99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.TestEquipmentDepot.com Muti-Range Bench-Top DC Power Supply PSB-2000 series User Manual GW INSTEK PART NO.
Copyright Statement This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent of Good Will company. The information in this manual was correct at the time of printing. However, Good Will continues to improve products and reserves the rights to change specification, equipment, and maintenance procedures at any time without notice.
Table of Contents Table of Contents SAFETY INSTRUCTIONS ................................................... 5 GETTING STARTED ........................................................... 9 PSB 2000 Series Overview .............................. 10 Appearance .................................................... 17 OPERATION .................................................................... 32 Connecting the AC Power Cable ......................
PSB-2000 Series User Manual PSB-001 Specifications (optional) .................. 99 PSB-002 Specifications (standard) ................ 100 Connection Methods .................................... 101 Connection Cables ........................................ 103 Address Setting ............................................ 104 Using the Interface Boards ........................... 107 Communication Commands ......................... 110 Registers ......................................................
SAFETY INSTRUCTIONS SAFETY INSTRUCTIONS This chapter contains important safety instructions that you must follow during operation and storage. Read the following before any operation to insure your safety and to keep the instrument in the best possible condition. Safety Symbols These symbols may appear in the manual or on the instrument. Warning: Identifies conditions or practices that WARNING could result in injury or loss of life.
PSB-2000 Series User Manual Safety Guidelines General Guideline CAUTION Do not place any heavy object on the unit. Avoid severe impact or rough handling that leads to damaging the unit. Do not discharge static electricity to the unit. Do not block the cooling fan opening. Do not perform measurements on circuits that are directly connected to mains power. Do not disassemble the PSB unless you are qualified.
SAFETY INSTRUCTIONS Cleaning the power supply Operation Environment Disconnect the power cord before cleaning the oscilloscope. Use a soft cloth dampened in a solution of mild detergent and water. Do not spray any liquid into the oscilloscope. Do not use chemicals containing harsh products such as benzene, toluene, xylene, and acetone.
PSB-2000 Series User Manual Power cord for the United Kingdom When using the power supply in the United Kingdom, make sure the power cord meets the following safety instructions.
GETTING STARTED GETTING STARTED The PSB series are variable output, highperformance, regulated, switching DC power supplies. They incorporate a high-frequency current suppression circuit and accept input voltages rated from AC100V to 240V without the need to switch inputs. The offer a wide voltage and current range within their maximum rated power envelope. They also have a variable constant power function.
PSB-2000 Series User Manual PSB 2000 Series Overview Series line up Product name Voltage range Current range Power range PSB-2400H 0V to 800V 0A to 3A 0W to 400W PSB-2800H 0V to 800V 0A to 6A 0W to 800W PSB-2400L 0V to 80V 0A to 40A 10W to 400W PSB-2800L 0V to 80V 0A to 80A 10W to 800W PSB-2400L2 (Dual 0V to 80V channel type) × 2CH 0A to 40A × 2CH 10W to 400W × 2CH 0V to 80V 0A to 80A 10W to 800W PSB-2800LS (Booster unit) 10 Test Equipment Depot - 800.517.
GETTING STARTED ■ 400W Type PSB-2400L ■ 800W Type PSB-2800L ■ 400W×2-Channel Type PSB-2400L2 ■ 800W Type Booster unit PSB-2800LS ■ 400W Type PSB-2400H ■ 800W Type PSB-2800H 11
PSB-2000 Series User Manual Main Features Multi-Range Output Capable of a wide-range of voltage and current settings within the rated power envelope. Constant-Power Control Provides constant-power (CP) control in addition to constant-voltage (CV) and constant-current (CC) controls. Power Factor A built-in power factor correction circuit ensures Correction Circuit compatibility to a wide AC input voltage range from AC100V to 240V without the need to use a switch. It also suppresses harmonic current.
GETTING STARTED Single Unit Control of Parallel/Series Operation The PSB-L series uses a single power supply unit (acting as the master unit) to control all connected slave units for series or parallel operation. In parallel, up to 4 units can be controlled (including the master) to increase the total power. In series, a maximum of 2 units (including the master) can be used.
PSB-2000 Series User Manual Accessories Model Number Description PSB-001 GPIB Control Board. Includes GRJ-1101 modular cables. For further details, see page 99. PSB-002 RS-232C/USB Control Board. Includes GRJ-1101 modular cables. For further details, see page 100. PSB-003 Parallel Connection Kit for Horizontal Installation. PSB-007 Joint Kit Kit includes: PSB-007 Joint kit, Horizontal bus bar x2, PSB-005 x1. Horizontal Bus Bar PSB-005 PSB-004 Parallel Connection Kit for Vertical Installation.
GETTING STARTED Vertical Bus Bar PSB-005 PSB-005 Parallel Connection Signal Cable PSB-006 Serial Connection Signal Cable PSB-007 Joint Kit: Includes 4 joining plates, 4X M3x6 screws, 2X M3x8 screws. GRJ-1101 Modular Cables: 500mm 6P6C RJ11 (local bus cables) 15 Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176 TestEquipmentDepot.
PSB-2000 Series User Manual Standard Accessories Model Number Description User Manual CD x 1 AC power cable x 1 Screws for output terminals on rear panel Protection covers for output terminals on rear panel Protection caps for output terminals on the front panel External control connector (26-pin) GND cable 16
GETTING STARTED Appearance Front Panel (PSB-2400L2 shown) 1 5 6 7 8 9 10 11 12 13 PSB - 2400L 2 V W OUTPUT ON / OFF A W MENU CH 1 OFF TIMER DISP CH1 DELAY CH2 Hi - W (L Type ONLY) V POWER W MENU PRESET CC CP DISP ENTER ESC FAST/ LOCK(3s) 2 3 / LOCAL MAX 400W MAX DC 80V AT E 1 CV CHECK A CH 2 O T FAST LOCK SEQUENCE R MAX DC 40A REMOTE CH 1 CH 2 Multi- Range DC Power Supply 2 3 4 14 15 16 17 18 19 20 21 22 17
PSB-2000 Series User Manual Front Panel (PSB-2400H shown) 1 5 6 7 8 9 10 11 12 13 PSB - 2400 H V W OUTPUT ON / OFF A W MENU OFF TIMER Hi - W ( L Type ONLY) V POWER W A MENU PRESET 2 DISP ESC CC CP FAST/ LOCK(3s) 3 / LOCAL AT E 1 CV CHECK ENTER O T FAST R LOCK SEQUENCE REMOTE CAUTION Regulated DC Power Supply MAX 400W MAX DC 800V MAX DC 3A 2 3 4 14 Item 15 16 17 18 19 20 21 22 Description 1 Front grill This is a ventilation grill for for cooling t
GETTING STARTED Panel Operation Unit PSB-2400L, PSB-2800L PSB-2400H, PSB-2800H Type 5 PSB- 2400L2 Description Address no., Step no., cycle no., Menu no. Normal operation Not displayed. 6 Channel LEDs The LED of the selected channel is lit. Both LEDs are lit when the tracking function is activated. 7 Current LED Normal (7-segment) operation Current or power is displayed. Sequence operation Number of steps or cycles is displayed. Sequence operation Step No. is displayed. Menu Tracking Menu No.
PSB-2000 Series User Manual 8 Voltage LED Normal (7-segment) operation Voltage or power is displayed. Sequence operation Cycle No. is displayed. Menu Alarm Set parameter OVP, OCP, is displayed. HARD or OHP is displayed. The ―W‖ LED on the right of the 7-segment LED is lit in the power display state. 9 Function LEDs 10 ESC/DISP key (ESC / DISP) These LEDs display the On/Off state of the OFF TIMER, DELAY or HiΩ functions. The LED is lit green when the corresponding function is activated.
GETTING STARTED 13 Rotary encoder Used to select the functions and change the values. 14 V key (green) Used for setting the voltage. Press the key and (V) rotate the encoder to change the set value. If the A key is pressed while holding the V key, both LEDs are lit and the Current LED enters the power display mode. 15 A key (green) Used for setting the current. Press the key and (A) rotate the encoder to change the set value.
