was last powered down. Note If the PEL-3000 fails to start up properly or does not turn on, please see you local distributor.
PEL-3000 User Manual Load Default Settings When first using the PEL-3000, recall the factory default settings to ensure the unit is in a known state. See page 178 for a list of the default settings. Description File Operation 1. Press Shift + . Select Media/Default[F1]. Select Factory Default[F2].
GETTING STARTED RS232 LOAD 03/Sep/2012 Date Date/Time Month Day Year Hour Minute System Info Load 3 9 2012 0 9 Interface Time Set Other Load Wiring Wire Gauge considerations Before connecting the unit to a power source, the wire gauge must be taken into account. Load wires must be large enough to resist overheating when a short-circuit condition occurs as well as to maintain a good regulation.
PEL-3000 User Manual 2 3 4 5 6 7 8 9 10 11 12 13 14 Load Line Inductance Considerations 6.54304 5.82676 5.18922 4.62026 4.1148 3.66522 3.2639 2.90576 2.58826 2.30378 2.05232 1.8288 1.62814 0.51266 0.64616 0.81508 1.02762 1.29593 1.6341 2.0605 2.59809 3.27639 4.1328 5.20864 6.56984 8.282 181 158 135 118 101 89 73 64 55 47 41 35 32 When using the PEL-3000 load generator, voltage drop and voltage generated due to load line inductance and current change must be taken into account.
GETTING STARTED Current ∆I Voltage time ∆T E Min. V time The diagram above shows how changes in current can affect voltage. Limiting Load line inductance Load line inductance can be reduced in two ways. 1. Ensure load wires are as short as possible and twist the positive and negative load wires together. 2. Current change can be limited by limiting the slew rate or response speed when switching in CR and CC mode.
PEL-3000 User Manual Load Wire Connections Description The PEL-3000 has input terminals on both the front and rear panels. Follow the procedures below for all load connections. Please adhere to the following precautions to ensure your safety and to protect the unit from damage. Connection When connecting the PEL-3000 to the DUT, make sure that the polarity of the connection between the DUT and the unit matches. Ensure that the maximum input voltage is not exceeded.
GETTING STARTED Using the Front Panel Input Terminals The front panel input terminals feature polarity-distinct caps and accept M6 sized crimped terminals. Description The front panel input terminals on the PEL-3000 are physically connected to the rear panel terminals. Caution Steps 1. Turn the power off from the rear panel or put the unit into standby mode. 2. Turn the power off from the DUT. 3.
PEL-3000 User Manual Using the Rear Panel Input Terminals The rear panel input terminals accept up to M8-sized crimped terminals. The rear terminals come with a load input terminal cover for safety. Description The front panel input terminals on the PEL-3000 are physically connected to the rear panel terminals. Caution Steps 1. Turn the power off from the rear panel or put the unit into standby mode. 2. Turn the power off from the DUT. 3.
GETTING STARTED Using the Terminal Cover Description The rear panel terminal cover should be used to prevent electric shock. The rear panel terminal covers should always be used when connecting a load to the rear panel terminals. As the front panel and rear panel terminals are physically connected, the terminal cover should also be used as a safety measure when a DUT is connected to the front terminals Caution Ensure the power is off before making any connections to the PEL-3000.
PEL-3000 User Manual 2 Detail 3 4. Use your thumb to slide the terminal covers shut, as shown in the diagram below.
GETTING STARTED 5. When the top and bottom covers are flush, reinsert the screw that was removed in step 1.
PEL-3000 User Manual Remote Sense Remote sense can be used to help compensate for long cable length. The longer the cable, the higher the potential resistance and inductance, therefore a short cable is best. Twisting the cable can help reduce induced inductance and using the Vsense terminals compensates the voltage drop seen across the load leads, especially leads with higher resistance. This is useful when used in CV, CR or CP mode. Description Steps 1.
GETTING STARTED Firmware Update Description The PEL-3000 allows the firmware to be updated by end-users. Before using the PEL3000, please check the GW Instek website or ask your local distributor for the latest firmware. System version Before updating the firmware, please check the firmware version. Utility Operation 1. Press Shift + Help . 2. Select System/Info[F1]. 3. The System information is listed on the display. Model: PEL-3000 model number. Serial Number: XXXXXXXX Firmware Ver.
PEL-3000 User Manual RS232 LOAD 03/Sep/2012 Model : PEL-30XX Serial Number : 00000001 Firmware Ver. : 1.01.011 http://www.goodwill.com.tw System Info Load Interface Time Set Other Update Firmware 1. Insert a USB drive into the USB port. Ensure the USB drive has the firmware file located in the root directory. File 2. Press Shift + FUNC . 3. Select USB with the Media[F1] soft-key. 4. Press the File Utility[F5] soft-key. 5. Select the *.UPG upgrade file and press Select[F1] twice.
GETTING STARTED Conventions The following conventions are used throughout the user manual. Read the conventions below for a basic grasp of how to operate the PEL-3000 menu system using the front panel keys. Soft Menu keys The F1 to F5 function keys at the bottom of the display correspond directly to the soft-menu keys on top. RS232 LOAD 03/Sep/2012 0.00 w 0.000 V 0.000 A Soft-menu keys Preset F1 ~ F5 function keys 175W 1.5 - 150V 0 - 35A Select Sub Menu I MON OUT File CC A Value 0.
PEL-3000 User Manual Toggle Parameter or State Function/Item Mode CC Parameter or State This type of soft-menu icon has the function/item on the top of the label and the selected setting or mode on the bottom of the label. Repeatedly press the associated function key (F1~F5) to cycle through each setting. For example, repeatedly pressing the Mode softmenu key will cycle through the CC, CR, CV and CP modes. Mode CC Mode CR Mode CV Mode CP For some parameters, a popup window will also appear.
GETTING STARTED The scroll wheel, Enter key and number pad can be used to edit parameter values. Parameter Input Number pad P7 P8 P9 7 8 9 P4 P5 P6 4 5 6 P1 P2 P3 1 2 3 P0 CAL. Lock 0 Scroll wheel Clear Enter Enter key 1. Use the scroll wheel to move the cursor to the desired parameter. A scroll bar is shown when there are additional parameters off-screen. RS232 LOAD 03/Sep/2012 0.000 V 0.00 w 0.000 ACursor Level1 Level2 Timer1 Mode CP 0.00 W 0.00 W 0.
PEL-3000 User Manual 3. Then use the number pad* or scroll wheel** to edit the parameter value. RS232 LOAD 03/Sep/2012 0.000 V 0.000 A 0.00 w Parameter CC A Value 0.000 A CC B Value 1.000 A SlewRate 2500.00 mA/us Mode CC I Range H 35A V Range L 15V Function Static Fine A Value Configure 4. Press the Enter key again to finish editing the parameter value. Clearing a Value* *When editing a parameter with the number pad, pressing the Clear key will restore the parameter to the previous value.
GETTING STARTED Step Mode: This is the default step resolution method and will only be available to use when it is applicable (Indicated by Fine or Coarse in the Operation Status panel). When a parameter is highlighted (step 3 above) pressing the scroll wheel will toggle the step resolution between fine and coarse. For details on how to set the step resolution, see page 78. RS232 LOAD 03/Sep/2012 0.00 w 0.000 V 0.000 A + CC A Value 0.000 A CC B Value 1.000 A SlewRate 2500.
PEL-3000 User Manual When renaming files, creating memos or notes, you will be required to enter alphanumeric characters when the character entry screen appears. Entering Alphanumeric Characters Only alphanumeric characters as well as space [ ], underscore [_] and minus [-] characters allowed. 1. Use the scroll wheel to move the cursor to the desired character. Rename: Filename A B C D E F G H I J K L M N O P Q R S T U V W X Y Z 1 2 3 4 5 6 7 8 9 0 _ 1 Cursor 2.
GETTING STARTED Help Menu When any function key has been pressed or when a menu has been opened, the HELP key can be used to display a detailed description. Help Selection 1. Press any function key or soft-menu key. 2. Press Help to see the help contents on that particular function key or menu. 3. Use the scroll to navigate the help contents. 4. Press the Exit[F5] key to exit the help menu. 03/Sep/2012 RS232 LOAD HELP Press F5 to exit the Help mode. Rotate the VARIABLE knob to scroll all the contents.
PEL-3000 User Manual OPERATION Basic Operation .............................................................. 51 CC Mode ................................................................................................................... 51 CR Mode ................................................................................................................... 53 CR Units ...................................................................................................... 55 CV Mode.....................
OPERATION Cursor Mode Configuration ................................................................................... 77 Step Mode Configuration ....................................................................................... 78 Protection Settings .......................................................... 80 OCP ........................................................................................................................... 80 OPP .......................................................
PEL-3000 User Manual File Types .................................................................................................. 120 Saving Files to Internal Memory ............................................................ 121 Saving Files to USB Memory .................................................................. 123 Recalling Files from Internal Memory................................................... 125 Recalling Files from USB Memory ........................................................
OPERATION Basic Operation The PEL-3000 supports 7 main operating modes: CC, CC+CV; CR, CR+CV; CV; CP, CP+CV CC Mode Description Warning Operation In Constant Current Mode the load units will sink the amount of current programmed. Regardless of the voltage, the current will stay the same. For more details on CC mode, please see the Appendix on page 186. If you change the mode or the range when the load is already on, the load will be turned off automatically. 1. Make sure the load is off. 2.