PSB-2000 Series User Manual 20 ENTER/ CHECK Key (ENTER/ CHECK) Alternates the operation (and display) between the output value and the set value. When the output is on, every press of the ENTER/ CHECK key alternates the display between the output value and set value. ・ When the V key is lit The voltage setting is enabled. ・ When the A key is lit The current setting is enabled. ・ When the V and A keys are lit the power setting is enabled.
GETTING STARTED Rear Panel (PSB-2400L2 shown) 23 24 25 26 27 28 29 30 31 CH 1 ! DC OUTPUT DC DC 400W 80V 40A J1 J2 PSB-002 I ~100V-240V 50Hz / 60Hz 650 VA MAX 26 25 I ▲ EXT CONT J3 USB MAX MAX MAX I CH 2 ! DC OUTPUT DC DC MADE IN TAIWAN ! △ AC INPUT 400W 80V 40A 2 1 LOCAL BUS MAX MAX MAX 23 24 25 26 27 28 29 30 31 +S CAUTION J1 J2 + USB I -S - PSB-002 I 26 25 I ! DC OUTPUT 400W DC 800V DC 3A ! △ AC INPUT 2 1 LOCAL BUS EXT CONT J3 MAX MAX MAX MADE IN T
PSB-2000 Series User Manual Description 23 Optional Interface board slot The optional interface board slot is used to install the optional PSB-001 board for the GPIB interface. The product is supplied with the USB/RS-232C option as standard. 24 J3 external control connector The external control connector is used to control or monitor a number of different parameters using external components. The pin assignment of this connector can be found on page 26(40A models) 30(3A/6A models).
GETTING STARTED 27 J1 control This connector is used for parallel and serial signal input control for master/slave operation. The optional connector frame link cables must be used with this connector. 28 J2 control This connector is used for parallel and serial signal output control for master/slave operation. The optional connector framelink cables must be used with this connector. 29 Exhaust Grill Air taken into the unit from the front is blown out through this grill.
PSB-2000 Series User Manual Pin assignment of the J3 External Control Connector (PSB-2400L, 2800L, 2400L2, 2800LS) Pin No. Signal name Function 1 CH2 STATUS COM COM for pins 2, 3 and 4. (COM for 2, 3 & 4) 2 CH2 ALARM OUT Open collector output. When the alarm is output for channel 2 then this pin is pulled low. 3 CH2 EXT CC STATUS OUT Open collector output. Set to the low level when channel 2 is in CC mode. 4 CH2 EXT CV STATUS OUT Open collector output.
GETTING STARTED 6 CH2 EXT CC CONTROL IN Constant-current control input pin for channel 2. In the external voltage control mode, an external voltage of 0V to 10V can be used to control the ouput current from ~0A to the rated output current. In the external resistance control mode, an external reistance of 0kΩ to 10kΩ can be used to control the output current from ~0A to the rated output current. 7 CH2 COM COM pin for channel 2. Connected to the negative output terminal of channel 2.
PSB-2000 Series User Manual 13 CH2 COM COM pin for channel 2. Connected with the negative output terminal of channel 2. 14 CH1 EXT CV CONTROL IN Constant-voltage control input pin for the channel 1. In the external voltage control mode, an external voltage of 0V to 10V can be used to control the output voltage from ~0V to the rated output voltage.
GETTING STARTED 18 CH1 EXT A MON OUT Output current monitor pin for channel 1. Outputs approx. 0V to 10V to represent 0 to the rated output current. 19 CH1 COM COM pin for channel 1. Connected with the negative output terminal of channel 1. 20 CH1 EXT ALARM IN Causes the alarm state to be triggered when short-circuited with the CH1 COM pin. 21 CH1 EXT OUTPUT Turns on the CH1 output when shortIN circuited with the CH1 COM pin. 22 CH1 COM COM pin for channel 1.
PSB-2000 Series User Manual Pin assignment of J3 external control connector (PSB-2400H, 2800H) Pin No. Signal name Function 13 NC 14 EXT CV CONTROL Constant-voltage control input pin. IN In the external voltage control mode, an external voltage of 0V to 10V can be used to control the output voltage from 0V to 800V. In the external resistance control mode, an external resistance of 0kΩ to 10kΩ can be used to control the output voltage from 0V to 800V.
GETTING STARTED 18 EXT A MON OUT Output current monitor pin Outputs approx. 0V to 10V to represent the outuput current from 0A to 3A(400H) or 6A(800H). 19 COM COM Connected with the negative output terminal. 20 EXT ALARM IN Trigger the alarm state when shortcircuited with the COM pin. 21 EXT OUTPUT IN Turns on the output when shortcircuited with the COM pin. 22 COM COM Connected with the negative output terminal. 23 EXT CV STATUS OUT Open collector output.
PSB-2000 Series User Manual OPERATION This chapter describes the start up procedures and the preparation that is necessary before operating the DC power supply. Connecting the AC Power Cable Introduction Make sure that the power source is shut off. Use the AC power cable supplied with the product. Plug the connector of the AC power cable into the AC INPUT receptacle on the rear panel.
OPERATION still if the cables are twisted to reduce noise or to avoid malfunctioning. Be careful of the temperature! Connecting to the Rear Output Terminals (PSB-2400L, 2800L, 2400L2, 2800LS) Procedure 1. Remove the AC cable from the AC INPUT. 2. Connect crimped lug terminals to the ends of the load cables. Tighten the lug terminals firmly using the nuts supplied with the power supply. CAUTION Fig. Connection with Rear Output Terminals The rear output terminals have M6 holes and M3 (tapped) holes.
PSB-2000 Series User Manual Note Connect the cables using the bolts supplied with the power supply as shown above. If different bolts are used, they may contact the protective cover or interfere with the protective cover. The lug terminals must be on the outside of the output terminals. 3. Connect the positive or negative output terminal to the GND screw with the symbol using the GND cable supplied with the product as the necessity requires.
OPERATION 4. Sandwich the output terminals and the load cables from above and below with the rear output terminal protective covers, as shown below. Drive the screw into the protective covers at the center. Fig. Attaching Rear Output Terminal Protective Covers CAUTION Make sure that the protection covers are always attached to the terminals even when they are not being used. The front and rear output terminals are electrically connected internally.
PSB-2000 Series User Manual Fig. Parts to be cut Parts to be cut Parts to be cut Parts to be cut Connection with the Rear Output Terminals (PSB-2400H, 2800H) Procedure 1. Remove the AC cable from the AC INPUT. 2. Insert the load line and then use a flathead screwdriver or similar tool to firmly secure it. 3. If necessary, use the supplied output ground cable and screw to establish a positive or negative ground connection to the output ground terminal ( mark).
OPERATION Fig. Connection with Rear Output Terminals マイナスドライバー等 A flathead screwdriver or similar tool Load line 負荷線 Note + - The negative potential of the external voltage control is the same as that of the negative output terminal. If the power supply unit is grounded at the positive terminal and the power source for external control is grounded at the negative terminal, the load cables for external voltage control will short-circuit the output of the power supply unit, which could damage the unit.
PSB-2000 Series User Manual Connection with the Front Output Terminals (PSB-2400L, 2800L, 2400L2, 2800LS) Procedure 1. Turn on the unit using the POWER switch. 2. Connect crimped lug terminals to the ends of the load cables. Fix the load cables firmly to eliminate loose connections from the front output terminals and load cables. 3. If current is output through the rear output terminals, cover the front output terminals with the protective caps for safety. Fig.
OPERATION Assembling and Connecting the Front Output Terminal Plugs (PSB-2400H, 2800H) 1. Insert the cable (load line) into the plug. Procedure 2. Use a 1.5 mm hex key to fasten the 2 screws. 3. Insert the cover into the plug and make sure it hooks into place (completion image). 4. Turn the power switch off from the unit. 5. Insert the above-mentioned plug into the front output terminal. 6. When current is drawn from the rear output terminals, the plug must be removed from the front output terminal.
PSB-2000 Series User Manual Operation Ranges (PSB-2400L, 2800L, 2400L2, 2800LS) The PSB-2000 series power supply units offer wider voltage and current range settings, within the rated power envelope, than our traditional models.
OPERATION Operation Ranges (PSB-2400H, 2800H) Voltage setting range: 0V to 800V (All models) Current setting range: 0A to 3A (PSB-2400H) 0A to 6A (PSB-2800H) Power setting range: 0W to 400W (PSB-2400H) 0W to 800W (PSB-2800H) Output voltage Output voltage 800V 800V 700V PSB-2400H 600V 600V 500V PSB-2800H 700V 400W Power limit line 400V 400V 300V 300V 200V 200V 133V 133V 0.5A 1A 1.5A 2A 2.5A 3A Output current Fig.
PSB-2000 Series User Manual Various Settings Turning the Power On Introduction Note First, press the POWER switch to turn on the power. The power supply unit will show the startup screen (firmware version and models) for several seconds and then displays the last-used settings. The unit saves the last-used settings automatically when the power supply source is cut off or the POWER switch is shut off. Model PSB-2400L, version 1.
OPERATION How to Set the Current Procedure 1. Make sure that the A key is lit green. If not, press the A key to turn it on. V W A 2. Set the current with the encoder wheel. How to Set Power Procedure 1. Make sure that both the V and A keys are lit. If not, press the V and A keys to turn them on. (Both keys need to be lit when setting the power.) V W A If the A key is pressed while keeping the V key depressed, the Current LED display can be used to enter the power setting.
PSB-2000 Series User Manual Fig. Power Display Voltage and Power: 80V and 400W Current and Power: 400W and 40A How to Turn the Output On Output Methods Turning the output on or off using the OUTPUT key. Turning the output on or off using the CH1 or CH2 key (PSB-2400L2 only). Turning the output on or off using the external control function. Note If the output is quickly turned off then on, then it is possible that the voltage will not discharge normally.
OPERATION The CH1 and CH2 keys are independent of each other, and it is possible to turn the output on through channel 1 or B by pressing the CH1 or CH2 key to select the corresponding channel. However, the output is disabled unless the OUTPUT key is lit. Note Fig. Output by Pressing OUTPUT key For the PSB-2400L2, if neither the CH1 nor CH2 key is lit, the OUTPUT key will not go on even if it is pressed. (No output is provided.
PSB-2000 Series User Manual How to Display the Setting Value When the Output is On Output methods The power supply unit displays the output value when the output is on. Press the ENTER/ CHECK key when the output is on to switch the display to the setting value. Every press of the ENTER/CHECK key toggles the display between the setting mode and output mode.
OPERATION How to Rotate the Display Panel 90 Degrees for Vertical Installation The display panel on the PSB-2000 series can be rotated 90 degrees so that the unit can be operated comfortably in either the horizontal or vertical orientations. Hold the encoder wheel and rotate the orientation of the panel while pressing the ROTATE key below the encoder wheel. Keep turning the panel until a ―click‖ sound is heard. This indicates that the panel is now locked in place.
PSB-2000 Series User Manual How to Disable Panel Operations (Key Lock Function) Operation CAUTION It is possible to disable the front panel keys by pressing the FAST/LOCK(3s)/LOCAL key on the left of the encoder. Hold this key for three or more seconds to lock the panel keys. The keys are locked when the LED beside the key turns red. To cancel the key lock function, hold the FAST/LOCK(3s)/LOCAL key for 3 or more seconds. This key serves as the FAST, LOCK (3s), and LOCAL keys.
OPERATION Menu Key Functions Introduction Every press of the MENU key changes the menu numbers: PSB-2400L, 2800L, 2800LS: MENU Option ―01‖ to ―07‖. PSB-2400L2: MENU Option ―01‖ to ―09‖. PSB-2400H, 2800H: MENU Option ―01‖ to ―06‖. Operation Overview Press the ESC/DISP key to return from the MENU settings to the normal settings. To deactivate a function, select the corresponding setting again from the menu and deactivate it. MENU key: Cycles through the menu options.
PSB-2000 Series User Manual The diagram below can be used as a reference for the menu operations in the following pages: Voltage LED Current LED 2 digit LED for displaying the number of cycles, step No., and menu No. General Setting Procedure 1. Press the MENU key until an intended function number is displayed. 2. Press the ENTER/ CHECK key to validate the function. Proceed to setting of the next item. 3. Set a numeric value or item with the encoder, and press the ENTER/ CHECK key to validate it. 4.
OPERATION Sequence External (voltage/resistance) External (On/Off) Delay (PSB-L Series Only) Tracking (PSB-L Series Only) Preset Off timer External (voltage/resistance) External (On/Off) Delay Tracking Preset Tracking Off timer Delay Sequence Off timer Sequence External (voltage/resistance) External (On/Off) 51
PSB-2000 Series User Manual Preset Function Menu Item: 01(All Models) Introduction Procedure This function saves settings to one of the three PRESET keys. The settings shown below may be preset. Note that any other settings/values may not be saved. Set voltage Set current Set power 1. Set the voltage/current/power settings that you want saved. 2. Press the MENU key until menu number ―01‖ is displayed. 3. Press the ENTER/ CHECK key. All the PRESET keys blink green. 4.
OPERATION activating the preset function. OVP/OCP function Menu Item: 02 (All Models) Introduction OVP: (Over Voltage Protection) The OVP function turns off the output when the output voltage of the PSB-2000 series exceeds the preset OVP value. Model Setting Range Resolution PSB-2400L PSB-2800L PSB-2400L2 PSB-2800LS 1.0V to 84.0V 0.1V PSB-2400H PSB-2800H 10.0V to 840.
PSB-2000 Series User Manual Procedure 1. Press the MENU key until menu number ―02‖ is displayed. 2. Press the ENTER/ CHECK key to toggle between the OVP and OCP setting displays. On the PSB2400L2, the OVP and OCP settings for channel 1 appear first, followed by channel 2 next. OVP setting OCP setting → OVP and OCP setting of channel 1 OVP and OCP setting of channel 2 3. When the intended protection function is displayed (OVP or OCP), rotate the encoder wheel to set the OVP or OCP level. 4.
OPERATION Hi-Ω- Function Menu Item: 03 (PSB-L Series Only) Introduction The PSB-2000 series power supplies have filter capacitors connected to the output. The PSB-L power supplies also have a bleeder circuit to discharge these capacitors to a safe level when the output is turned off. When the Hi-Ω function is activated, the bleeder circuit is deactivated. This allows you to omit reverse-current preventing diodes that are necessary for charging batteries or capacitors when a bleeder circuit is active.
PSB-2000 Series User Manual Hi-Ω Off Hi-Ω On 3. Press the ENTER / CHECK key to confirm the setting. The Hi-Ω LED in the center of the panel turns on. ○ OFF TIMER ○ DELAY ● Hi-Ω 4. Next, set the time limit for when the bleeder circuits are turned back on with the encoder wheel. Setting range: 5~30 minutes. Setting resolution: 5 minute steps. Press the ENTER / CHECK key to confirm the setting. Example: Timer set for 20 minutes. 5.
OPERATION CAUTION When the Hi-Ω function is activated, the output terminals of the power supply unit keep on carrying voltage even after the output is turned off. The Hi-Ω LED will blink when Hi-Ω function is still active as the internal capacitors remain charged. Voltages as high as 80V may remain at the terminals when the output is turned off. Such a state is very dangerous. To avoid accidents, isolate the output terminals from the load cables completely with a relay or switch.
PSB-2000 Series User Manual Off Timer Function Menu Item: 04(PSB-L Series), 03(PSB-H Series) Introduction This function turns the output off automatically after a set amount of time. The timer can be set in ten minute steps to a maximum of 99 hours, 50 minutes. Procedure 1. Press the MENU key until menu number ―04‖ is displayed(PSB-L) or ―03(PSB-H series) 2. Press the ENTER / CHECK key to enter the Off Timer settings. 3. Select ON or OFF with the encoder wheel. The Off Timer is turned off by default.