PEL-3000 User Manual 6. Set the current level parameters using the scroll wheel and number pad. For Static mode, set CC A Value and/or CC B Value. For Dynamic mode, set Level1 and Level2. The maximum and minimum current levels depend on the selected ranges. 7. To add CV mode to CC mode (CC+CV), see page 58. 8. Set the remaining basic configuration settings such as the slew rate, and switching mode settings. See page 63 for details. Display RS232 LOAD 03/Sep/2012 w 0.000 V Active 0.
OPERATION CR Mode Description Warning Operation In Constant Resistance Mode, the unit will maintain a constant resistive load by varying the current. CR mode uses ohms, Ω (resistance) or siemens, S (conductance) for the setting units. For more details on CR mode, see the appendix on page 187. If you change the mode or the range when the load is already on, the load will be turned off automatically. 1. Make sure the load is off. 2. Press Main . 3. Select CR mode with the Mode[F1] soft-key. 4.
PEL-3000 User Manual 6. Set the resistance or conductance level parameters using the scroll wheel and number pad. For Static mode, set CR A Value and/or CR B Value. For Dynamic mode, set Level1 and Level2. The maximum and minimum conductance/ resistance levels depend on the selected current range. 7. To add CV mode to CR mode (CR+CV), see page 58. 8. Set the remaining basic configuration settings such as the slew rate, and switching mode settings. See page 63 for details.
OPERATION CR Units Description Operation The CR setting units can be set to ohm (Ω) or millisiemens (mS). 1. Make sure the load is off. 2. Press Main > Configure[F5] > Other[F2] and set the CR Unit setting. Range: Ω, mS CV Mode Description Warning Operation In Constant Voltage Mode, the unit will maintain a constant voltage. In CV mode you set the constant voltage level. For more details on CV mode, see the appendix on page 190.
PEL-3000 User Manual 6. Set the voltage level parameters using the scroll wheel and number pad. Set CV A Value and/or CV B Value. The maximum and minimum voltage levels depend on the selected voltage range. 7. Set the remaining basic configuration settings such as the response settings. See page 63 for details. Display RS232 LOAD 03/Sep/2012 0.00 w 0.000 V Active setting 0.000 Current setting A Voltage settings Mode CV A Value CV B Value 15.000 V 15.
OPERATION If you change the mode or the range when the load is already on, the load will be turned off automatically. Warning Operation 1. Make sure the load is off. 2. Press Main . 3. Select CP mode with the Mode[F1] soft-key. 4. Select the current range with the I Range[F2] soft-key. Range: High, Middle, Low 5. Select the voltage range with the V Range[F3] soft-key. Range: High, Low 6. Set the power level parameters using the scroll wheel and number pad.
PEL-3000 User Manual Display RS232 LOAD 03/Sep/2012 0.00 V 0.00 w 0.000 Current setting A Active setting Power settings CP A Value CP B Value Mode +CV Mode CP I Range H 35A 0.00 W 0.00 W Voltage range OFF Fine A Value V Range H 150V Function Static Configure Current range Basic CP mode configuration is complete. See page 63 for more configuration options. Note The current range and voltage range applies to all the operating modes. +CV Mode CV mode can be added to CC, CR and CP mode.
OPERATION Display RS232 LOAD 03/Sep/2012 0.000 V 0.000 A 0.00 w Timer1 +CV setting 0.025 ms Timer2 0.025 ms +CV 5.500 V Mode CP I Range H 35A V Range L 15V Function Dynamic Configure The +CV settings apply to all the applicable operating modes. Note For example: The +CV settings made in CR mode will be carried over to the +CV settings in CC and CP mode. +CV settings cannot be controlled with external control. Note Turning on the Load Description 1.
PEL-3000 User Manual Note The load can be set to automatically turn on at start up. See page 75. The load can be turned on via remote control. See the programming manual. The load can be turned on via external control. See page 143. By default the load will automatically turn off if the range or operating mode (CC, CV, CR, CP) is changed. To disable this behavior, Set Load Off (Mode) and Load Off (Range) to the OFF setting. See page 76 for details.
OPERATION Operation 1. The short function can be turned on and off by pressing the Short key. The Short key will turn red when the short function is active. The Short icon will appear when the short function is active. Range: Toggle, Hold Display SHORT on SHORT RS232 LOAD 03/Sep/2012 1.500 V Short Key Configuration 0.000 A Level1 W The Short key can be0.00 configured to Toggle or Hold. By Default the0.00 ShortWkey is set to Toggle. Level2 Description Operation 1.
PEL-3000 User Manual Operation 1. The keys can be locked and unlocked by Lock pressing Shift + Clear LOCK will appear in the Mainframe status panel when the keys are locked. The on. Load On/ Off Display key will not be locked if the load is LOCK icon LOCK 03/Sep/2012 0.000 V 0.000 A Timer1 Timer2 +CV Mode CP 62 . RS232 LOAD 0.00 w 0.025 mS 0.025 mS 5.
OPERATION Basic Configuration The basic configuration settings are the common configuration settings that are used for each operating mode. After selecting a basic operating mode (CC, CR, CV or CP mode), the slew rate, switching mode, response rate and other common parameters should be configured. Select the Switching Function The PEL-3000 has two switching modes, static and dynamic. The switching modes allow the PEL-3000 to switch between two preset levels.
PEL-3000 User Manual Dynamic Mode Level Level 2 Level 1 Timer1 Timer2 Timer1 Time Dynamic mode is not available for CV mode. Note Operation 1. Make sure the load is off. 2. Press Main . 3. Select Dynamic or Static mode with the Function[F4] soft-key. A different switching mode can be set for CC, CR and CP mode. 4. For dynamic mode, set the Timer1 and Timer2 parameters using the scroll wheel and number pad. Timer1 sets the Level1 on-time. Timer2 sets the Level2 on-time.
OPERATION Display: Static Mode The load can be ―on‖ when switching between A Value and B Value. RS232 LOAD 03/Sep/2012 0.00 w 0.00 V A 0.000 B Value A Value CP A Value 0.00 ActiveWsetting CP B Value 0.00 W StaticOFF modeV +CV Mode CP Display: Dynamic Mode I Range H 35A V Range H 150V Function Static 0.000 V A 0.000 Level2 Level1 Mode CP Configure RS232 LOAD 03/Sep/2012 Level1 Level2 Timer1 Fine A Value 0.00 w Timer1 0.00 W 0.00 W 0.
PEL-3000 User Manual Operation 1. Make sure the load is off. 2. Press Main > Configure[F5] > Other[F2] and set the Dyna. Level setting. Range: Value, Percent Display: Percent Setting RS232 LOAD 03/Sep/2012 0.000 V Set level A 0.000 Set Level Timer1 Mode CP Example 0.00 w % from the Set value 1.00 W 50.0 % 0.025 ms I Range H 35A V Range L 15V Function Dynamic Fine Configure Dynamic Mode: Dyna.
OPERATION Select the Switching Time Configuration for Dynamic Mode The switching time for dynamic mode can be configured to switch between two preset ontimes (Timer1, Timer2) or by setting a switching frequency and duty cycle. Description Operation 1. Press Main > Configure[F5] > Other[F2] and set the Dyna. Time setting. Range: T1/T2, Freq. Duty Slew Rate The current slew rate can be set for CC and CR mode. The slew rate setting is used to limit the change in current when switching.
PEL-3000 User Manual Display RS232 LOAD 03/Sep/2012 0.00 V Slewrate settings A 0.000 SlewRate SlewRate Timer1 Mode CC I Range H 35A 0.00 w 2500.00 mA/uS 2500.00 mA/uS 0.025 ms V Range H 150V Function Dynamic Configure CV Mode Response Speed The response speed setting is the response speed for the negative feedback control of the load current when used in CV mode. Response speed settings are only applicable to CV mode.
OPERATION Display RS232 LOAD 03/Sep/2012 0.000 V 0.000 A CV A Value CV B Value 15.000 V 15.000 V Response setting 0.00 w Fine A Value Mode CV I Range H 35A V Range Response Configure L 15V Slow CC, CR and CP Mode Response Speed By default, the ―normal current response‖ speed is set to 1/1. The response speed can be reduced to 1/2, 1/5, 1/10. Description Operation Reducing the current response speed can affect other settings such as the slew rate and soft start settings. 1.
PEL-3000 User Manual Advanced Configuration Settings Use the advanced configuration settings to configure settings other than those described in the basic configuration chapter. Soft Start Setting The soft start setting is used to limit the amount of input current at start-up or from when the Von Voltage threshold is tripped. Description The soft start setting only applies to CC, CR and CP mode.
OPERATION Von Voltage Settings Von Voltage Level Description The Von Voltage is the threshold voltage at which the load module will start to sink current. V Von voltage V out Von Load on I Time PEL-3000 Time Operation 1. Press Main > Configure[F5] > Other[F2] and set the Von Voltage level. Range: Von Voltage: 0.
PEL-3000 User Manual Von Voltage Latch When Von Latch is set to ON, the load will continue to sink current after being ―latched‖, even if the voltage drops below the Von Voltage threshold level. Description When Von Latch is set to OFF, the load will turn off when the voltage drops below the Von Voltage threshold level. By default Von Latch is set to OFF.
OPERATION Von Voltage Delay Von Delay is the amount of time the unit will wait before turning the load on after the Von Voltage threshold has been latched. This will prevent overshoot current from affecting the Von Voltage threshold. Description Operation 2. Press Main > Configure[F5] > Other[F2] and set the Von Delay time. Range: Von Delay: OFF, 1.0~60ms Note: CR mode can have the delay time set separately from the other modes (called Von Delay –CR when in CR mode).