OPERATION The timer may be set in steps of ten minutes to a maximum of 99 hours and 50 minutes. The OFF TIMER LED will blink when the remaining time is less than five minutes. The remaining time for the off-timer may be checked by pressing the ESC/DISP key while the off-timer is running. (On the PSB-2400L2, pressing the ESC/DISP key toggles the display in the following order: CH1 settings, CH2 settings, and then the remaining time of the offtimer.) Example: Off Timer set to ten minutes 6.
PSB-2000 Series User Manual Sequence Function Menu Item: 05(PSB-L), 04(PSB-H) Introduction This function executes sequence programs. Please note that sequence programs can only be created when one of the interface boards (PSB-001 or PSB002) are installed. Without an interface board installed, the sequence function is not available. Please see the PSB_Sequence_203 usermanual or the GW Instek website for more information on how to program sequences.
OPERATION CAUTION If the output is active at the end of the program as shown in the figure above, the power supply output will remain at the level of the last step even after the completion of the sequence operation. (I.e., the output stays active.) The last step number must be set to OFF for the the output to be turned off at the end of a sequence. The sequence operation will end prematurely if the OUTPUT key pressed when a sequence is running.
PSB-2000 Series User Manual ○ ○ ○ ―●SEQUENCE― 4. Next, set the Start Step number with the encoder wheel. Press the ENTER / CHECK key to confirm. The setting range is from 0 to 99. Example: The Start Step is set to No. ―00‖. 5. Set the End Step number with the encoder wheel. Press the ENTER / CHECK key to confirm. The setting range is from 0 to 99. Example: The End Step is set to step No. ―99‖. 6. Set the number of times to repeat the steps above with the encoder wheel.
OPERATION mode. External Control (External Voltage, External Resistance) Menu Item: 06(PSB-L), 05(PSB-H) Introduction Constant-Voltage (CV) Control Using External Voltage This function allows you to control the voltage of the PSB-2000 series power supply unit by applying an external voltage to the unit. An external voltage of 0V to 10V can be used to control the output voltage from ~0V to the rated output voltage.
PSB-2000 Series User Manual of the PSB-2000 series power supply unit by connecting an external resistance to the unit. An external resistance of 0Ω to 10kΩ can be used to control the output current from ~0A to the rated output current. CAUTION Procedure The PSB-2000 series power supply unit is incapable of simultaneous external voltage and external resistance control. For example: Using an external voltage for CV control and external resistance for CC control is not supported. 1.
OPERATION Controlling constant voltage Controlling constant voltage from the front panel using external control Controlling constant current Controlling constant current from the front panel using external control 4. Finally, press the ENTER / CHECK key to validate the settings. Setting the control mode is now complete. 5. Press the ESC / DISP key to quit the setting mode and return to normal operation.
PSB-2000 Series User Manual Procedure 1. Press the MENU key until menu number ―07‖(PSB-L) or ―06‖(PSB-H) is displayed. 2. Press the ENTER / CHECK key to enter the external output On/Off control setting mode. 3. Select On or Off with the encoder wheel, and press the ENTER / CHECK key again to confirm the settings. The external output on/off setting is now complete. The output control modes are shown below: IN= The output is controlled with the OUTPUT key.
OPERATION Delay Function Menu Item: 08 (PSB-L2) Introduction The delay function is available on the dual channel model (PSB-2400L2) only. It adds a rise and fall delay time to the output of channel 2 for a specified amount of time (in seconds) from a reference point (output of channel 1). The rise delay time refers to the delay time for turning the output on. The fall delay time refers to the delay time for turning the output off. Fig. Temporal Concept of Delay Function Positive (10 seconds Max.
PSB-2000 Series User Manual 3. Press the ENTER / CHECK key to confirm the setting. The DELAY LED in the center of the panel turns on. ○ OFF TIMER ● DELAY ○ Hi-Ω 4. Set the rise delay time with the encoder wheel. When a positive time is set, the output of channel 2 is delayed with respect to channel 1. On the contrary, when a negative time is set, the output of channel 2 leads that of channel 1. The delay time can be set in the range of -9.99 seconds to +10.00 seconds in steps 10 ms.
OPERATION Tracking Function Menu Item: 09 (PSB-L2) Introduction The tracking function is available on the dual channel model (PSB-2400L2) only. When the tracking function is turned on, the output of channel 2 is made to match the output of channel 1, thus channel 2 can be said to ―track‖ channel 1. This effectively means that the values of both channels change simultaneously. Fig.
PSB-2000 Series User Manual menu and return to normal operation. ―Ab‖ is displayed on the MENU LED when the tracking function is activated. Example: Tracking function is activated. Master-slave function Menu Item: 10 The master-slave function allows the PSB series to operate in parallel or series (PSB-L only). For series operation a maximum of 2 PSB-L units can be used. For parallel operation, a maximum of 4 (PSB-L) units or 2 units (PSB-H) units can be used.
OPERATION Display for a slave unit in a parallel connection Procedure Display for a slave unit in a series connection 1. The master-slave settings can be accessed by turning on the power switch while holding the MENU key. 2. Select the operation mode for the unit with the encoder wheel and press the ENTER / CHECK key to confirm the setting.
PSB-2000 Series User Manual 3. Set the total power with the encoder wheel if the unit is set as the master unit in a parallel connection. Example: Total power of 3200 W. 4. Press the ESC / DISP key to exit the settings and return to normal operation.
OPERATION Voltage Sense Description CAUTION The PSB-2000 series power supply units have an output voltage remote sensing function. This function eliminates influences of voltage drops between the power supply unit and load, which is caused by the contact resistance or the resistance of the load cable conductors. Voltage sense compensates for a voltage of up to 1V on a single terminal.
PSB-2000 Series User Manual firmly. NOTE Approximately 1mA of current flows through the sensing wires at the rated output voltage. Use AWG 26 to 18 wires as the sensing wires. Fig. Remote Sensing Connection (PSB-L) +S +OUTPUT + -OUTPUT -S Shielded cable or Twisted pair wires + Load Fig.
OPERATION External Control Functions Description The following connectors are supplied with the power supply for external control. Procedure 1. XG5M-2635-N (manufactured by OMRON Corporation) (For all PSB-2000 series) This section describes how to assemble the external control connector Assembling the XG5M-2635-N Connector Procedure 1. Remove the contacts from the housing. Each contact can be easily removed by pulling it out while using a pin to hold down its catch.
PSB-2000 Series User Manual Fig. Assembling the External Control Connector (XG5M-2635-N) The 26-pin connector for external control: XG5M-2635N (OMRON Corporation) Each contact can be easily removed by pulling it out while using a pin to hold down its catch. The XY2E-0001 contact removal tool (manufactured by OMRON Corporation), can also be used to remove the contacts. Applicable wire: Twisted wire AWG28 or 26 Outer diameter φ1.1 to 1.3 mm Mount the semi-covers on both sides of the connector.
OPERATION NOTE Procedure The internal impedance of the voltage and current monitoring circuits are approximately 1kΩ. Be careful not draw over 1mA through the monitoring circuits. 1. Voltage monitor CH1: Pins 17 and 16 (COM), CH2: Pins 8 and 7 (COM) 2. Current monitor CH1: Pins 18 and 16 (COM), CH2: Pins 9 and 7 (COM) Fig.
PSB-2000 Series User Manual Constant-Voltage (CV) Control with External Voltage or Resistance Introduction CAUTION The output voltage can be controlled by an external voltage or resistance through the J3 external connection (EXT CONT) on the rear panel if external control is selected. The negative side of the external voltage is connected with the negative output terminal of the power supply unit. Have the external voltage source floating to avoid accidents or malfunctions.
OPERATION Fig.External Voltage/ Resistance Control Terminal(CV) EXT CONT (J3) 2 1 0V ~ 10V 26 25 Negative output terminal of CH1 CH1 0Ω ~ External 10kΩ control ※ Use a shielded cable or twisted pair wires for this control. EXT CONT (J3) 0V ~ 10V 26 25 2 1 Negative output terminal of CH2 CH2 0Ω ~ External 10kΩ control ※ Use a shielded cable or twisted pair wires for this control.