PEL-3000 User Manual Operation Display 1. Press Main > Configure[F5] > Other[F2] and turn the Count Time on or off. Range: ON, OFF RS232 LOAD 03/Sep/2012 0.00 w 0.000 VElapsed time 0:00:05 0.000 A Cut Off Time Level1 Level2 Timer1 Mode Description Operation Display 0.00 W 0.00 W 0.025 mS IRange VRange Fine Function Configure H 35A L 15V Dynamic TheCPCut Off Time function will turn the load off after a set-amount of time.
OPERATION Auto Load Configuration The PEL-3000 can be configured to automatically load the last program, normal sequence, fast sequence or load setting at startup. Description By default, this setting is disabled. Utility Operation 1. Press Shift + Help > Load[F2]. 2. Turn Auto Load On or Off. When set to OFF, the Auto Load setting is disabled. 3. Select the Auto Load On configuration.
PEL-3000 User Manual Load Off (Mode) and Load Off (Range) By default the load will automatically turn off when the either the operating mode (CC, CV, CR, CP) or the range (I range, V range) is changed. Description To allow the load to stay on when the operating mode is changed, set the Load Off (Mode) setting to OFF. To allow the load to stay on when the current or voltage range is changed, set the Load Off (Range) setting to OFF. By default, these settings are set to ON. Utility Operation 1.
OPERATION Step Resolution Configuration There are two different ways to set the set resolution when using the scroll wheel to edit parameters. Step Mode and Cursor Mode. Step Mode is the default method. Only one mode can be active at a time; When one mode is active, the other mode is deactivated. Cursor Mode Configuration Description Cursor mode allows you to edit the selected parameter one digit at a time. When editing a parameter, pressing the scroll wheel determines which digit is selected.
PEL-3000 User Manual Step Mode Configuration Description When set to Step Mode, the voltage, current, resistance and power settings can have the step resolution configured. The step resolution refers to the step resolution of the coarse adjustment for these settings. The fine adjustment cannot be configured. See the Conventions section on page 41 for details on how to switch between coarse and fine adjustment modes.
OPERATION Operation 1. Press Main > Configure[F5] > Next Menu[F4] > Knob[F2] and make sure the Status setting is set to Step. 2. Set the desired step resolution settings. (The step resolution settings are only available when Status=Step (coarse/fine)) Display For example if the step resolution for CCM Step is 0.5A, then the resolution can be incremented in 0.5A steps. RS232 LOAD 03/Sep/2012 Configure Status Step (coarse/fine) CCH Step 0.100 A CCM Step 0.0100 A CCL Step 0.00100 A CRH Step 40.
PEL-3000 User Manual Protection Settings The Protection settings are used to prevent damage to the unit or the DUT by excessive current, voltage or power. An alarm is generated and a message is displayed on the screen when a protection setting is tripped. When an alarm is activated, the load is turned off (or limited), and the ALARM STATUS pin of the J1 connector on the rear panel (pin 16) turns on (open collector output by a photocoupler).
OPERATION Display 03/Sep/2012 Alarm message when OCP is set to Load Off RS232 LOAD 2.596 V 1.2982 w OCP mA 500.06 OCP Alarm OCP indicator Please Press Enter CV A Value 15.000 V To Clear Alarm CV B Value 15.000 V Fine A Value Mode CV I Range L 0.7A V Range Response Configure L 15V Fast OPP For OPP, the PEL-3000 can be configured to either limit the power or turn off the load. Description The OPP levels can be set to 10% higher than the rating power. Operation 1.
PEL-3000 User Manual Display 03/Sep/2012 Alarm message when OPP is set to Load Off RS232 LOAD 2.596 V 1.2982 w OPP mA 500.06 OPP Alarm OCP indicator Please Press Enter CV A Value 15.000 V To Clear Alarm CV B Value 15.000 V Fine A Value Mode CV I Range L 0.7A V Range Response Configure L 15V Fast UVP If the UVP is tripped, the PEL-3000 will turn off the load. Description The UVP levels can be set from 0V to 10% higher than the rating voltage. Operation 1.
OPERATION Display 03/Sep/2012 Alarm message when UVP is tripped RS232 LOAD 2.596 V 1.2982 w UVP mA 500.06 UVP Alarm UVP indicator Please Press Enter CV A Value 15.000 V To Clear Alarm CV B Value 15.000 V Fine A Value Mode CV I Range L 0.7A V Range Response Configure L 15V Fast OVP If the OVP is tripped, the PEL-3000 will turn off the load. Description The OVP levels can be set from 0V to 10% higher than the rating voltage. Operation 1.
PEL-3000 User Manual Display RS232 LOAD 03/Sep/2012 Alarm message when OVP is tripped 2.596 V 1.2982 w OVP mA 500.06 OVP Alarm OVP indicator Please Press Enter CV A Value 15.000 V To Clear Alarm CV B Value 15.000 V Fine A Value Mode CV I Range L 0.7A V Range Response Configure L 15V Fast UnReg The UnReg error message will appear on the display when the electronic load is operating in an unregulated state.
OPERATION Para The Para error message will appear on the display when the PEL-3000 is used in parallel and if an error is produced. Description Alarm Display The Para error message indicates one of the following possible conditions: UnReg, R.OCP, OHP. To clear the Para indicator, remove the cause of the alarm. RS232 LOAD 03/Sep/2012 2.596 V 1.2982 w Para 500.06 mA Para indicator CV A Value CV B Value 15.000 V 15.000 V Fine A Value Mode CV I Range L 0.
PEL-3000 User Manual System Settings The following section covers a number or miscellaneous system settings such as: Speaker settings Display settings Alarm tone settings Input control settings Language settings All system settings are accessible in the Utility menu. Sound Settings Speaker Settings Turns the speaker sound on or off for the user interface, such as key press tones and scrolling tones. Description Utility Operation 1. Press Shift + Help > Other[F5]. 2.
OPERATION Alarm Tone Settings The alarm tone for the unit can be turned on or off in the utility menu. The alarm tone can be set separately for the protection settings (OCP, OPP, UVP, OVP), Go-NoGo testing or for when the unit is operating in an unregulated state (see page 84). Description Utility Operation 1. Press Shift + Help > Other[F5]. 2. Set the alarm tone settings on or off. The alarm tone settings ignore the Speaker setting.
PEL-3000 User Manual Control Settings The Knob Type setting determines if values are updated immediately as they are edited or if they are only updated after the Enter key is pressed. Description The Updated setting is applicable for when the load is already on and the user wishes to change the set values (current, voltage, etc.) in realtime. The Old setting will only update the values after the Enter key is pressed. Utility Operation 1. Press Shift + Help > Other[F5]. 2.
OPERATION Go-NoGo The Go-NoGo configuration is used to create pass/fail limits on the voltage or current input. If the voltage/current exceeds the pass/fail limits, an alarm will be output. The Go-NoGo configuration can be used with the Program function to create complex pass/fail tests. Setting the Go-NoGo Limits The Go-NoGo setting limits can be set as either discrete high & low values or as a percentage offset from a center value. Description Operation 1. Press Main > Configure[F5] > Go-NoGo[F3].
PEL-3000 User Manual 5. Set the Delay Time. The delay time setting will delay activating the Go-NoGo testing by a specified amount of time. The delay setting can compensate for startup oscillation and other instabilities during startup. Delay Time 0.0~1.0 seconds (0.1s resolution ) When the Main settings are saved or recalled, the Go-NoGo settings are also saved/recalled. See the Save/Recall chapter for details, page 119.
OPERATION Display: GO Display: NG RS232 LOAD 03/Sep/2012 0.000 V 0.00 w GO A test = ON 0.000 SPEC Test result Level1 Level2 Timer1 03/Sep/2012 0.00 W 0.00 W 0.025 mS RS232 SPEC Fine LOAD Test result V 0.00 w 0.000 NG A test = ON 0.000 SPEC Mode CP IRange H 35A Level1 Level2 Timer1 Mode CP VRange L 15V Function Dynamic 0.00 W 0.00 W 0.
PEL-3000 User Manual Program The PEL-3000 can create programs that are designed to stepthrough up to 16 pre-set load operations. The program function is a powerful tool that can allow you to perform a number of different operations in succession. The execution time of each step is user-defined. Programs can be chained together to make larger programs. Up to 16 programs can be created for a program chain. See page 119 for saving load operations.
OPERATION program chains. Program chains need not be executed in order. There are 16 steps to a program. There are up to 16 programs to a chain. PROGRAM 1 STEP 01 STEP 02 : STEP 16 PROGRAM 2 STEP 01 STEP 02 : STEP 16 PROGRAM 3 STEP 01 STEP 02 : STEP 16 A program contains the following settings for each step: Setting Overview Memory: the memory location of the load operation for the selected step (M001~M256). Run: Designates the run setting for the step (Auto, Manual, Skip).
PEL-3000 User Manual Below is a timing diagram of a single step in a program. Timing Diagram for Single Step P/F End Test Time (fixed) P/F Start Test Time (fixed) Start of Step 0.04s P/F Time 0.06s Short-Time On-Time Off-Time Step test time End of Step Create a Program Before creating a program, the settings for each step must first be created and saved to internal memory (M001~M256). See the save recall chapter for further details, page 119.
OPERATION PROG 01 ~ 16 3. Select a STEP in the selected program. STEP 01 ~ 16 4. Select Memory and select which memory location to load for the selected step. Settings loaded from the memory location will be used for the selected step. The same memory location can be used for multiple steps. Memory M001 ~ M256 5. Set the Run setting for the step. By default RUN is set to Skip. The Auto setting will automatically start and go onto the next step.
PEL-3000 User Manual 8. Choose the P/F-Time (pass/fail time) in seconds. The P/F-Time refers to the P/F delay time. This delay time includes the 0.06 P/F start test time, as shown in the timing diagram on page 94. P/F-Time Off, 0.0 ~ 119.9 seconds 9. Set the Short-Time in seconds. Has the same action as pressing the short key. See page 61 for details about shorting the load. Short-Time Off, 0.1 seconds ~ On-Time 10. Repeat steps 3 to 9 for all the steps in the program.
OPERATION Create a Program Chain Before creating a program chain, make sure a number of programs have already been saved. These will be used to create the program chain. Note Chain Setting Display Overview RS232 03/Sep/2012 Starting program for the chain Program Chain Set LOAD Start P01 P01 Off P02 Off P03 Off P04 Off Select Start Operation 1. Press Recall Default FUNC Previous Menu > Program[F1] > Chain[F1].
PEL-3000 User Manual 4. Repeat step 3 for any remaining programs in the chain. 5. Press Save to save the program chain to internal memory. Pressing Recall Default[F4] will reset the chain to the default settings. See page 178 for details. Recall Default[F4] will essentially clear the program chain. Running a Program or Chain A program or program chain is run the same way as a normal load. Description Operation 1. Press FUNC > Program[F1]. 2. Turn program mode on by setting Program[F1] to On.
OPERATION 5. When a program/chain has finished running, a list of the Go-NoGo results for each step are displayed. Display: Program/Chain Running Press Exit[F5] to exit. RS232 PROG 03/Sep/2012 0.000 V 0.000 A Run Program Program No: Step(Memory) Pause Next Step that is currently running. 0.00 w Program number that is currently running. 01 01(001) GO No-NoGo result for the step Memory number of current step.
PEL-3000 User Manual Sequence The PEL-3000 supports both programs and sequences. The essential difference between programs and sequences is that programs can use different operating modes for each step while sequences use the same operating mode throughout the whole sequence. In effect sequences are used to create complex load simulations. There are two different types of Sequences, Normal Sequences and Fast Sequences. Normal sequences can define the execution time and slew rate of each step.
OPERATION Start Sequence Sequence 1 Sequence 2 : : : : Sequence 10 Description STEP 01 STEP 02 : STEP N STEP 01 STEP 02 : STEP N STEP 01 STEP 02 : STEP N Normal Sequence configuration is split into Timing Edit configuration and Data Edit configuration. Timing Edit configuration is used to configure the actual sequences, such as mode, range, loops and chains. Data Edit configuration is used to create the actual steps used in each sequence. See below for a description of each.
PEL-3000 User Manual A user-created note for the currently selected sequence. Operating mode for the sequence. +CV mode is supported. Low I range, low V range Middle I range, low V range High I range, low V range Low I range, high V range Middle I range, high V range High I range, high V range Sets the amount of times to loop the selected sequence. Set the load condition after the end of the sequence. The setting value of the load for when Last Load = ON.
OPERATION RAMP ON, OFF When turned on the current transition is evenly ramped from the start of the step to the end of the step. When turned off the current transition is stepped. Ramp = On amplitude Time Step time Ramp = Off amplitude Time Step time TRIG OUT ON, OFF amplitude When TRIG OUT is set to ON, a trigger signal is output from the TRIG OUT BNC terminal at the start of the step. See page 150 for details.
PEL-3000 User Manual PAUSE Pause: Inserts a pause at the end of the step. When paused, the unit will pause at the end of the step current/voltage/resistance/ power level. The sequence can be resumed by pressing Next[F2] or by using an external trigger signal (page 147). ON, OFF Timing Edit Configuration Edit Timing Display Sequence number 03/Sep/2012 Start sequence RS232 LOAD Timing Edit for Normal Sequence Start S01 Seq.No: S01 Memo: Mode: Range: Loop: N. Seq.
OPERATION 4. Set the following parameters for the currently selected sequence. See page 100 for details on each parameter. Memo Mode Range Loop Last Load Last Chain 5. Press Save[F3] to save the timing settings for the currently selected sequence. Sequence Timing configuration is complete. Go to Data Edit to edit the steps used in the Normal Sequences. See page 106. Go to Running a Normal Sequence to run the normal sequence. See page 108.
PEL-3000 User Manual Data Edit Configuration Data Edit Display Total number of steps Active step number 03/Sep/2012 RS232 LOAD Data Edit for Normal Sequences Step: 0001 / 0001 Value: 0.00000 A Time: 000 H: 00 M: 00 S. 001ms LOAD: OFF TRIG OUT OFF RAMP: OFF PAUSE: OFF Insert Point Operation Step settings Delete Point Save Previous Menu 1. Press FUNC > Sequence[F2] > Normal Sequence[F1]. 2. Select Seq.No. and select the sequence you wish to edit. Start: S01 ~ S10 3.
OPERATION 5. Set the following parameters for the currently selected step. See the Data Edit Overview on page 102 for configuration details. Value Time LOAD RAMP TRIG OUT PAUSE 6. If you wish to edit a previously inserted point/step, use the Step parameter. Steps can only be selected after they have already been inserted. Steps 0001 ~ 1000 7. The currently selected step can be deleted using the Delete Point[F2] function. 8.
PEL-3000 User Manual Running a Normal Sequence A load created with the Normal Sequence function is run the same way as a normal load. Description Operation 1. Press [F1]. FUNC > Sequence[F1] > Normal Sequence 2. Turn normal sequence mode on by setting N. Seq.[F1] to On. will appear at the top of the display when N. Seq. is On. NSEQ 3. Turn the load on. The normal sequence/chain starts immediately. The NSEQ icon turns orange when the load is turned on. 4.
OPERATION Display: Sequence/Chain Running RS232 NSEQ 03/Sep/2012 0.000 V 0.000 A Run N.Seq. Seq. No: Step Loop: 0.
PEL-3000 User Manual Fast Sequence Overview A fast sequence is comprised of a user-defined number of steps that can be executed at a high frequency. Unlike normal sequences, each step in a fast sequence has the same execution time (time base). Description This mode is only available for CC and CR mode. Up to 1000 discrete steps can be configured using fast sequences. Each fast sequence can have a memo note attached to it.
OPERATION Description Fast Sequence configuration is split into Timing Edit configuration and Data Edit configuration. Timing Edit configuration is used to configure all the settings that are common to all the steps of the fast sequence. This includes settings such as the mode, range, loops and time base. Data Edit configuration is used to create the actual steps used in each sequence. See below for a description of each.
PEL-3000 User Manual Data Edit Overview Each step in a fast sequence contains the following setting parameters: Setting Step Setting Range 0001 ~ 1000 Description Selects/displays the current step in the sequence. The number of available steps is dependent on the number of steps added using the Ins. Point[F1] functions. A minimum of 3 steps. The current or resistance setting for the selected operating mode.
OPERATION range. FILL example Value setting End_Value Filled values Start_Value Step Step Step Step 02 03 4 01 Step Start_Step Filled steps End_Step Setting Start_Value Setting Range End_Value Start_Step 0001 ~ 1000 End_Step 0001 ~ 1000 Description Sets the current or resistance value for the starting step. Sets the current or resistance value for the ending step. Sets the starting step number. Sets the ending step number.
PEL-3000 User Manual Timing Edit Configuration Edit Timing Display RS232 LOAD 03/Sep/2012 Timing Edit for Fast Sequence Memo: 001 Mode: CC Last Load: OFF Range: ILVL Last 0.00000 A Loop: Infinity RPTSTEP 0004 Time Base: 600.00 ms F. Seq. Off Operation Edit Sequence Sequence settings Previous Menu 1. Press FUNC > Sequence[F2] > Fast Sequence[F2]. Note that F. Seq.[F1] is off by default. 2. Set the following parameters for the fast sequence. See page 112 for details on each parameter.
OPERATION Sequence Timing configuration is complete. Go to Data Edit to edit the steps used in the Fast Sequence. Page 115. Go to Running a Fast Sequence to run the fast sequence. Page 117. Data Edit Configuration Data Edit Display Total number of steps Active step number 03/Sep/2012 RS232 LOAD Data Edit for Fast Sequences Step: 0001 / 0005 Value: 0.
PEL-3000 User Manual 2. Press Insert Point[F1] to add a step to the sequence. Every-time Insert Point is pressed the Step parameter is incremented. The newly inserted ―point‖ becomes the active step. 3. Set the following parameters for the currently selected step. See page 115 for configuration details. Value TRIG OUT 4. If you wish to edit a previously added point/step, use the Steps parameter. Steps can only be selected after they have already been added. Steps 0001 ~ 1000(RPTSTEP) 5.
OPERATION After all the steps for the sequence are complete, press Save[F3] to save the steps. Save Data Edit for Fast Sequences configuration is complete. Go to Timing Edit for Fast Sequences to edit the sequence. Page 114. Go to Running a Fast Sequence to run the fast sequence. Page 117. Running a Fast Sequence A Fast Sequence is run the same way as a normal load. Description Operation 1. Press FUNC > Sequence[F2] > Fast Sequence[F2]. 2. Turn fast sequence mode on by setting F. Seq.
PEL-3000 User Manual Display: Fast Sequence Running RS232 FSEQ 03/Sep/2012 0.998 V 0.1528 w mA 153.10 Current step number Run F.Seq.
OPERATION Save Recall The PEL-3000 can save and recall system settings, preset data, memory data, Go-NoGo settings as well as normal and fast sequences to internal memory or to USB. File Structure Description The PEL-3000 file system can save files to internal memory (Media|Memory) and external memory (Media|USB). To save or recall Memory, Setup or Preset data, the PEL-3000 uses a three tier system where files are saved or recalled in the following order: Active settings <> Internal memory <> USB.