PSB-2000 Series User Manual Constant-Current (CC) Control with External Voltage or Resistance Introduction The current output can be controlled using an external voltage or external resistance through the connector J3 (EXT CONT) on the rear panel if external control is selected. External Resistance and External Voltage Control Pins for current control: CH1: Pins 15 and 16 (COM) CH2: Pins 6 and 7 (COM) Fig.
OPERATION Output ON/OFF with External Contacts Introduction The output can be turned on or off using external contact switches if the external control function is activated. External Control Pins for Output ON/OFF control: CH1: Pins 21 and 22 (COM) CH2: Pins 12 and 13 (COM) Short: OUTPUT ON Open: OUTPUT OFF Fig.
PSB-2000 Series User Manual Alarm Function using External Contacts Introduction An external contact switch can force the PSB-L into the alarm state. When in the alarm state, the output is turned off and ―HARD‖ is displayed on the LED display. Remove the input power or turn off the power from the POWER switch to cancel the alarm state. External Control Pins to activate the alarm state: CH1: Pins 20 and 22 (COM) CH2: Pins 11 and 13 (COM) Fig.
OPERATION Status Signals (CV, CC & ALARM) Introduction Constant-Voltage (CV) Status Signal This status signal goes low when the PSB-2000 series power supply unit enters the constantvoltage (CV) status. Constant-Current (CC) Status Signal This status signal goes low when the PSB-2000 series power supply unit enters the constantcurrent (CC) status. Alarm Status Signal This status signal goes low when the PSB-2000 series power supply unit enters the alarm status.
PSB-2000 Series User Manual Fig. Status Pins EXT CONT (J3) EXT CONT (J3) 26 2 25 1 2 1 26 25 CV CV CC CC ALARM CH1 status ALARM Inside of PSB-2000 Series CH2 status R Fig. Photocoupler current V Internal current 2mA I=1mA or less ※ Select and use proper voltage or resistance so that the open collector current does not exceed 1mA.
OPERATION Using the Sequence Function Description The section ―Sequence Function‖ (page 60) shows how to execute a sequence program on the power supply when equipped with the optional interface board. The PSB_Sequence_203 software is used to create a program in advance via the optional interface board. See the Sequence Function section on page 60 for details. The PSB_Sequence_203 software can be downloaded at the GW Instek website. Procedure 1. Write a sequence program through the interface board.
PSB-2000 Series User Manual OUTPUT CAUTION Ends the sequence operation. The OUTPUT key does not the start sequence operation. Use the PRESET 1 ( ) key to start the sequence operation. Even if the sequence function is activated and the ―● SEQUENCE LED‖ is lit, the sequence operation will not start unless the PRESET 1 ( ) key is pressed. Functions other than the preset function will work normally even when the ―● SEQUENCE LED‖ is lit.
OPERATION the sequence operation partway, press the OUTPUT key or deactivate the sequence function as shown in the Section ―Sequence Function‖(page 60).
PSB-2000 Series User Manual OTHER FUNCTIONS Display in Alarm Status Description When the PSB-2000 series power supply unit enters an alarm state or if the alarm state is manually set using the external control connector (see page 82), an alarm code is shown on the display. The alarm code will indicate what type of alarm has been triggered. When an alarm occurs, the power supply unit turns off the output and stays in the alarm state.
OTHER FUNCTIONS (2) OCP alarm This alarm code is displayed if the output current exceeds the preset OCP value. (3) OHP alarm The OHP alarm is displayed if the temperature at an internal detection point exceeds a set temperature. The OHP alarm that is displayed differs from model to model, as shown below. For example, on the 2400L2, an OHP alarm is displayed for each channel.
PSB-2000 Series User Manual ALARM connector are shorted. For details, see page 82. PSB-L Only. Frame Link Controlled Parallel Operation (excluding PSB-2400L2) Description The PSB Series power supply units are capable of frame link controlled parallel operation of up to four units(PSB-L), or up to 2 units (PSB-H) including the master unit. When performing parallel operation using master units, the master and slave units should be set properly in advance, see the Master-slave function chapter on page 70.
OTHER FUNCTIONS CAUTION Improper wiring or settings may cause failures. Recheck the settings before starting frame control operation. If the load cables of a slave unit are disconnected, excessive voltage is applied to the slave unit instantaneously and a ―HArd‖ alarm occurs. Check if the cables are connected properly. Repair improper connections. The master unit displays the total current.
PSB-2000 Series User Manual Frame Link Controlled Series Operation (excluding PSB-2400L2, PSB-H series) Description The PSB-L series power supply (exlcluding the PSB-2400L2) units are capable of frame link controlled series operation of up to two units, including the master unit. When performing series operation using master units, the slave unit should be set properly in advance, see the Master-slave function chapter on page 70. Output depends on the master unit.
OTHER FUNCTIONS Power Extension using PSB-2800LS (Parallel Connection Only) Description The PSB-2800LS (booster unit) is especially designed to boost the power capacity when used in parallel. It is possible to increase the output up to a maximum of 3200W when used in parallel with a PSB-2800L as the master unit). NOTE Note that the PSB-2800LS cannot be used for series operation. Fig.
PSB-2000 Series User Manual Fig. Connection Example for Horizontal Installation Fig. Connection Example for Vertical Installation Using the PSB-007 Extension kits Description The PSB-007 extension kits allow master units to be physically connected to slave units. The extension kits can be used horizontally or vertically. NOTE Note that the PSB-2800LS cannot be used for series operation.
OTHER FUNCTIONS How to Connect the Units Vertically Steps 1. Remove the rubber feet from the bottom of unit A. (Keep the removed rubber feet and screws with care not to lose them.) 2. Fix the joint kit (PSB-007) to the top panel of unit B with the flat countersunk head screws supplied with the kit. (Four positions) 3.
PSB-2000 Series User Manual How to Connect the Units Horizontally Steps 1. Remove the rubber feet from the side of unit B. (Keep the removed rubber feet and screws with care not to lose them.) 2. Fix the joint kit (PSB-007) to the side of the unit A with the flat countersunk head screws supplied with the kit. (Four positions) 3.
OTHER FUNCTIONS Bus Bar Connection Fig.
PSB-2000 Series User Manual EXTERNAL CONTROL Remote Control Description NOTE The PSB-2000 series power supplies can be controlled from a PC or sequencer when one of the optional interface boards are installed. Two types of interface boards are available: PSB-001 (GPIB) and PSB-002 (RS-232C and USB). A maximum of ten units to be connected together with the local bus connection, with one unit as a master unit. The master unit is then connected to a PC through GPIB, RS-232C or USB.
EXTERNAL CONTROL Interface Connectors USB connector RS-232 connecter Local bus connecter GP-IB connector Fig. Diagram of the Interface Boards PSB-001 Specifications (optional) GPIB Specifications Interface functions Address setting Delimiter Listener function Talker function Service request function Q’ty of connectable units Local bus Specifications Max. cable length Conforms to IEEE488-1978.
PSB-2000 Series User Manual Connector type Applicable cable Q’ty of connectable units Terminator Q’ty of ports RJ-11 (6-pin modular) Pin 2 (D+), pin 3 (D-) Modular cable: GRJ-1101 (500mm 6P6C RJ11) A maximum of 10 units can be connected in a daisy chain configuration. The terminator is built-in. It may be turned on or off with a jumper pin. 2 ports, non-directional PSB-002 Specifications (standard) RS-232C Specifications Data transmission speed Data bit Max.
EXTERNAL CONTROL Terminator Built-in. May be turned on/off with jumper pin. Q’ty of ports 2 ports, non-directional NOTE The PSB-001 and PSB-002 interface boards have the same local bus for connecting slave units, which may be equipped with either type of interface board. Connection Methods Description Fig. Local Bus Connection The following shows an example of connecting several PSB-2000 series power supply units through the local bus.