PEL-3000 User Manual For example: To load Preset Data P7 from USB, you must first load Preset Data P0~P9 to internal memory, then from internal memory load Preset P7 to be the active preset setting. For normal and fast sequences however, files can be saved or recalled directly to/from USB memory. File Types Memory Data Memory data contains general settings and is used for creating programs. Memory Data contains the operating mode, range, response and Go/NoGo settings.
OPERATION Preset Data Preset Data contains the same settings as the Memory Data. Preset Data contains the operating mode, range, response and Go-NoGo settings. Internal Format P0 ~ P9 External Format model no_file no.P example: 3021_00.P NSeq Data NSeq Data contains the Normal Sequence settings. Internal Format None External Format model no_file no.N example: 3021_00.N FSeq Data FSeq Data contains the Fast Sequence settings. Internal Format None External Format model no_file no.F example: 3021_00.
PEL-3000 User Manual Memory Data Example Media | Memory M001 : MXXX : M256 Active setting Display RS232 LOAD 03/Sep/2012 Save fileCC type Data Type Memory Memory M256 0.35A 15V Static Save file location Memory Media Memory Save Recall A Value File Utility File Operation 1. Press Shift + FUNC . 2. Select Memory with the Media[F1] soft-key. 3. Select the Data Type and choose the type of file to save. Data Type: Memory Data, Setup Data, Preset Data 4.
OPERATION Note Normal Sequence and Fast Sequence data cannot be recalled from or saved to an internal memory slot. Saving Files to USB Memory Description Memory Data Example When saving files to USB memory, all the memory locations from the selected data type are saved as a single file to the USB file path directory. Media | Memory Media | USB M001 : MXXX : M256 Save file For example, Memory Data M001 to M256 are saved to a single file on USB.
PEL-3000 User Manual Operation 1. Insert a USB drive into the USB port. File 2. Press Shift + FUNC . 3. Select USB with the Media[F1] soft-key. 4. Select the Data Type and choose the type of file to save. Data Type: Memory Data, Setup Data, Preset Data, NSeq, FSeq 5. Select Save File and choose a save filename. Turn the scroll wheel to increase/decrease the file number. Memory: Model_file number.M Setup Memory: Model_file number.S Preset: Model_file number.P NSeq: Model_file number.
OPERATION Recalling Files from Internal Memory Description When recalling Memory, Setup or Preset Data from the internal memory slots, the recalled file becomes the active setting. Memory Data has 256 memory slots, Setup Data has 100 memory slots and Preset Data has 10 memory slots. Memory Data Example Media | Memory M001 : MXXX : M256 Active setting Display RS232 LOAD 03/Sep/2012 Save fileCC type Data Type Memory Memory M256 0.
PEL-3000 User Manual 4. Select which memory slot to recall from. Memory: M001 ~ M256 Setup Memory: 1 ~ 100 Preset: P0 ~ P9 5. Press Recall[F4] to recall. Note For Memory Data and Preset Data, a popup window will appear. Press the Enter key to confirm the recall. Normal Sequence and Fast Sequence data cannot be recalled from or saved to an internal memory slot. They can, however, be recalled directly from USB memory. See the next section below for details.
OPERATION Memory Data Example Media | Memory Media | USB Recall file M001 : MXXX : M256 For example, if the file 3021_01.M is recalled, all the Memory Data from M001 to M256 will be overwritten. Display RS232 LOAD 03/Sep/2012 Save fileCC type Data Type Memory 15V Static Save File Recall File Path: usb: 3021_01.M 3021_02.M Save file name USB USB file path Media USB Operation 0.35A Save Recall A Value File Utility 1. Insert a USB drive into the USB port. File 2. Press Shift + FUNC .
PEL-3000 User Manual Memory: Setup Memory: Preset: NSeq: FSeq: Model_file number.M Model_file number.S Model_file number.P Model_file number.N Model_file number.F 6. Press Recall[F4] to recall. Press File Utility[F5] to access the file utility. See page 128 for details. File Utilities Caution Recall Ok will be displayed when the recall has been completed. Change the USB path. Rename files or create directories.
OPERATION This setting only applies when recalling preset settings from internal memory, either by using the Presets keys (P0 ~ P9) or by using the File menu. See page 131 and 125. Note File Utility The file utility allows you to create new folders, rename files and set the USB path directory. Description It is only available for use with the USB external memory. Display 03/Sep/2012 RS232 LOAD USB path cursor Path: usb:\Test Folder1 Folder2 16-Feb-12 13:46 18-Feb-12 11:16 Folder3 19-Feb-12 08:32
PEL-3000 User Manual Rename a Folder 1. Use the scroll wheel to move the cursor to the file/folder you wish to rename. 2. Press Rename[F3]. Delete File or Folder Use the on-screen display to enter the filename. A maximum of 8 characters. 1. Use the scroll wheel to move the cursor to the file/folder you wish to delete. 2. Press Delete[F4]. 3. Press Delete[F4] again to confirm the deletion. Preset The Preset key is used to save and recall preset settings from the front panel quickly.
OPERATION Quick Preset Recall Presets P0 to P9 can be recalled quickly by using the Preset key and the number pad. Description P0 Operation 1. Press Preset + 0 P9 ~ 9 . 2. Press Enter to confirm the recall when a popup window appears. 3. Press key. Preset again to deactivate the preset Default Settings Factory Default Settings Description The factory default settings can be recalled at any time. See page 178 for a list of the factory default settings. File Operation 1.
PEL-3000 User Manual User’s Default Setting The currently active settings can be set as the ―User’s Default‖ settings. Description File Save User’s Default Setting 1. Press Shift + FUNC . 2. Select Default with the Media[F1] soft-key. 3. Press Save[F3]. The User’s Default is saved immediately. File Recall User’s Default Setting 1. Press Shift + FUNC . 2. Select Default with the Media[F1] soft-key. 3. Press Recall[F4]. 4. Press Recall[F4] again to confirm.
EXTERNAL CONTROL EXTERNAL CONTROL Analog Control ............................................................... 134 J1 Connector Overview ........................................................................................ 134 External Voltage Control - Overview ................................................................. 135 External Voltage Control – Operation .................................................. 136 External Resistance Control - Overview .........................................
PEL-3000 User Manual Analog Control The Analog Control subsection describes how to use the J1 Frame Control Connector for voltage or resistance control. The J2 connector, located under the J1 connector is used for parallel control. See page 181 for the details J1 and J2 connectors. J1 Connector Overview Description The J1 External Control Connector is a standard Mil 20 pin connector (OMRON XG4A IDC plug). The connector is used for all analog control. The pins are used to determine what mode is used.
EXTERNAL CONTROL External Voltage Control - Overview Background External voltage control of the CC, CR, CV and CP mode is accomplished using the J1 connector on the rear panel. An input voltage of 0~10V corresponds to 0% ~ 100% of the rated current (CC mode), rated voltage (CV mode), or rated power (CP mode). For CR mode, 0V ~ 10V corresponds to the maximum resistance ~ minimum resistance.
PEL-3000 User Manual Caution When using external voltage control, make sure no more than ±11V is applied across pins 1 and 3. Exceeding this voltage could damage the PEL-3000. Exceeding 11.8V will cause an EXT.OV alarm message to appear which also will reset the voltage output to 0V until the external voltage is reduced back down below 11.8V. Use caution when using pin 3. Pin 3 is directly coupled to the negative input terminal.
EXTERNAL CONTROL CR Mode Input conductance = rated conductance × (external voltage/10) Input Conductance Rated Conductance 0V CV Mode 10V External Voltage Input voltage = rated voltage × (external voltage/10) Input Voltage Rated Voltage 0V CP Mode 10V External Voltage Input power = rated power × (external voltage/10) Input Power Rated Power 0V Operation 10V External Voltage 1. Turn the power off from the PEL-3000 and from the load. 2.
PEL-3000 User Manual 3. Turn the power on the PEL-3000. 4. Set the operating mode and range. See page 51 for CC mode. See page 53 for CR mode. See page 55 for CV mode. See page 56 for CP mode. 5. Press Main > Configure [F5] > Next Menu [F4] > External [F3]. 6. Set the Control parameter to V. The J1 connector is now ready for external voltage control.
EXTERNAL CONTROL Connection When connecting the external resistance source to the J1 connector, use a ferrite core and use twisted pair wiring. EXT-R PEL-3000 1 J1 connector 3 Ferrite Core and twisted wiring Input Terminals Pin1 → EXT-R Pin3 → EXT-R Note Use resistors with minimum residual resistance of 50Ω or less. Note for proportional control: Do not use swtiches that switch between fixed resistances. Please use continuously variable resistors.
PEL-3000 User Manual External Resistance Control – Operation Description External resistance control can be used to control the current, voltage, resistance and power for CC, CR, CV and CP modes. Configuration for each operating mode is the same. CC Mode Proportional Control: Input current = rated current × (external resistance/10). Inverse Control: Input current = rated current × (1 - external resistance/10).
EXTERNAL CONTROL CR Mode Proportional Control: Input conductance = rated conductance × (external resistance/10). Inverse Control: Input conductance = rated conductance × (1 - external resistance/10). Inverse control Input Conductance Proportional control Rated Conductance 0Ω CV Mode External Resistance 10kΩ Proportional Control: Input voltage = rated voltage × (external resistance/10). Inverse Control: Input voltage = rated voltage × (1 - external resistance/10).
PEL-3000 User Manual Proportional Control: Input power = rated power × (external resistance/10). CP Mode Inverse Control: Input power = rated power × (1 - external resistance/10). Input Power Inverse control Proportional control Rated Power 0Ω The inverse configuration is recommended for safety reasons. In the event that any of the cables become accidentaly disconnected, the current/voltage/power input will drop to the minimum.
EXTERNAL CONTROL 5. Press Main > Configure [F5] > Next Menu [F4] > External [F3]. 6. Set the Control to R for proportional control or to Rinv for inverse control. The J1 connector is now ready for external resistance control. Turning the Load On using External Control Description The load can be turned on and off with an external switch connected to pins 7 and 12 of the J1 connector. Pin Inputs Pin 7 of the J1 connector is internally pulled up to 5V with a 10kΩ resistor when the switch is open.
PEL-3000 User Manual The LoadOn IN setting determines whether the load is turned on when the external switch is closed (low) or open (high). Example High LoadOn In = High Low High LoadOn In = Low Low On Load off Load Off Load on Operation: Configuration Note 144 1. Press Main > Configure [F5] > Next Menu [F4] > External [F3] and set the LoadOn IN setting. Set to Low if you want the load to be turned on when the switch is closed.
EXTERNAL CONTROL Load On/Off Status Description Pin 13 (Load On Status) of the J1 connector is used to monitor the load status (on or off). Pin out The Load On Status pin is a photocoupled opencollector output. 13 17 Photocoupler input: 30V max, 8mA, max. External Control of the Range Description The range for the present operating mode can be externally controlled when the current range is set to high range. The range is changed using pins 8, 9 (Range Cont 1 &2) and 12 (A Com) of the J1 connector.
PEL-3000 User Manual Pin Inputs Pins 8 and 9 of the J1 connector are internally pulled up to 5V with a 10kΩ resistor when open. When closed, pin 8 and 9 are pulled down to the A COM ground level. PEL-3000 +5V Switches 10kΩ 8 9 Analog connector 12 A COM Note The range can only be externally controlled when the IRange has been set to High using the front panel controls. I Range Status Description Pins 14 and 15 (Range Status 1&2) of the J1 connector are used to monitor the IRange status.
EXTERNAL CONTROL Pin out The Range Status pins are photocoupled opencollector outputs. 14, 15 17 Photocoupler input: 30V max, 8mA, max. External Trigger Signal Description Pins 11 and 12 of the J1 connector are the trigger signal inputs. The trigger signal is used to resume a sequence after a pause. This action is useful to synchronize the execution of a sequence with another device. Pin out Pin 11 of the J1 connector is internally pulled down to A COM with an approx. 50kΩ resistor.
PEL-3000 User Manual External Control of the Alarm Description An alarm can be activated/deactivated using external control with the J1 connector (pins 10, 12). When the alarm is activated, an EXT.AL message is also output. The alarm can be activated by an external device or by a parallel slave unit. The alarm is activated by sending a low-level signal. The operating threshold level is TTL. Pin Inputs Pin 10 is internally pulled up to 5V with a 10kΩ resistor when open.
EXTERNAL CONTROL Alarm Status Description Pins 16 and 17 of the J1 connector are used to monitor whether the alarm is on or off. Pin out The Alarm Status pin is a photo-coupled open-collector output. 16 17 Photocoupler input: 30V max, 8mA, max. Short Control Description The Short Signal Out pins (19 and 20) are 30VDC 1A relay contact outputs. These outputs can be used to drive an external relay to physically short the terminal outputs.
PEL-3000 User Manual Monitor Signal Output Trigger Signal Output Description The trigger output signal is generated every time a switching operation is performed (i.e., Dynamic mode) or when a Fast or Normal Sequence is executed and the TRIG OUT parameter is enabled. The trigger output signal from TRIG OUT BNC is a 5V pulse of at least 2us with an impedance of 500Ω. The common potential is connected to the chassis potential. The signal threshold level is TTL.
EXTERNAL CONTROL settings. Current Rated Current IMON V Monitor Output Range Monitor Connector Current Range I MON OUT (BNC) I MON (J1) H, L M H, L M Monitor Output Range 0 ~ 1V 0 ~ 0.1V 0 ~ 10V 0 ~ 1V I MON OUT BNC Connector The IMON OUT BNC connector outputs a voltage of 0 ~ 1V for the High and Low current ranges and 0 ~ 0.1V for the Middle current range. The common potential is connected to the chassis ground potential.
PEL-3000 User Manual Parallel Operation The PEL-3000 series can be connected in parallel to increase the total power capacity of a single unit. The PEL-3000 series can operate with up to 5 units in parallel. A single unit is designated as a master unit and any other connected units as slaves. Only units of the same type and rating can be used in parallel or alternatively, the PEL-3211 booster pack can be used as a slave with the PEL-3111.
EXTERNAL CONTROL Parallel Capacity, PEL-3211 Model No. of Units V I Total Sink Current PEL-3111 + PEL-3211 Total Power PEL-3111 + PEL-3211 PEL-3111: Master x1 150V 210A N/A N/A x1 150V 420A 630A 3150W x2 150V 840A 1050A 5250W x3 150V 1260A 1470A 7350W PEL-3211: Slave Boosters x 4 150V 1680A 1890A 9450W Note: The PEL-3211 booster packs do not have a control panel. They can only be used as slaves with a single PEL-3111 in parallel.
DUT + SLAVE 1 J1 + J2 -S +S SLAVE 2 J1 + J2 -S +S SLAVE 3 J1 + J2 -S +S Cautions Frame link cable (GTL-255) Sense wiring No ferrite core to last J1 connection Load wiring MASTER J1 + J2 -S +S Ferrite cores PEL-3000 User Manual Only the rear terminals can be used for parallel connections. Make sure all connections are correct before turning on the load. Incorrect connections could damage the units.
EXTERNAL CONTROL Configuration When using the multiple units in parallel all the basic settings are adopted from the master unit. Description Operation 1. Make sure all load units are turned off. 2. Make sure the DUT is turned off. 3. Connect the load units to the DUT. Ensure the wire gauge is sufficient to handle the increase in current 4. Connect the Master unit to the slave units via the J1/J2 connectors*.
PEL-3000 User Manual A maximum of 5 units can be used in parallel. A maximum of 4 boosters can be used with a single PEL-3111, acting as a master unit. RS232 LOAD 03/Sep/2012 Configure Operation Master CV 35A 15V Fast Parallel Booster Parallel 3 OFF Knob External A Value Previous Menu 9. On the slave units, press Main > Configure [F5] > Next Menu [F4] > Parallel[F1] > and set Operation to Slave. When in Slave mode, all keys are locked, except for the Scroll wheel and Enter key.
EXTERNAL CONTROL Turning the Load On Operating the PEL-3000 Series in parallel mode is the same as for single units. Description When using the units in parallel, the load line inductance could be increased or the stability of the units could be reduced. It may be necessary to reduce the response speed setting to increase stability. Note 1. Turn the slave and master units on. 2. Set the operation mode and settings on the master unit. The master’s settings will be used by the slave units. 3.
PEL-3000 User Manual Disable Parallel Mode Description Operation To disable parallel mode, each unit must be set as a ―Master‖. 1. Turn the power off on all the units and remove the GTL-255 frame link cables. 2. Turn the power back. 3. On each unit, press Main > Configure [F5] > Next Menu [F4] > Parallel[F1]. 4. Set the unit to Master with the Operation setting. 5. Turn the Parallel and Booster settings to Off.
REMOTE CONTROL REMOTE CONTROL This chapter describes basic configuration of IEEE488.2 based remote control. For a command list, refer to the programming manual, downloadable from GW Instek website, www.gwinstek.com Interface Configuration .................................................. 160 Configure to USB Remote Interface ................................................................... 160 Configure GPIB Interface ....................................................................................
PEL-3000 User Manual Interface Configuration Configure to USB Remote Interface USB configuration Note Operation PC side connector Type A, host PEL-3000 side connector Rear panel Type B, slave Speed 2.0 (full speed) USB Class USB CDC ACM Before USB can be used for remote control, it is necessary to install the PEL-3000 USB device driver, located on the accompanying User Manual CD. 1. Connect the USB cable to the rear panel USB B port. Utility 2.
REMOTE CONTROL 2. Connect a GPIB cable from a GPIB controller to the GPIB port on the PEL-3000. 3. Turn the PEL-3000 on. Utility 4. Press Shift + Help > Interface[F3] and set the Interface setting to GPIB. 5. Set the GPIB address.
PEL-3000 User Manual Configure RS232C RS232C Configuration Operation Connector DB-9, Male Baud Rate 2400, 4800, 9600, 19200, 38400 Stop Bit 1, 2 Parity None, Odd, Even 1. Connect an RS232C cable from the PC to the rear panel RS232 port. Utility 2. Press + > Interface[F3] and set the Interface setting to RS232. Shift Help 3. Set the Baud Rate, Stop Bit and Parity settings.
REMOTE CONTROL RS232C/USB Remote Control Function Check Functionality check Invoke a terminal application such as Realterm. For RS-232C, set the COM port, baud rate, stop bit, data bit and parity accordingly. To check the COM settings in Windows, see the Device Manager. For example, in WinXP go to the Control panel → System → Hardware tab.
PEL-3000 User Manual Using Realterm to Establish a Remote Connection Background Realterm is a terminal program that can be used to communicate with a device attached to the serial port of a PC or via an emulated serial port via USB. The following instructions apply to version 1.99.0.27. Even though Realterm is used as an example to establish a remote connection, any terminal program can be used that has similar functionality. Note Realterm can be downloaded on Sourceforge.net free of charge.