PSB-2000 Series User Manual When connecting units together using the local bus connection, any of the local bus ports on the interface board can be used as the input or output. Use the shortest modular cables possible to connect each unit. Terminate the start and end of the daisychain-connected units by shorting CN2 jumper pins on the interface boards with the shorting connectors1. Disconnect the shorting connectors from all the other interface boards 2.
EXTERNAL CONTROL Connection Cables Procedure Fig. RS-232C Cable Connection Use the proprietary modular cables for the local bus connection (GRJ-1101). Use standard GPIB cables for the GPIB connections. Use USB cables (applicable for Full Speed USB or greater) for the USB connections. Use interlink cables for the RS-232C connection. The pin assignment is as shown below. Note that normal crossover cables may not be used.
PSB-2000 Series User Manual Address Setting Description The interface has two addresses: Personal Computer Address, and System Address. The type of address that is used depends on whether the unit is the master connected to a PC or a slave unit connected over the local bus. If the System Address is set to 1, then that unit is designated as the master unit. A Personal Computer Address can then be assigned to the master unit as well.
EXTERNAL CONTROL Procedure 1. Turn on the unit while holding the A key to set the System Address and/or Personal Computer Address. The model name and version data are displayed first, and then the interface type is displayed. After this, the System Address may be set 1. ―Sy.Ad‖ is displayed on the Voltage LED, and the address is displayed on the Current LED. Rotate the encoder to select the System Address, and press the ENTER / CHECK key to confirm.
PSB-2000 Series User Manual 3. The unit saves the System Address and Personal Computer Address in non-volitile memory. The System Address and Personal Computer Address will remain saved even if the power to the unit is turned off.
EXTERNAL CONTROL Using the Interface Boards Using the GPIB interface Description All GPIB operations have been tested using a NATIONAL INSTRUMENTS GPIB controller and sample programs. All interface cards conforming to the IEEE488 standard should be compatible with the PSB-001 interface board. However, compatibility cannot be assured. The PSB-001 accepts the following delimiters: LF (0×0A), EOI, and LF (0× 0A) + EOI. It sends a response using LF (0× 0A) + EOI only.
PSB-2000 Series User Manual Using the USB interface Description NOTE Installing the USB driver in Windows 8 You may use the USB port of your Personal computer for communication through the USB interface. Microsoft Windows 98SE, 2000, XP to Windows 8* may be used. To use the USB interface, it is necessary to install the device driver. This driver may fail to work properly if the host PC is in the suspend mode or sleep mode.
EXTERNAL CONTROL Using the RS-232C Interface Description The serial port on a PC or sequencer can be used for communication through the RS232C interface. The interface uses CTS-RTS for flow control. Please note that with this type of communication, if the flow control fails to work properly, some characters may be lost, which may result in a malfunction or error.
PSB-2000 Series User Manual Communication Commands Description Every communication command consists of general alphanumeric characters and symbols and a header, which is the abbreviation of a function. Parameters can be either an integer (NR1) or a floating point number with decimal places (NR2). Parameters following the tenth character are ignored. Decimal places are rounded off according to the actual setting resolution. Responses contain no header. Only parameters are sent as responses.
EXTERNAL CONTROL An error occurs if a command causing a conflicting operation is sent while the sequence, tracking or external control function is working.
PSB-2000 Series User Manual Model inquiry ESR query Event enable STB query SRQ enable Common Clear Reset Completion Wait for completion Local Extension communication Remote mode *ESE *SRE *CLS *RST *OPC *IDN? *ESR? *ESE? *STB? *SRE? *OPC? ----------------- 128 129 129 129 129 129 129 130 *WAI - --- 130 :ADDR - 104 130 :REMOTE :REMOTE? 48 131 Output Voltage Setting (:VOLT) This command sets or inquires about the output voltage.
EXTERNAL CONTROL OVP Setting (:VOLT:PROT) This command sets or inquires about the OVP (over-voltage protection) value. Setting Application example Query Response example Remark :VOLT:PROT Sets the OVP value of a single channel model. :VOLT:PROT:A Sets the OVP value of CH1. :VOLT:PROT:B Sets the OVP value of CH2. The range is from 1.00 to 84.00(PSB-L), 10.0 to 840.0(PSB-H). Two decimal places are valid. :VOLT: PROT 10.10 Sets the OVP value of a single channel model to 10.
PSB-2000 Series User Manual Application example Query Response example Remark The range for single-unit operation is as shown below: PSB-2400L & PSB-2400L2: 0.00 to 41.00 PSB-2800L: 0.00 to 82.00 PSB-2400H: 0.00 to 3.07 PSB-2800H: 0.00 to 6.15 Two decimal places are valid. The setting range changes when the power supplies are used in parallel. Resolution in parallel operation: 100mA Setting range: 0.0 to (total current x 1.025) :CURR 10.10 Sets the output current of a single channel model to 10.
EXTERNAL CONTROL Application example Query Response example Remark The range in single-unit operation is as shown below: PSB-2400L & PSB-2400L2: 1.00 to 42.00 PSB-2800L: 1.00 to 84.00 PSB-2400H: 0.10 to 3.15 PSB-2800H: 0.10 to 6.30 Two decimal places are valid. The setting range changes when the power supplies are used in parallel. Resolution in parallel operation: 100mA Setting range: 0.0 to (total current x 1.05) :CURR:PROT 10.10 Sets the OCP value of a single channel model to 10.10A.
PSB-2000 Series User Manual Response example Remark Inquires about the set output power of a single channel model. :POW:A? Inquires about the set output power of CH1. :POW:B? Inquires about the set output power of CH2. 100 Indicates that the set output power is 100W. When the tracking mode is on, setting CH1 will affect CH2. Setting CH2 in the tracking mode will cause an execution error. OUTPUT ON/OFF (:OUTP) This command turns on or off output.
EXTERNAL CONTROL Hi-Ω ON/OFF(:CONF:HIZ) This command turns on or off the Hi-Ω function. Only applicable to the PSB-L series only. Setting Application example Query Response example Remark :CONF:HIZ is as shown below: 1: Hi-Ω On 0: Hi-Ω Off :CONF:HIZ 1 Activates the Hi-Ω function. :CONF:HIZ? Inquires about the setting. 1 Indicates that the Hi-Ω function is working. The return values of the query have the same function as the setting .
PSB-2000 Series User Manual Application example Query Response example Remark is as shown below: 1: CH1 voltage + current display 2: CH1 voltage + power display 3: CH1 power + current display 4: CH2 voltage + current display 5: CH2 voltage + power display 6: CH2 power + current display 7: Sequence or Off Timer display For a single channel model, use the values 1 to 3 or 7 to specify a display mode. :CONF:DISP 1 Selects the voltage + current display mode.
EXTERNAL CONTROL External Control Setting (:EXT:MOD) This command sets the external control mode. Setting Application example Query Response example Remark :EXT:MOD is as shown below: 0: Settings are controlled from the front panel or via remote control. 1: External voltage control 2: External resistance control :EXT:MOD 1 Selects the external voltage control. :EXT:MOD? Inquires about the setting status. 1 Indicates that external voltage control has been enabled.
PSB-2000 Series User Manual Response example Remark Inquires about the setting. 1 Indicates that external control of the voltage output is enabled. The query return value has the same meaning as the setting . This command causes an error if the sequence function is running. 120 Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176 TestEquipmentDepot.
EXTERNAL CONTROL External Control of the Current Output ON/OFF (:EXT:CURR) This command chooses whether the external control is used to control the output current or if the front panel controls are used to control the output current. Setting Application example Query Response example Remark :EXT:CURR Activates or deactivates external control of the output current of a single channel model. :EXT:CURR:A Activates or deactivates external control of the output current of CH1.
PSB-2000 Series User Manual Response example Remark 1 Indicates that output On/Off with external contacts is working. The query return value has the same meaning as the setting . This command causes an error if the sequence function is running. Off Timer ON/OFF (:TIMER:MOD) This command activates or deactivates the Off Timer. Setting Application example Query Response example Remark :TIMER:MOD is as shown below: 0: Deactivates the Off Timer. 1: Activates the Off Timer.