REMOTE CONTROL If using USB, the baud rate, stop bit and parity settings can be viewed by right-clicking connected device and selecting the Properties option. 5. Start Realterm on the PC as an administrator. Click: Start menu>All Programs>RealTerm>realterm Tip: to run as an administrator, you can right click the Realterm icon in the Windows Start menu and select the Run as Administrator option.
PEL-3000 User Manual 6. After Realterm has started, click on the Port tab. Enter the Baud, Parity, Data bits, Stop bits and Port number configuration for the connection. The Hardware Flow Control, Software Flow Control options can be left at the default settings. Press Open to connect to the PEL-3000.
REMOTE CONTROL 7. Click on the Send tab. In the EOL configuration, check on the +CR and +LF check boxes. Enter the query: *idn? Click on Send ASCII. 8. The terminal display will return the following: GW, PEL-3XXX,EXXXXXXX,VX.XX.XXX (manufacturer, model, serial number, version) 9. If Realterm fails to connect to the PEL-3000, please check all the cables and settings and try again.
PEL-3000 User Manual GPIB Function Check Functionality check Please use the National Instruments Measurement & Automation Controller software to confirm GPIB/LAN functionality. See the National Instrument website, http://www.ni.com for details. Note Operation For further details, please see the programming manual, available on the GW Instek web site @ www.gwinstek.com. 1. Start the NI Measurement and Automation Explorer (MAX) program.
REMOTE CONTROL 3. Press the Scan for Instruments button. 4. In the Connected Instruments panel the PEL-3000 should be detected as Instrument 0 with the address the same as that configured on the PEL-3000. 5. Double click the Instrument 0 icon. 3 2 4 5 6. Click on Communicate with Instrument. 7. In the NI-488.2 Communicator window, ensure *IND? is written in the Send String: text box. Click on the Query button to send the *IDN? query to the instrument. 8.
PEL-3000 User Manual 6 7 8 9. The function check is complete.
FAQ FAQ • The load voltage indicated on the load module is below expected. • The front panel keys are not working. • The load won’t turn on. • The performance does not match the specification The load voltage indicated on the load module is below expected. Ensure the load leads are as short as possible, twisted and use the appropriate wire gauge. Ensure that voltage sense is used, this can help alleviate the voltage drop across the load the leads. The front panel keys are not working.
PEL-3000 User Manual For more information, contact your local dealer or GWInstek at www.gwinstek.com / marketing@goodwill.com.
APPENDIX APPENDIX Replacing the Dust Filter ................................................ 175 Replace the Clock Battery ............................................... 176 GPIB Installation ............................................................ 177 PEL-3000 Default Settings .............................................. 178 Frame Control Connector Contacts ................................. 181 Operating Mode Description .......................................... 186 CC Mode ......................
PEL-3000 User Manual Other ....................................................................................................................... 204 Analog External Control....................................................................................... 204 Front Panel BNC Connector ............................................................................... 206 PEL-3000 Dimensions .................................................... 207 PEL-3111 ................................................
APPENDIX Replacing the Dust Filter Background Procedure The dust filter should be replaced twice a year. Not replacing the filter will reduce performance and may cause the PEL-3000 to malfunction. 1. Turn the PEL-3000 off completely at the rear panel power switch. Gently lift the grill up from the bottom. 2. Remove the filter from the grill and replace with GW Instek part number: PEL-010.
PEL-3000 User Manual Replace the Clock Battery The system clock keeps time using a userreplaceable battery. Background The battery should be replaced approximately every 3 years. Battery type: Procedure CR123A 1. Turn off the PEL-3000 and remove the case. First remove the handle by carefully removing the plastic tabs and then unscrewing the two screws connecting the handle to the case. A total of 10 screws should be removed from the case. 2.
APPENDIX GPIB Installation Background Procedure GPIB is an optional extra. The following instructions describe how to install the optional GPIB card if necessary. 1. Turn off the PEL-3000. 2. Remove the two screws holding the cover on the option bay. 3. Slide the GPIB card onto the rails in the option bay. 4. Re-screw the screws back into place.
PEL-3000 User Manual PEL-3000 Default Settings The following default settings are the factory configuration settings for the PEL-3000.
APPENDIX Main > Configure > Other Item Panel Settings Soft Start OFF Von Voltage 0.00V Von Latch ON Von Delay 2.0 ms Short Key Toggle Count Time(elapsed OFF time display) Cut Off Time OFF Response 1/1 Mem.Recall Safety Dyna. Level Value Dyna. Time T1/T2 CR Unit mS Main > Configure > Go-NoGo Item Panel Settings SPEC. Test Delay Time Entry Mode OFF 0.
PEL-3000 User Manual Main > Configure > Next Menu > Knob Item Panel Settings Status Step CCH Step Resolution CCM Step Resolution CCL Step Resolution CRH Step Resolution CRM Step Resolution CRL Step Resolution CVH Step Resolution CVL Step Resolution CPH Step Resolution CPM Step Resolution CPL Step Resolution Main > Configure > Next Menu > External Item Panel Settings Control LoadOn IN OFF OFF 180 Setup Memory Settings (all 100 sets) Step Resolution Resolution Resolution Resolution Resolution Resolutio
APPENDIX Frame Control Connector Contacts J1 Connector Pin name EXT R/V CONT Pin number Description 1 Used for voltage/resistance control of CC, CR, CV and CP mode. 0V to 10V corresponds to 0% to 100% of the rated current (CC mode), rated voltage (CV mode), or rated power (CP mode).
PEL-3000 User Manual TRIG INPUT 11 When paused, clears the pause when a low level TTL signal is applied for 10 μs or longer. Pulled down the internal circuit to A COM using approx. 50kΩ. A COM 12 Connected to the negative load input terminal on the rear panel. LOAD ON 13 Turns on when load is on. Open collector output by STATUS a photocoupler.*4 RANGE STATUS 1 14 Range status output. Open collector output by a RANGE STATUS 0 15 photocoupler.
APPENDIX J2 Connector Pin name N.C. N.C. N.C. SUM I MON PRL OUT+ PRL OUTLOAD ON/OFF CONT N.C. SLAVE RANGE CONT N.C. N.C. A COM N.C. N.C. N.C. ALARM INPUT A COM N.C. N.C. +15V Pin number Description 1 2 3 4 Connect to SUM I MON of the J1 connector. 5 Used during master/slave operation. Connected to PRL IN+ of the J1 connector. 6 Used during master/slave operation. Connected to PRL IN- of the J1 connector. 7 8 9 Used during master/slave operation. Connected to RANGE CONT 0 of the J1 connector.
PEL-3000 User Manual SUM I MON PRL IN+ PRL INLOAD ON/OFF CONT N.C. RANGE CONT 0 N.C. N.C. A COM ALARM STATUS STATUS COM N.C. A COM +15V 4 5 6 7 Connected to SUM I MON of the J2 connector. Connected to PRL OUT+ of the J2 connector. Connected to PRL OUT- of the J2 connector. "Turns on the load with low (or high) TTL level signal. 8 Pulled up the internal circuit to 5 V using 10 kΩ." 9 "External range switch input*1 *2 Pulled up the internal circuit to 5 V using 10 kΩ.
APPENDIX J2 Connector Booster Pin name N.C. N.C. N.C. SUM I MON PRL OUT+ PRL OUTLOAD ON/OFF CONT N.C. SLAVE RANGE CONT N.C. N.C. A COM N.C. N.C. N.C. ALARM INPUT A COM N.C. A COM +15V Pin number Description 1 2 3 4 Connect to SUM I MON of the J1 connector. 5 Used during master/slave operation. Connected to PRL IN+ of the J1 connector. 6 Used during master/slave operation. Connected to PRL IN- of the J1 connector. 7 8 9 Used during master/slave operation. Connected to RANGE CONT 0 of the J1 connector.
PEL-3000 User Manual Operating Mode Description CC Mode CC Mode When the unit is set to CC mode it will operate as a constant current load when connected to a constant voltage source. This means the unit will sink a designated amount of current, up to the rated power level, regardless of the voltage. This is illustrated below.
APPENDIX CC + CV Mode Load Input Voltage CC Current Value CV level Load Current Note that when the source voltage is less than the CV level, no current will flow due to a very high impedance. CR Mode CR Mode When the unit is set to CR mode it will operate as a constant resistance load when connected to a constant voltage source. This means the unit will maintain a set resistance, up to the rated power, regardless of the input voltage.
PEL-3000 User Manual CR+CV Mode When CR+CV mode is enabled, the unit will act as constant resistive load after the input voltage is greater than the user-defined CV level. At the CV level, the unit works as a constant voltage load. This mode effectively creates a voltage ceiling before the unit operates in CR mode. The diagram below illustrates this.
APPENDIX CP Mode Load Input Voltage CP Value Load Current CP+CV Mode When CP+CV mode is enabled, the unit will act as a constant power load after the input voltage is greater than the user-defined CV level. At the CV level, the unit works as a constant voltage load. This mode effectively creates a voltage ceiling before the unit operates in CP mode. The diagram below illustrates this.
PEL-3000 User Manual CV Mode CV Mode When the unit is set to CV mode it will operate as a constant voltage load when connected to a constant current source. This means the unit will maintain a set voltage level, up to the rated power, regardless of the input current. When the source voltage is less than the CV level, no current will flow due to a very high impedance. This is illustrated below.