EXTERNAL CONTROL Delay Function ON/OFF (:DELAY:MOD) This command activates or deactivates the delay function. This function only applies to the PSB-2400L2. Setting Application example Query Response example Remark :DELAY:MOD is as shown below: 0: Deactivates the delay function. (Normal) 1: Activates the delay function. :DELAY:MOD 1 Activates the delay function. :DELAY:MOD? Inquires about the setting. 1 Indicates that the delay function is working.
PSB-2000 Series User Manual Delay Fall Time Setting (:DELAY:FALL) This command sets or inquires about the delay time for turning off output. Setting Application example Query Response example Remark :DELAY:FALL The range is from -9.99 to +10.00 seconds. :DELAY:FALL 0.3 Sets the delay time for turning off output to 0.3 second. :DELAY:FALL? Inquires about the setting. 0.3 Indicates that the delay time for turning off output is set to 0.3 seconds.
EXTERNAL CONTROL Preset Recall (:PRES:CALL) This command recalls and inquires about preset data. Setting Application example Query Response example Remark :PRES:CALL is as shown below: 0: Cancels preset. 1: Calls PRESET 1 data. 2: Calls PRESET 2 data. 3: Calls PRESET 3 data. :PRES:CALL1 Recalls the set values stored in PRESET 1. :PRES:CALL? Inquires about the setting. 1 Indicates that PRESET 1 is selected. The query return value has the same meaning as the setting .
PSB-2000 Series User Manual Sequence Mode Setting (:SEQ:MOD) This command controls a sequence operation. It can start, stop or pause a sequence. Setting Application example Query Response example Remark :SEQ:MOD is as shown below: 0: Stops sequence operation. 1: Pause sequence operation – Waits for start. 2: Runs sequence operation (Executes sequence). :SEQ:MOD 2 Runs the sequence. :SEQ:MOD? Inquires about the setting. 2 Indicates that sequence operation is being executed.
EXTERNAL CONTROL Sequence Start Step Setting (:SEQ:START) This command specifies which step to start from when running a sequence. Setting Application example Query Response example Remark :SEQ:START The range is from 0 to 99. :SEQ:START2 Sets the sequence to start from step no. 2. :SEQ:START? Inquires about the setting. 2 Indicates that the sequence starts from step 2. None Sequencer End Step Setting (:SEQ:END) This command specifies which step to end the sequence on.
PSB-2000 Series User Manual Remark None Sequence Data Transfer (:SEQ:DOWNLOAD) This command transfers the sequence set data. Setting Application example Query Response example Remark 1 :SEQ:DOWNLOAD represents 1609-byte binary sequence set data. :SE:DOWNLOAD#6001600………… LF Transfers an 8-byte header for the binary data, 1600-bytes of actual data, and a 1 byte for the delimiter (total: 1609 bytes). :SEQ:DOWNLOAD? Requests the sequence data.
EXTERNAL CONTROL Standard Event Status Register Inquiry (*ESR?) The function of this command is described in the ―Standard Event Status Register‖ in the following section. Standard Event Status Enable Register Setting (*ESE) The function of this command is described in ―Standard Event Status Enable register‖ in the following section. Status Byte Inquiry (*STB?) The function of this command is described in ―Status Byte Register‖ in the following section.
PSB-2000 Series User Manual Command Completion (*OPC) This command sets bit 0 of the standard event status register (ESR) when all current overlapped commands have been processed. Setting Query *OPC Sets bit 0 of the ESR when all current overlapped commands are complete. A SRQ is generated depending on the status of the ESE register and SRE register. *OPC? The value “1” is returned when all current commands are completed. Wait for Completion (*WAI) This command waits for command completion.
EXTERNAL CONTROL Remote/Local Setting (:REMOTE) This command sets or inquires about the remote/local status. Setting Application example Query Response example Remark :REMOTE is as shown below: 0: Local status (Normal manual operation) 1: Remote status 2: Local lockout remote status (Cannot return to the local status through key operation.) :REMOTE0 Sets the unit to local status. :REMOTE? 1 Indicates that the unit is in the remote status.
PSB-2000 Series User Manual Registers Introduction The PSB power supply unit has registers that conform to the status reporting specified in IEEE488.2.
EXTERNAL CONTROL Status Byte Register (STB, SRE) Bit Data Item Description 7 128 6 64 Unused. Service request Message summary 5 32 0 SRQ RQS MSS ESB 4 16 MAV 3 2 1 8 4 2 0 0 LERR 0 1 TMO Summary Item Standard event summary Output message available Unused. Unused. Local bus error Local bus Time out Initial STB value 0 Initial SRE value 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Each bit is masked when it is set to ―0‖. (0 is the default setting.
PSB-2000 Series User Manual Query command Response example *STB? Enables the MAV and ESB bits since the value of 48 ( 00110000 in binary) sets bit 4(MAV) and 5(ESB). *SRE? 48 The masking value set with this command remains valid until the setting is changed or the power is turned off. All bits are masked (0) when the power is turned on, regardless of the previous setting. Returns the status byte register and MSS. Setting command Query command Response example None. Query only.
EXTERNAL CONTROL Item *ESE Description Sets or inquires about the standard event status enable register. Setting command *ESR? *ESE The range is from 0 to 255. Application example *ESE 48 Enables the CME (bit 5) and EXE (bit 4) of the Event Status register. Query command *ESE? Response example 48 The masking set with this command remains valid until the setting is changed or power is turned off. All bits are masked (0) when power is turned on, regardless of the previous setting.
PSB-2000 Series User Manual (SRE) is set 1 at this time, bit 6 (MSS) of the status byte register is set to 1 and a service request (SRQ) is generated. NOTE Bit 5 ESB Standard event status register summary Bit 4 MAV Message available Bit 1 LERR Local bus execution error Bit 0 TMO Local bus time-out An SRQ is issued through the GPIB interface only.
EXTERNAL CONTROL When receiving the *CLS command, the PSB 2000 series power supply unit clears the standard event register and the status byte register. When MAV occurs. The MAV bit is cleared when all the data is read out from the output queue. The output queue is not cleared by the *CLS command. When the event register and MAV are cleared completely, MSS in bit 6 is also cleared.
PSB-2000 Series User Manual *RST (Reset command) 138 The GPIB buffer, output queue and input queued commands are cleared. The interface status (specified talker or listener status) is cleared. The SRQ and status byte register are cleared. The remote status and LLO (local lock out) setting are cleared and the power supply unit enters the local state. Panel setting remains unchanged. Responses to the IEEE488.
EXTERNAL CONTROL Turning on power When power is turned on again, the statuses are as again shown below: The specified talker or listener status is cleared. The GPIB buffer, output queue and input queued commands are cleared. The SRQ, status byte register and mask settings are cleared. The unit enters the local status. The LLO (local lock out) set before turning off power is cleared. Panel setting at the time when power is turned off remains unchanged.
PSB-2000 Series User Manual Remote/Local Function Introduction The remote/local function is controlled by the system controller and with the FAST key on the PSB 2000 series power supply unit. (This key serves as the FAST, LOCK and LOCAL keys.) The PSB 2000 series power supply unit always resides in the local, remote, or remote with local lockout state. Local The PSB 2000 series power supply unit enters the local status in either of the following cases: Remote When power is turned on.
EXTERNAL CONTROL Responses to Multi-Line Message Commands The table below shows the types of multi-line message commands and the responses to the commands. Introduction Type Name Description Response Universal commands DCL SPE SPD PPU Clears the GP-IB buffer. Establishes the serial polling state. Clears serial polling. Clears parallel polling. Brings all devices into the local lockout status to disable manual operation. Cancels the specified listener status.
PSB-2000 Series User Manual APPENDIX Trouble Shooting Overview This section shows some possible problems that may arise and the solutions to some of these problems. Most problems may be solved by rechecking connections, settings or some other simple solution. Contact your nearest distributor if problems are not eliminated or improved using the trouble shooting guide. Never open the case to check the inside.
APPENDIX ・On/Off with the external contacts is selected. ・The channel output key is not selected or an incorrect channel is selected for output. ・Keys are locked. “OVP” is displayed when the OUTPUT key is pressed. “OCP” is displayed when the OUTPUT key is pressed. Cannot raise the current up to the set current value. Output is unstable. Output voltage does not fall. current control with external voltage or resistance.” ・See page 81, “Output On/Off with external contacts”. ・See page 44, “How to output”.
PSB-2000 Series User Manual Maintenance Introduction The PSB Series power supply unit employs a fan for forced cooling. Clean the dust filter inside the front grill periodically to maintain the cooling efficiency. Pull the front grill while pressing the notch in the upper part to detach the grill. Clean the filter with water. Before you remove the grill, turn off the POWER switch and disconnect the AC power cable to turn off the unit. CAUTION Dry the filter completely before re-attaching it.
APPENDIX PSB-2800LS PSB-2800LS Pull frontward while pressing here. Dust filter Front grill 145 Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176 TestEquipmentDepot.
PSB-2000 Series User Manual Dimensions PSB--2400L, PSB-2400L2, PSB-2800L 9 124 10 209 9 12.8 290 146 35.
APPENDIX PSB-2800LS 9 124 10 209 9 290 35.7 Φ6.5 82.
PSB-2000 Series User Manual 10 124 9 PSB-2400H, PSB-2800H 209 12.
APPENDIX Specifications Output Model PSB-2400L PSB-2800L PSB-2400L2 PSB-2800LS Rated output voltage 80.00V 80.00V 80.00V×2CH 80.00V Setting accuracy 0.1% setting ±2 digit (23ºC ±5ºC) Resolution 10mV Display accuracy 0.2% reading ±2 digit (23ºC ±5ºC) Rated output current 1 40.00A 80.00A 40.00A×2CH 80.00A Setting accuracy 0.2% setting ±2 digit (23ºC ±5ºC) Resolution 10mA Display accuracy 0.
PSB-2000 Series User Manual Input PSB-2800L, PSB-2400L2, PSB-2800LS, PSB-2800H Input voltage AC100V to 240V, single-phase, frequency: 50Hz or 60Hz Power consumption 3 560VA 1120VA Power factor 4 0.99 Rush current 35A max. 70A max. 3, 4 At the rated output voltage and AC100V input Model PSB-2400L, PSB-2400H Constant-Voltage Characteristics Model Source fluctuation 5 Load fluctuation 6 Ripple noise (p-p) 7 Ripple noise (rms) 8 Transient response (typ.) 9 Rise time (typ.) 10 Fall time (typ.
APPENDIX Constant-Current Characteristics Model Source fluctuation 5 Load fluctuation 13 Ripple noise (rms) Temperature coefficient (typ.) 12 PSB-2400L PSB-2800L PSB-2400L2 0.01% ±2mV of rated voltage 0.01% ±3mV of rated voltage 30mA 60mA 30mA ±100ppm/ºC (after 30-minute warming up) Model Source fluctuation 5 Load fluctuation 13 Ripple noise (rms) Temperature coefficient (typ.) 12 PSB-2400H PSB-2800H 0.05% ±10mV of rated voltage 0.
PSB-2000 Series User Manual Output current: Approx. 0A to rated output current Constant-current (CC) control with external resistance For external resistance: 0Ωto 10kΩ External On/Off control On/Off at contact. Short: On, Open: Off Approx. 0V to 10V for 0V to rated output voltage. Output voltage monitor signal Output current monitor signal Constant-voltage (CV) status signal Constant-current (CC) status signal Alarm signal output Alarm signal input Approx. 0V to 10V for 0A to rated output current.
APPENDIX Protective functions Over-voltage protection (OVP): Stops oscillation when the output voltage exceeds 110% of Fixed 15 rated voltage. (Output Off) Presettable range: 1V to 84V on front panel.(PSB-L series) Over-voltage protection (OVP): Presettable range: 1V to 840V on front panel.(PSB-H Variable 16 series) Stops oscillation when OVP works. (Output Off) Over-current protection (OCP): Stops oscillation when output current exceeds 110% of Fixed 15 rated current.
PSB-2000 Series User Manual Applicable Standards EN61010-1 2nd edition (2001) Indoor use Altitude up to 2000m LVD Transient overvoltage: Overvoltage category II Pollution Degree 2 EN61000-3-2 clause 7.1 class A EN61000-3-3 clause 5 EMS (Min) EN61326-1:2006 EMC EMI(Class A) EN61326-1:2006 The standards are applicable for the product marked CE on the rear panel only and not for modified products.
APPENDIX Sequence item: Power Sequence item: Output Sequence item: Time Key lock function One-control operation Output status Sequence operation status Off-timer operation status System Address Personal Computer Address 410W/820W OFF 1sec OFF OFF Initialized when power is turned off. ×(Stop status) ×(Non operating status) 1 3 O O O × O × × × O O Parallel/Serial Operation Setting Table PSB-2400H Single Parallel 400H 400H x 2 400W 800W SLOW 100mV FAST 10V Voltage Setting Range 0V to 820V Min.
PSB-2000 Series User Manual PSB-2800H Single Parallel 800H 800H x 2 800W 1600W SLOW 100mV FAST 10V Voltage Setting Range 0V to 820V Min. display digit 100mV SLOW 10mA 100mA FAST 1A 1A Current Setting Range 0A to 6.15A 0A to 12.3A Min. display digit 10mA 100mA SLOW 10W 20W FAST 100W 200W Power Setting Range 10W to 820W 20W to 1640W Min. display digit 1W SLOW 1V FAST 100V OVP Setting Range 10V to 840V Min. display digit 100mV SLOW 10mA 20mA FAST 1A 2A Range 0.1A to 6.3A 0.2A to 12.6A Min.
APPENDIX PSB-2400L (Part 1/2) Item Single 2400L 2400L x 2 Parallel 2400L x 3 2400L + 2800L 1200W 2400L x 4 400W 800W 1600W Voltage Setting SLOW 10mV FAST 1V Range 0V to 82V Min. display digit 10mV Current Setting SLOW 10mA 100mA 90mA 80mA FAST 1A 10A 9A 8A Range 0A-41A 0A-82A 0A-123A 0A-164A Min. display digit 10mA 100mA Power Setting SLOW 10W 100W FAST 100W 1000W Range 10W-410W 20W-820W 30W-1230W 40W-1640W Min. display digit 1W OVP Setting SLOW 100mV FAST 10V Range 1V-84V Min.
PSB-2000 Series User Manual PSB-2400L (Part 2/2) Item Parallel Series 2400L+ 2800L x 2400L + 2400L 2400L + 2800L x 2400L + 2400L 2 + 2800L x 2 3 2000W 2400W 2800W 800W Voltage Setting SLOW 10mV FAST 1V Range 0V to 82V Min. display digit 10mV Current Setting SLOW 100mA 60mA 70mA 10mA FAST 10A 6A 7A 1A Range 0A-205A 0A-246A 0A-287A 0A-41A Min. display digit 100mA 10mA Power Setting SLOW 100W 10W FAST 1000W 100W Range 50W-2050W 60W-2460W 70W-2870W 10W-410W Min.
APPENDIX PSB-2800L Item Single 800L 800W 800L x 2 1600W Parallel 800L x 3 2400W 800L x 4 3200W Series 800L + 800L 1600W Voltage Setting SLOW 10mV FAST 1V Range 0V-82V Min. display 10mV digit Current Setting SLOW 10mA 100mA 90mA 80mA 10mA FAST 1A 10A 9A 8A 1A Range 0A-82A 0A-164A 0A-246A 0A-328A 0A-82A Min. display 10mA 100mA 10mA digit Power Setting SLOW 10W 100W 10W FAST 100W 1000W 100W Range 10W-820W 20W-1640W 30W-2460W 40W-3280W 10W-820W Min.
PSB-2000 Series User Manual Declaration of Conformity We GOOD WILL INSTRUMENT CO., LTD. (1) No.7-1, Jhongsing Rd., Tucheng City, Taipei County, Taiwan (2) No.