APPENDIX Operating Area PEL-3021 191
PEL-3000 User Manual PEL-3041 192
APPENDIX PEL-3111 193
PEL-3000 User Manual PEL-3211 Booster Pack 194
APPENDIX PEL-3000 Specifications The specifications apply when the PEL-3000 is powered on for at least 30 minutes to warm-up to a temperature of 20˚C to 30˚C, unless specified otherwise. All specifications apply when using the rear panel terminals. If the front panel terminals are used or if operating with long cables, remote sense must be connected to the terminals. In parallel mode: All operation/settings/resolution specifications are xN. This does not include voltage settings and measured values.
PEL-3000 User Manual CC Mode Model PEL-3021 PEL-3041 PEL-3111 Operating Range H Range 0A~35A 0A~70A 0A~210A M Range 0A~3.5A 0A~7A 0A~21A L Range 0A~0.35A 0A~0.7A 0A~2.1A Setting Range H Range 0A~35.7A 0A~71.4A 0A~214.2A M Range 0A~3.57A 0A~7.14A 0A~21.42A L Range 0A~0.357A 0A~0.714A 0A~2.142A Default Setting H Range 0A 0A 0A M Range 0A 0A 0A L Range 0A 0A 0A Resolution H Range 1mA 2mA 10mA M Range 0.1mA 0.2mA 1mA L Range 0.01mA 0.02mA 0.1mA Accuracy of Setting H, M Range ±(0.2 % of set + 0.1 % of f.
APPENDIX CR Mode Model PEL-3021 Operating Range*1 H Range 23.3336S~400uS (42.857mΩ~2.5kΩ) M Range L Range 2.33336S~40uS (428.566mΩ~25kΩ) 0.233336S~4uS (4.28566Ω~250kΩ) PEL-3041 PEL-3111 140.0016S~2.4mS 46.6672S~800uS (7.1427mΩ (21.428mΩ~1.25kΩ) ~416.6667Ω) 14.0001S~242.4uS 4.6667S~80uS (71.427mΩ~ (214.28mΩ~12.5kΩ) 4.16667kΩ) 1.40001S~24.24uS 0.46667S~8uS (714.27mΩ (2.1428Ω~125kΩ) ~41.6667kΩ) Setting Range H Range 24.5S~0S 49.0S~0 S 147.000S~0S (40.8163 mΩ~OPEN) (20.408 mΩ~OPEN) (6.
PEL-3000 User Manual Setting Range H Range M Range Resolution H Range M Range Accuracy of Setting*1 H, L Range Input current variation*2 0V~157.5V 0V~15.75V 10mV 1mV ±(0.1 % of set + 0.1 % of f.s) 12mV *1 At the sensing point during remote sensing under the operating range of the input voltage. It is also applied for the condition of the parallel operation. *2 With respect to a change in the current of 10 % to 100 % of the rating at an input voltage of 1.5 V (during remote sensing).
APPENDIX Slew Rate Model PEL-3021 Setting Range (CC Mode) H Range 2.5mA/us~2.5A/us M Range 250uA/us~250mA/us L Range 25uA/us~25mA/us Setting Range (CR Mode) H Range 250uA/us~250mA/us M Range 25uA/us~25mA/us L Range 2.5uA/us~2.5mA/us Resolution Resolution 1mA Setting 250mA/us~2.5A/us Resolution 100uA Setting 25mA/us~250mA/us Resolution 10uA Setting 2.5mA/us~25mA/us Resolution 1uA Setting 250uA/us~2.5mA/us Resolution 100nA Setting 25uA/us~250uA/us Resolution 10nA Setting 2.
PEL-3000 User Manual Ammeter H, M Range 0.000A~35.000A 0.000A~70.000A 0.00A~210.00A L Range 0.00mA~350.00mA 0.00mA~700.00mA 0.0mA~2100.0mA Accuracy ±(0.2 % of rdg + 0.3 % of f.s) Accuracy Parallel Operation: ±(1.2% of rdg +1.1% of f.s.) Wattmeter H, M Range 0.00W~175.00W 0.00W~350.00W 0.00W~1050W L(CC/CR/CV 0.000W~52.500W 0.000W~ 105.000W 0.00W~315.00W mode) L(CP mode) 0.0000W~ 1.7500W 0.0000W~ 3.5000W 0.000W~ 10.
APPENDIX Slew Rate Setting Range (CR Mode) H Range 250uA/us~250mA/us M Range 25uA/us~25mA/us L Range 2.5uA/us~2.5mA/us Slew Rate Resolution Resolution 1mA Setting 250mA/us~2.5A/us Resolution 100uA Setting 25mA/us~250mA/us Resolution 10uA Setting 2.5mA/us~25mA/us Resolution 1uA Setting 250uA/us~2.5mA/us Resolution 100nA Setting 25uA/us~250uA/us Resolution 10nA Setting 2.5uA/us~25uA/us Slew Rate Accuracy of Setting*1 500uA/us~500mA/us 1.6mA/us~1.
PEL-3000 User Manual Resistance Accuracy of setting H, M Range ±(0.5 % of set*1 + 0.5 % of f.s*2) + Vin*3/500 kΩ L Range ±(0.5 % of set*1 + 0.5 % of f.s) + Vin*3/500 kΩ *1 set = Vin / Rset *2 f.s. = Full scale of High Range *3 Vin = Input terminal voltage of Electronic Load Power Operating Range H Range 17.5W 35W~350W 105W ~175W ~1050W M Range 1.75W 3.5W~35W 10.5W ~17.5W ~105W L Range 0.175W 0.35W~3.5W 1.05W ~1.75W ~10.5W Setting Range H Range 0W~178.5W 0W~357W 0W~1071W M Range 0W~17.85W 0W~35.7W 0W~107.
APPENDIX Protection Function Model PEL-3021 PEL-3041 PEL-3111 Overvoltage protection(OVP) Turns off the load at 110% of the rated voltage Overcurrent protection(OCP) 0.03 ~ 38.5A 0.06A ~ 77A 0.2A ~ 231A or 110% of the maximum current of each range Load off or limit selectable Overpower protection(OPP) 0.1W ~ 192.5W 0.
PEL-3000 User Manual Fast Sequence Operation CC or CR mode Maximum number of 1000 steps Step Execution 25 μs – 600 ms Time Time 1us(25us -60ms) /10us(60.01ms -600ms) resolution Other Elapsed Time Delay Measures the time from load on to load off. On/Off selectable. Measures from 1 s up to 999 h 59 min 59 s Auto Load Off Timer Automatically turns off the load after a specified time elapses. Can be set in the range of 1 s to 999 h 59 min 59 s or off Communication Function GPIB IEEE std. 488.
APPENDIX Range Switch Input Switch ranges L, M, and H using a 2-bit signal Range Status Output Outputs range L, M, or H using 2-bit signal (open collector output by a photocoupler) Trigger Input Clear the sequence operation pause with a high TTL level signal for 10 μs or more.
PEL-3000 User Manual Front Panel BNC Connector TRIG OUT Trigger output: Approx. 5V pulse width: Approx. 2 μs, output impedance: Approx. 500 Ω Outputs a pulse during sequence operation and switching operation. I MON OUT Current monitor output 1 V f.s (H or L range) and 0.1 V f.
1050W 1.5 - 150V 0 - 70A 427.8 I MON OUT 441.4 TRIG OUT Shift Preset 5 2 CAL. P2 P5 0 P0 1 P4 4 8 P1 P8 7 Clear Lock 3 P3 6 P6 9 P9 DC Electronic Load 0 - 210A / 1.5 - 150V , 1050W P7 PEL-3111 Local File Main Enter Load On/ Off Short Help Utility FUNC 400.5 464.4 APPENDIX PEL-3000 Dimensions PEL-3111 143.8 124.
PEL-3000 User Manual PEL-3021, PEL-3041 213.8 Local Main File FUNC Utility Help Short Preset P7 P8 P9 7 8 9 P4 Shift 4 P1 175W 1.5 - 150V 0 - 35A P5 5 P2 1 2 P0 CAL. 0 I MON OUT Load On/ Off P6 6 P3 3 Lock Clear Enter 124.0 151.6 DC Electronic Load 0 - 35A / 1.5 - 150V , 175W PEL-3021 TRIG OUT 400.5 464.
PEL-3211 DC Electronic Load 0 - 420A / 1.5 - 150V , 2100W 427.7 LINK STBY 5.0 5.8 553.5 592.5 APPENDIX PEL-3211 147.8 127.
PEL-3000 User Manual Declaration of Conformity We GOOD WILL INSTRUMENT CO., LTD. No. 7-1, Jhongsing Rd, Tucheng Dist., New Taipei City 236, Taiwan GOOD WILL INSTRUMENT (SUZHOU) CO., LTD. No. 69 Lushan Road, Suzhou New District Jiangsu, China.
INDEX INDEX Accessories ................................. 12 Advanced configuration Alarm tone ..................................... 87 Auto Load ...................................... 75 Control settings ............................. 88 Count time ..................................... 73 Cut off time.................................... 74 Display ........................................... 87 Dyna. Time .................................... 67 Go-NoGo........................................ 89 Language ...
PEL-3000 User Manual Knob configuration Cursor ............................................. 77 Step ................................................. 78 Load default settings................. 28 Load wiring ................................ 31 Connection ..................................... 32 Main features ............................. 11 Marketing Contact ......................................... 172 Memory Recall safety setting................................ 128 Monitor signal output .............
INDEX About disassembly ......................... 4 Contact ......................................... 172 Setting the date and time .......... 28 Specifications Dimensions .................................. 207 Frequency .................................... 195 PEL-3211 ...................................... 195 UnReg alarm ......................... 84, 85 Unreg Tone ................................. 87 UVP alarm................................... 82 Warning symbol ...........................